Electrical Safety-Related Work Practices for Workers
For general industry workers who work on, near or with electrical equipment but are not qualified persons: know your limits, treat unlocked parts as live, keep away from overhead lines, work safely near exposed parts, and use the right protection and warnings.
Need proof of training? The full course (25 min) adds practice questions, a job scenario, the final quiz and a certificate your employer can verify.
Take the courseSwitched off, still live
What happened. In October 2004, a 32-year-old maintenance worker was changing a broken bulb in a ceiling light. He worked at an assisted living facility in Washington State. He turned off the wall switch and taped it in the off position. Then he climbed into the attic to reach the fixture.
Holding the fixture in one hand, he touched the bulb base with a tool that was not insulated. The fixture was still energized. It was on a separate emergency lighting circuit that his building plans did not show. He was electrocuted.
What went wrong
- Not qualified. He was not trained or authorized to do electrical work.
- Off is not dead. A switch taped off is not lockout, and no one tested the circuit.
- Plans, not tests. The drawings did not show the real wiring.
The investigators' rule of thumb: if you can't test, let it rest.
Reference: WA FACE report 04WA080 (2008) · 29 CFR 1910.333(b)(1) · 29 CFR 1910.333(b)(2)(iv)(B) · 29 CFR 1910.333(c)(2)
Off is not the same as safe
Deenergize first
Live parts you may be exposed to must be deenergized before you work on or near them. The employer may skip this only if it can show one of two things. Deenergizing creates added or increased hazards, or it is infeasible because of equipment design or operating limits. Live parts under 50 volts to ground need not be deenergized. That holds only if there is no increased exposure to electrical burns or to explosion from electric arcs.
Switched off but not locked or tagged? Treat it as live
Parts that have been deenergized but not locked out or tagged under the procedure must be treated as energized. Someone may be exposed to contact with parts of fixed equipment or circuits that have been deenergized. While they are, the circuits feeding those parts must be locked out, tagged, or both.
- A push button, selector switch or interlock may not be the only means of deenergizing. Pressing Stop is not lockout. Interlocks for electric equipment may not be used as a substitute for lockout and tagging procedures.
- Stored electric energy that might endanger people must be released.
- Your employer must keep a written copy of the lockout and tagging procedures and make it available for you to inspect.
Reference: 29 CFR 1910.333(a)(1) · 29 CFR 1910.333(b)(1) · 29 CFR 1910.333(b)(2) · 29 CFR 1910.333(b)(2)(i) · 29 CFR 1910.333(b)(2)(ii)(B) · 29 CFR 1910.333(b)(2)(ii)(C)
Want the certificate? Practice this rule with real job scenarios and get a certificate your employer can verify.
Start the courseKeep yourself and your tools back
Before work starts near overhead lines, the lines must be deenergized and grounded, or other protective measures must be in place.
Your distances as an unqualified person
When you work in an elevated position near overhead lines, watch your distance. You and the longest conductive object you may contact must not come closer to any unguarded, energized line than:
When you work on the ground near overhead lines, you may not bring any conductive object closer than those same distances.
Reference: 29 CFR 1910.333(c)(3) · 29 CFR 1910.333(c)(3)(i)(A) · 29 CFR 1910.333(c)(3)(i)(A)(1) · 29 CFR 1910.333(c)(3)(i)(A)(2) · 29 CFR 1910.333(c)(3)(i)(B) · 29 CFR 1910.333(c)(3)(i)(B) Note
Light, reach, jewelry, ladders and cleaning
- Light first. Do not enter a space with exposed energized parts unless there is enough light to do the work safely.
- No blind reaching. Do not reach blindly into areas that may contain energized parts.
- Conductive things you hold, like pipe, conduit, wire or metal tools, must be handled so they cannot contact exposed energized parts.
- Ladders must have nonconductive side rails where you or the ladder could contact exposed energized parts.
- Jewelry and clothing: do not wear conductive items that might contact exposed energized parts. These include watch bands, bracelets, rings, key chains, necklaces, metalized aprons, cloth with conductive thread and metal headgear. They may be worn if covering, wrapping or other insulating means makes them nonconductive.
- Housekeeping: do not clean so close to live parts that contact is possible unless adequate safeguards, such as insulating equipment or barriers, are provided. Do not use conductive cleaning materials near energized parts, such as steel wool, metalized cloth, silicon carbide or conductive liquids. The exception is when procedures that prevent electrical contact are followed.
Reference: 29 CFR 1910.333(c)(4)(i) · 29 CFR 1910.333(c)(4)(ii) · 29 CFR 1910.333(c)(6) · 29 CFR 1910.333(c)(7) · 29 CFR 1910.333(c)(8) · 29 CFR 1910.333(c)(9)
Common test questions
Who is a qualified person under OSHA's electrical work practice rules?
Someone trained to avoid the electrical hazards of working on or near exposed energized parts. Workers with little or no such training are unqualified persons.
Rule: 29 CFR 1910.331(a)
Is a switched-off circuit safe to work on?
Not yet. Parts that are deenergized but not locked out or tagged must be treated as energized, and a qualified person must use test equipment to verify they are deenergized.
Rule: 29 CFR 1910.333(b)(1), (b)(2)(iv)(B)
How close can an unqualified worker get to an overhead power line?
10 feet for lines at 50 kV to ground or less, plus 4 inches for every 10 kV over 50 kV. The distance includes the longest conductive object the worker may contact.
Rule: 29 CFR 1910.333(c)(3)(i)(A)
Who removes a lock and tag after electrical work?
The employee who applied it, or someone under their direct supervision. If that employee is absent, a designated qualified person may remove it only after the employer confirms the employee is not at the workplace and makes sure they know before they resume work.
Rule: 29 CFR 1910.333(b)(2)(v)(C)
Need proof of training? The full course (25 min) adds practice questions, a job scenario, the final quiz and a certificate your employer can verify.
Take the courseSources
Fact-checked against the regulation text on November 11, 2026. This certificate records completion of awareness training based on OSHA 29 CFR 1910.331–1910.335. It is not an OSHA card or license, it does not make you a qualified person, and it does not by itself meet the training requirements of 29 CFR 1910.332. Your employer must still train you, by classroom or on-the-job training matched to the risk to you, in the safety-related work practices that pertain to your job assignment and in any other electrically related safety practices necessary for your safety.
This guide explains the rule in plain words. Always read the regulation itself and your employer's site-specific procedures.