For workers who store, pour, dispense and use flammable liquids such as gasoline and solvents: recognize a flammable liquid, use the right container, store it within the limits, transfer it without a spark, and fuel equipment safely.

Based on OSHA 29 CFR 1926.152 (construction) and 29 CFR 1910.106 (general industry) · about 7 min read

Need proof of training? The full course (20 min) adds practice questions, a job scenario, the final quiz and a certificate your employer can verify.

Take the course
What is a flammable liquid?

Flashpoint and the four categories

Flashpoint

The flashpoint is the lowest temperature at which a liquid gives off enough vapor to form an ignitable mixture with the air near its surface.

Flammable liquid

Any liquid with a flashpoint at or below 199.4 °F (93 °C) is a flammable liquid. They are divided into four categories:

Category 1Flashpoint below 73.4 °F (23 °C) and boiling point at or below 95 °F (35 °C)
Category 2Flashpoint below 73.4 °F (23 °C) and boiling point above 95 °F (35 °C)
Category 3Flashpoint at or above 73.4 °F (23 °C) and at or below 140 °F (60 °C)
Category 4Flashpoint above 140 °F (60 °C) and at or below 199.4 °F (93 °C)

Construction uses the same four categories: 1926.152 applies to flammable liquids with a flashpoint at or below 199.4 °F (93 °C), and 1926.155(h) defines Categories 1 to 4 the same way.

Many rules in this course apply to Categories 1, 2 and 3. Check the label or Safety Data Sheet for the flashpoint and category.

Reference: 29 CFR 1910.106(a)(14) · 29 CFR 1910.106(a)(19) · 29 CFR 1910.106(a)(19)(i) · 29 CFR 1910.106(a)(19)(ii) · 29 CFR 1910.106(a)(19)(iii) · 29 CFR 1910.106(a)(19)(iv) · 29 CFR 1926.152(h) · 29 CFR 1926.155(h)

Containers

Approved containers, kept closed

On a construction site

What a safety can is

General industry (1910.106(a)(29)): an approved container of not more than 5 gallons, with a spring-closing lid and spout cover, designed to safely relieve internal pressure when exposed to fire.

Construction (1926.155(l)): an approved closed container of not more than 5 gallons with a flash-arresting screen, spring-closing lid and spout cover, designed to safely relieve internal pressure when exposed to fire.

Keep it closed

On a construction site, keep Category 1, 2 and 3 flammable liquids in closed containers when not actually in use. In general industry, the same applies to Category 1 and 2 liquids and Category 3 liquids with a flashpoint below 100 °F: covered containers when not in use.

Not in the way out

Never store flammable liquids in exits, stairways or areas normally used for the safe passage of people (construction, 1926.152(a)(2)). General industry has the same rule: flammable liquids shall not be stored so as to limit use of exits, stairways, or areas normally used for the safe egress of people (1910.106(d)(5)(i)).

Reference: 29 CFR 1926.152(a)(1) · 29 CFR 1910.106(a)(29) · 29 CFR 1926.152(f)(1) · 29 CFR 1910.106(e)(2)(iv)(a) · 29 CFR 1926.152(a)(2) · 29 CFR 1926.155(l) · 29 CFR 1910.106(d)(5)(i)

Storage limits and cabinets

How much, and where

Construction sites (1926.152)

Plants where flammable liquids are incidental to the business (1910.106)

Outside a storage room or cabinet, in a building or any one fire area, the limit is:

A storage cabinet holds not more than 60 gallons of Category 1, 2 or 3, or 120 gallons of Category 4, and is labeled "Flammable-Keep Fire Away."

No flames, no smoking (general industry, 1910.106(d)(7)(iii)): open flames and smoking are not permitted in flammable liquid storage areas.

Reference: 29 CFR 1926.152(b)(1) · 29 CFR 1926.152(b)(2) · 29 CFR 1926.152(b)(2)(iii) · 29 CFR 1926.152(b)(3) · 29 CFR 1910.106(d)(3)(i) · 29 CFR 1910.106(d)(3)(ii) · 29 CFR 1910.106(e)(2)(ii)(b) · 29 CFR 1910.106(d)(7)(iii)

Transferring and using

Bond, transfer the right way, keep ignition away

Bond before you pour

On a construction site (1926.152(e)(2)), transfer Category 1, 2 or 3 liquids from one container to another only when the containers are electrically interconnected (bonded).

In general industry (1910.106(e)(6)(ii)), Category 1 or 2 liquids, or Category 3 liquids with a flashpoint below 100 °F (37.8 °C), shall not be dispensed into containers unless the nozzle and container are electrically interconnected.

Allowed ways to transfer on a construction site (1926.152(e)(3))

Air pressure on the container or portable tank is prohibited as a way to transfer.

In general industry (1910.106(e)(2)(iv)(d)), transfers within a building follow the same list, except that the last item reads "from a container or portable tanks by gravity through an approved self-closing valve." Transferring by air pressure on the container or portable tanks is prohibited there too.

Keep ignition sources away

Spills

On a construction site, leakage or spillage must be disposed of promptly and safely (1926.152(f)(2)). In general industry, where flammable liquids are used or handled, except in closed containers, means must be provided to dispose promptly and safely of leakage or spills (1910.106(e)(2)(iv)(b)).

Reference: 29 CFR 1926.152(e)(2) · 29 CFR 1926.152(e)(3) · 29 CFR 1926.152(f)(2) · 29 CFR 1926.152(f)(3) · 29 CFR 1910.106(e)(2)(iv)(c) · 29 CFR 1910.106(e)(6)(i) · 29 CFR 1910.106(e)(6)(ii) · 29 CFR 1910.106(e)(2)(iv)(d) · 29 CFR 1910.106(e)(2)(iv)(b)

Fueling and fire extinguishers

Engines off, no smoking, extinguisher close

When you fuel equipment on a construction site (1926.152(g))

Where the extinguishers go on a construction site (1926.152(d) and (g)(11))

Fueling areaAt least one extinguisher rated not less than 20-B:C, within 75 feet of each pump, dispenser, underground fill pipe opening and lubrication or service area
Indoor storage roomFor a room storing more than 60 gallons: at least one extinguisher rated not less than 20-B, outside the door and not more than 10 feet from it
Outdoor storage areaAt least one extinguisher rated not less than 20-B, not less than 25 feet and not more than 75 feet from the storage area
General industry numbers are different (1910.106(d)(7)(i)): at least one portable extinguisher rated not less than 12-B outside of, but not more than 10 feet from, the door opening into any room used for storage, and at least one rated not less than 12-B located not less than 10 feet, nor more than 25 feet, from any Category 1, 2 or 3 storage area located outside of a storage room but inside a building.
Good practice: know where the nearest extinguisher is before you start fueling or pouring.

Reference: 29 CFR 1926.152(g)(4) · 29 CFR 1926.152(g)(8) · 29 CFR 1926.152(g)(9) · 29 CFR 1926.152(g)(10) · 29 CFR 1926.152(g)(11) · 29 CFR 1926.152(d)(1) · 29 CFR 1926.152(d)(2) · 29 CFR 1910.106(d)(7)(i)(a) · 29 CFR 1910.106(d)(7)(i)(b)

Need proof of training? The full course (20 min) adds practice questions, a job scenario, the final quiz and a certificate your employer can verify.

Take the course

Sources

Fact-checked against the regulation text on October 09, 2026. This certificate records completion of awareness training based on OSHA 29 CFR 1926.152 and 1910.106. It is not an OSHA card or license. Neither 1926.152 nor 1910.106 has a training requirement of its own. In construction, 29 CFR 1926.21(b)(5) requires that employees required to handle or use flammable liquids be instructed in the safe handling and use of these materials and made aware of the specific requirements contained in subparts D, F, and other applicable subparts of Part 1926, and 1926.21(b)(2) requires the employer to instruct each employee in the recognition and avoidance of unsafe conditions. In general industry and construction alike, your employer must also train you on the hazardous chemicals in your work area under the Hazard Communication standard (29 CFR 1910.1200(h); 1926.59 in construction).

This guide explains the rule in plain words. Always read the regulation itself and your employer's site-specific procedures.