For construction workers who use temporary power, extension cords and portable tools: stay clear of live circuits, use ground-fault protection, inspect and run cords correctly, and respect tagged controls.
Need proof of training? The full course (20 min) adds practice questions, a job scenario, the final quiz and a certificate your employer can verify.
Take the courseYou must not be put to work so close to any part of an electric power circuit that you could contact it, unless you are protected in one of two ways:
Your employer must find out, by asking, looking or using instruments, whether any energized circuit, exposed or concealed, is located where the work could bring a person, a tool or a machine into contact with it. Where such a circuit exists, your employer must post warning signs and tell you where the lines are, the hazards, and the protective measures to take.
Reference: 29 CFR 1926.416(a)(1) · 29 CFR 1926.416(a)(3) · 29 CFR 1926.416(a)(2)
Live parts of electric equipment operating at 50 volts or more must be guarded against accidental contact, for example by cabinets or other enclosures.
Entrances to rooms and other guarded locations with exposed live parts must be marked with warning signs forbidding unqualified persons to enter. A qualified person is one familiar with the construction and operation of the equipment and the hazards involved. If that is not you, stay out.
When energized parts of electrical equipment are exposed, barriers or other guarding must keep the workspace in front of that equipment from being used as a passageway. Do not cut through it, and do not move the barrier to get by.
Reference: 29 CFR 1926.403(i)(2)(i) · 29 CFR 1926.403(i)(2)(iii) · 29 CFR 1926.449 "Qualified person" · 29 CFR 1926.416(b)(1)
On a construction site your employer must protect you with one of two systems: ground-fault circuit interrupters (GFCIs) or an assured equipment grounding conductor program.
All 120-volt, single-phase, 15- and 20-ampere receptacle outlets on the site that are not part of the permanent wiring of the building or structure, and that workers are using, must have approved GFCIs for personnel protection. Think spider boxes, temporary power panels and similar setups.
Portable lighting used in wet or conductive locations, such as drums, tanks and vessels, must run at 12 volts or less. 120-volt lights may be used there only if protected by a GFCI.
Reference: 29 CFR 1926.404(b)(1)(i) · 29 CFR 1926.404(b)(1)(ii) · 29 CFR 1926.405(a)(2)(ii)(G)
If your site uses an assured equipment grounding conductor program instead of GFCIs, cords and cord-and-plug tools are covered by inspections and tests.
Each cord set, plug, receptacle of a cord set, and cord-and-plug tool must be visually inspected before each day's use (except cord sets and receptacles that are fixed and not exposed to damage). Look for:
Anything found damaged or defective must not be used until repaired.
Required tests are done before first use, before equipment goes back into service after repairs, before equipment is used after an incident that may have caused damage (for example, when a cord set is run over), and at intervals not to exceed 3 months (6 months for cord sets and receptacles that are fixed and not exposed to damage). Tests must be recorded, and the record must be kept by logs, color coding, or other effective means until it is replaced by a more current record. Your employer must not make available, or let you use, equipment that has not met the program's requirements. Learn how your site marks equipment that has passed.
Reference: 29 CFR 1926.404(b)(1)(iii)(C) · 29 CFR 1926.404(b)(1)(iii)(E)(1) · 29 CFR 1926.404(b)(1)(iii)(E)(2) · 29 CFR 1926.404(b)(1)(iii)(E)(3) · 29 CFR 1926.404(b)(1)(iii)(E)(4) · 29 CFR 1926.404(b)(1)(iii)(F) · 29 CFR 1926.404(b)(1)(iii)(G)
Extension cords used with portable electric tools must be three-wire type and designed for hard or extra-hard usage.
Reference: 29 CFR 1926.405(a)(2)(ii)(J) · 29 CFR 1926.416(e)(1) · 29 CFR 1926.405(g)(2)(iii) · 29 CFR 1926.405(a)(2)(ii)(I) · 29 CFR 1926.416(e)(2) · 29 CFR 1926.416(b)(2) · 29 CFR 1926.405(a)(2)(ii)(F)
The path to ground from circuits, equipment and enclosures must be permanent and continuous. On a cord-and-plug tool, the third (grounding) pin is part of that path.
Exposed metal parts of cord-and-plug equipment that may become energized must be grounded on hand-held motor-operated tools, among other types.
So if a hand-held power tool has a two-prong plug, check that it is marked as double insulated. If a three-prong tool or cord has had its ground pin cut off, its path to ground is no longer continuous. Do not use it; report it.
Reference: 29 CFR 1926.404(f)(6) · 29 CFR 1926.404(f)(7)(iv) · 29 CFR 1926.404(f)(7)(iv)(C)(1) · 29 CFR 1926.404(f)(7)(iv)(C)(6)
When equipment or circuits are being worked on, the rules require tags:
Reference: 29 CFR 1926.417(a) · 29 CFR 1926.417(b) · 29 CFR 1926.417(c)
Need proof of training? The full course (20 min) adds practice questions, a job scenario, the final quiz and a certificate your employer can verify.
Take the courseFact-checked against the regulation text on October 09, 2026. This certificate records completion of awareness training based on OSHA 29 CFR 1926.400, 1926.403, 1926.404, 1926.405, 1926.416, 1926.417 and 1926.449. It is not an OSHA card or license, and it does not make anyone a qualified person for electrical work. Subpart K has no training paragraph of its own, and this certificate does not by itself meet the general training requirement of 29 CFR 1926.21(b)(2). Your employer must still instruct you in the recognition and avoidance of unsafe conditions and the regulations applicable to your work environment to control or eliminate any hazards.
This guide explains the rule in plain words. Always read the regulation itself and your employer's site-specific procedures.