1910.110(f): Storing LP-Gas Containers

By Black Belt Safety Editorial Team Official text as of octubre 15, 2026 Data updated octubre 20, 2026 6 min read

In plain words:

Employers storing portable LP-Gas containers of not more than 1,000 pounds water capacity, at user locations or for resale, must locate them to minimize excessive heat, damage and tampering, and not store them inside near exits, stairways or escape routes. Valves must be protected by a recess or a ventilated cap or collar and kept closed, empty containers stored inside count as full, and storage in buildings not frequented by the public may not exceed 300 pounds except as provided.

Key takeaways

  • 1910.110(f) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart H).
  • OSHA cited it 214 times in the last 3 years, in 203 inspections, with $266,076 in current penalties.
  • Most citations: TN (31), VA (24), MD (24).
  • Related part: 1910.110(f)(2) General (166 citations).
  • Free 5-minute toolbox talk for your crew below.
214citations, 3 years
$266,076current penalties
203inspections
0linked injury cases
In this article
  1. What this rule covers
  2. Official text
  3. Where and how often it was cited
  4. Free toolbox talk
  5. OSHA interpretation letters
  6. Related parts of this rule
  7. Get your crew competent
  8. Frequently asked questions
  9. About this page

What this rule covers

29 CFR 1910.110(f) ("Storage of containers awaiting use or resale") is one requirement inside 1910.110 Storage and handling of liquefied petroleum gases, an OSHA general industry standard (Part 1910, Subpart H). It includes 25 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(f) Storage of containers awaiting use or resale — 214 citations

(1) Application. This paragraph shall apply to the storage of portable containers not in excess of 1,000 pounds water capacity, filled or partially filled, at user location but not connected for use, or in storage for resale by dealers or resellers. This paragraph shall not apply to containers stored at charging plants or at plants devoted primarily to the storage and distribution of LP-Gas or other petroleum products.

(2) General. Open (f)(2) 166 citations

(i) Containers in storage shall be located so as to minimize exposure to excessive temperature rise, physical damage, or tampering by unauthorized persons. Open (f)(2)(i) 99 citations

(ii) Containers when stored inside shall not be located near exits, stairways, or in areas normally used or intended for the safe exit of people. Open (f)(2)(ii) 66 citations

(iii) Container valves shall be protected while in storage as follows: 1 citations

(a) By setting into recess of container to prevent the possibility of their being struck if the container is dropped upon a flat surface, or

(b) By ventilated cap or collar, fastened to container capable of withstanding blow from any direction equivalent to that of a 30-pound weight dropped 4 feet. Construction must be such that a blow will not be transmitted to a valve or other connection.

(iv) The outlet valves of containers in storage shall be closed.

(v) Empty containers which have been in LP-Gas service when stored inside, shall be considered as full containers for the purpose of determining the maximum quantity of LP-Gas permitted by this paragraph.

(3) [Reserved]

(4) Storage within buildings not frequented by the public (such as industrial buildings). Open (f)(4) 10 citations

(i) The quantity of LP-Gas stored shall not exceed 300 pounds (approximately 2,550 cubic feet in vapor form) except as provided in subparagraph (5) of this paragraph. Open (f)(4)(i) 10 citations

(ii) Containers carried as a part of service equipment on highway mobile vehicles are not to be considered in the total storage capacity in subdivision (i) of this subparagraph provided such vehicles are stored in private garages, and are limited to one container per vehicle with an LP-Gas capacity of not more than 100 pounds. All container valves shall be closed.

(5) Storage within special buildings or rooms. Open (f)(5)

(i) The quantity of LP-Gas stored in special buildings or rooms shall not exceed 10,000 pounds.

(ii) The walls, floors, and ceilings of container storage rooms that are within or adjacent to other parts of the building shall be constructed of material having at least a 2-hour fire resistance rating.

(iii) A portion of the exterior walls or roof having an area not less than 10 percent of that of the combined area of the enclosing walls and roof shall be of explosion relieving construction.

(iv) Each opening from such storage rooms to other parts of the building shall be protected by a 11⁄2 hour (B) fire door listed by a nationally recognized testing laboratory. Refer to § 1910.7 for definition of nationally recognized testing laboratory.

(v) Such rooms shall have no open flames for heating or lighting.

(vi) Such rooms shall be adequately ventilated both top and bottom to the outside only. The openings from such vents shall be at least 5 feet away from any other opening into any building.

(vii) The floors of such rooms shall not be below ground level. Any space below the floor shall be of solid fill or properly ventilated to the open air.

(viii) Such storage rooms shall not be located adjoining the line of property occupied by schools, churches, hospitals, athletic fields or other points of public gathering.

(ix) Fixed electrical equipment shall be installed in accordance with paragraph (b)(18) of this section.

(6) Storage outside of buildings. Open (f)(6) 32 citations

(i) Storage outside of buildings, for containers awaiting use or resale, shall be located in accordance with Table H-33 with respect to: 1 citations

(a) The nearest important building or group of buildings;

(b) [Reserved]

(c) Busy thoroughfares;

Table H-33

Quantity of LP-Gas Stored Distance
500 pounds or less 0
501 to 2,500 pounds 1 0
2,501 to 6,000 pounds 10 feet
6,001 to 10,000 pounds 20 feet
Over 10,000 pounds 25 feet
1 Container or containers shall be at least 10 feet from any building on adjoining property, any sidewalk, or any of the exposures described in § 1910.110(f)(6)(i) (c) or (d) of this paragraph.

(ii) Containers shall be in a suitable enclosure or otherwise protected against tampering. Open (f)(6)(ii) 31 citations

(7) Fire protection. Storage locations other than supply depots separated and located apart from dealer, reseller, or user establishments shall be provided with at least one approved portable fire extinguisher having a minimum rating of 8-B, C. 6 citations

Source: eCFR, text current as of 2026-10-15. Read all of 1910.110.

Where and how often it was cited

YearCitations
202329
202469
202572
202644

Top states: TN (31), VA (24), MD (24), CT (12), MA (10)

Largest penalties

EmployerLocationPenalty for this rule
AMERICOLD LOGISTICS, LLCMOUNTVILLE, PA$11,348
GREAT LAKES VENEER, INC.TIGERTON, WI$10,640
BGS HOLDINGS, LLC.ARCADIA, OK$8,511
WELSPUN TUBULAR LLCLITTLE ROCK, AR$7,367
JOHNSON THERMAL SYSTEMS, LLC.CALDWELL, ID$7,094

Free toolbox talk

A 5-minute crew talk on 1910.110(f), plus alerts when this rule changes. Free.




OSHA interpretation letters

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey, Dana Reyes

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

Can propane cylinders be stored near exits?

No. Containers stored inside shall not be located near exits, stairways or areas intended for the safe exit of people.

Do valves need to be closed in storage?

Yes. The outlet valves of containers in storage shall be closed.

Are empty LP-Gas containers treated as empty?

No. Empty containers that have been in LP-Gas service stored inside are considered full for determining the maximum quantity allowed.

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Desplácese hacia arriba