For general industry workers who work on, near or with electrical equipment but are not qualified persons: know your limits, treat unlocked parts as live, keep away from overhead lines, work safely near exposed parts, and use the right protection and warnings.

Based on OSHA 29 CFR 1910.331–1910.335 (electrical safety-related work practices, general industry) · about 9 min read

Need proof of training? The full course (25 min) adds practice questions, a job scenario, the final quiz and a certificate your employer can verify.

Take the course
Know your limits

Qualified and unqualified persons

Two kinds of workers

Qualified personHas training in avoiding the electrical hazards of working on or near exposed energized parts. At a minimum, they are trained to tell exposed live parts from other parts, to determine the nominal voltage of exposed live parts, and to know the clearance distances for the voltages they will be exposed to.
Unqualified personHas little or no such training. That is most likely you.

Your training

If your job exposes you to a risk of electric shock, you must be trained in the safety-related work practices that apply to your job, plus any other electrically related safety practices you need for your safety. Training is classroom or on-the-job, and how much you get depends on the risk to you.

What only qualified persons may do

Reference: 29 CFR 1910.331(a) · 29 CFR 1910.332(b)(1) · 29 CFR 1910.332(b)(2) · 29 CFR 1910.332(b)(3)(i) · 29 CFR 1910.332(b)(3)(ii) · 29 CFR 1910.332(b)(3)(iii) · 29 CFR 1910.332(c) · 29 CFR 1910.333(c)(2) · 29 CFR 1910.333(c)(10) · 29 CFR 1910.332(a)

Deenergized, locked, tagged, tested

Off is not the same as safe

Deenergize first

Live parts you may be exposed to must be deenergized before you work on or near them. The employer may skip this only if it can show deenergizing creates additional or increased hazards, or is infeasible because of equipment design or operational limits. Live parts under 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion from electric arcs.

Switched off but not locked or tagged? Treat it as live

Parts that have been deenergized but not locked out or tagged under the procedure must be treated as energized. While anyone is exposed to contact with parts of fixed equipment or circuits that have been deenergized, the circuits feeding them must be locked out, tagged, or both.

Reference: 29 CFR 1910.333(a)(1) · 29 CFR 1910.333(b)(1) · 29 CFR 1910.333(b)(2) · 29 CFR 1910.333(b)(2)(i) · 29 CFR 1910.333(b)(2)(ii)(B) · 29 CFR 1910.333(b)(2)(ii)(C)

Deenergized, locked, tagged, tested

Locks and tags

A lock and a tag on each disconnect

A lock and a tag go on each disconnecting means used to deenergize the circuits and equipment being worked on. Each tag carries a statement prohibiting unauthorized operation of the disconnecting means and removal of the tag. If you see a lock or tag on a disconnect, do not operate it and do not remove anything.

The two exceptions

Tag without a lockAllowed if a lock cannot be applied, or if the employer can show tagging gives safety equal to a lock. The tag must be backed up by at least one additional safety measure that gives safety equal to a lock.
Lock without a tagAllowed only when all three are true: only one circuit or piece of equipment is deenergized, the lockout does not extend beyond the work shift, and the employees exposed to reenergizing hazards are familiar with this procedure.

Reference: 29 CFR 1910.333(b)(2)(iii)(A) · 29 CFR 1910.333(b)(2)(iii)(B) · 29 CFR 1910.333(b)(2)(iii)(C) · 29 CFR 1910.333(b)(2)(iii)(D) · 29 CFR 1910.333(b)(2)(iii)(E)(1) · 29 CFR 1910.333(b)(2)(iii)(E)(2) · 29 CFR 1910.333(b)(2)(iii)(E)(3)

Deenergized, locked, tagged, tested

Testing, and turning the power back on

Before anything is worked as deenergized

Until those checks are done, the circuit cannot be considered and worked as deenergized. Wait for them.

Before the power comes back, in this order

  1. A qualified person conducts tests and visual inspections, as necessary, to verify that all tools, electrical jumpers, shorts, grounds and other such devices have been removed.
  2. Employees exposed to reenergizing hazards are warned to stay clear. When you get that warning, move away.
  3. Each lock and tag is removed by the employee who applied it, or under that employee's direct supervision. If that employee is absent from the workplace, a qualified person designated for the task may remove it, but only if the employer makes sure the employee is not available at the workplace, and makes sure the employee knows the lock or tag was removed before they resume work there.
  4. There is a visual check that all employees are clear of the circuits and equipment.

These steps apply before circuits or equipment are reenergized, even temporarily.

Reference: 29 CFR 1910.333(b)(2)(iv) · 29 CFR 1910.333(b)(2)(iv)(A) · 29 CFR 1910.333(b)(2)(iv)(B) · 29 CFR 1910.333(b)(2)(v)(B) · 29 CFR 1910.333(b)(2)(v)(C) · 29 CFR 1910.333(b)(2)(v)(C)(1) · 29 CFR 1910.333(b)(2)(v)(C)(2) · 29 CFR 1910.333(b)(2)(v)(D) · 29 CFR 1910.333(b)(2)(v) · 29 CFR 1910.333(b)(2)(v)(A)

Overhead power lines

Keep yourself and your tools back

Before work starts near overhead lines, the lines must be deenergized and grounded, or other protective measures must be in place.

Your distances as an unqualified person

When you work in an elevated position near overhead lines, you and the longest conductive object you may contact must not come closer to any unguarded, energized overhead line than:

50 kV to ground or below10 feet
Over 50 kV to ground10 feet plus 4 inches for every 10 kV over 50 kV

When you work on the ground near overhead lines, you may not bring any conductive object closer than those same distances.

What counts as conductive? For the voltages normally found on overhead power lines, any object that does not have an insulating rating for the voltage involved is considered conductive. Ladders, pipe, paint-roller poles and long tools count as conductive unless they have that insulating rating.

Reference: 29 CFR 1910.333(c)(3) · 29 CFR 1910.333(c)(3)(i)(A) · 29 CFR 1910.333(c)(3)(i)(A)(1) · 29 CFR 1910.333(c)(3)(i)(A)(2) · 29 CFR 1910.333(c)(3)(i)(B) · 29 CFR 1910.333(c)(3)(i)(B) Note

Overhead power lines

Cranes, lifts and trucks near lines

Any vehicle or mechanical equipment that can raise parts of its structure near energized overhead lines, such as a boom truck, aerial lift or dump body, must keep a clearance of 10 feet. Above 50 kV, add 4 inches for every 10 kV over that voltage.

The clearance may be reduced only under narrow conditions. For example, a vehicle in transit with its structure lowered may come within 4 feet (more above 50 kV).

If you are on the ground

Do not touch the vehicle, equipment or any of its attachments unless you are using protective equipment rated for the voltage, or the equipment is located so no uninsulated part of its structure can come closer to the line than the required clearance.

Reference: 29 CFR 1910.333(c)(3)(iii)(A) · 29 CFR 1910.333(c)(3)(iii)(A)(1) · 29 CFR 1910.333(c)(3)(iii)(B) · 29 CFR 1910.333(c)(3)(iii)(B)(1) · 29 CFR 1910.333(c)(3)(iii)(B)(2)

Near exposed live parts

Light, reach, jewelry, ladders and cleaning

Reference: 29 CFR 1910.333(c)(4)(i) · 29 CFR 1910.333(c)(4)(ii) · 29 CFR 1910.333(c)(6) · 29 CFR 1910.333(c)(7) · 29 CFR 1910.333(c)(8) · 29 CFR 1910.333(c)(9)

Protection and warnings

Protective equipment and insulated tools

Reference: 29 CFR 1910.335(a)(1)(i) · 29 CFR 1910.335(a)(1)(ii) · 29 CFR 1910.335(a)(1)(iv) · 29 CFR 1910.335(a)(1)(v) · 29 CFR 1910.335(a)(2)(i) · 29 CFR 1910.335(a)(2)(ii) · 29 CFR 1910.333(c)(5)

Protection and warnings

Signs, barricades and attendants

These alerting techniques warn you away from electrical hazards. Respect them.

Signs, symbols and tagsUsed where necessary to warn employees about electrical hazards.
BarricadesUsed with safety signs where access to work areas with uninsulated energized parts must be prevented or limited. Conductive barricades may not be used where they might cause an electrical contact hazard.
AttendantsIf signs and barricades do not give enough warning and protection, an attendant is stationed to warn and protect employees.
Good practice: do not step over a barricade or move it to take a shortcut, and follow an attendant's directions.

Reference: 29 CFR 1910.335(b)(1) · 29 CFR 1910.335(b)(2) · 29 CFR 1910.335(b)(3)

Need proof of training? The full course (25 min) adds practice questions, a job scenario, the final quiz and a certificate your employer can verify.

Take the course

Sources

Fact-checked against the regulation text on October 09, 2026. This certificate records completion of awareness training based on OSHA 29 CFR 1910.331–1910.335. It is not an OSHA card or license, it does not make you a qualified person, and it does not by itself meet the training requirements of 29 CFR 1910.332. Your employer must still train you, by classroom or on-the-job training matched to the risk to you, in the safety-related work practices that pertain to your job assignment and in any other electrically related safety practices necessary for your safety.