1910.252(a)(2): Special Precautions for Welding and Cutting
Where welding or cutting falls under the rule's special-precaution scope, employers must protect combustibles below floor openings and near wall cracks, doorways and windows from sparks, and keep suitable fire extinguishing equipment ready for instant use. Fire watchers are required where more than a minor fire could develop or listed conditions exist, such as appreciable combustibles closer than 35 feet, and they must have extinguishing equipment and training.
Key takeaways
- 1910.252(a)(2) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart Q).
- OSHA cited it 138 times in the last 3 years, in 103 inspections, with $583,555 in current penalties.
- 4 deaths are linked to inspections that cited this rule.
- Most citations: TX (24), VA (10), GA (10).
- Related part: 1910.252(a) Fire prevention and protection (192 citations).
- Free 5-minute toolbox talk for your crew below.
In this article
What this rule covers
29 CFR 1910.252(a)(2) ("Special precautions") is one requirement inside 1910.252 General requirements, an OSHA general industry standard (Part 1910, Subpart Q). It includes 32 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.
Official text
(2) Special precautions. When the nature of the work to be performed falls within the scope of paragraph (a)(1)(ii) of this section certain additional precautions may be necessary: 138 citations
(i) Combustible material. Wherever there are floor openings or cracks in the flooring that cannot be closed, precautions shall be taken so that no readily combustible materials on the floor below will be exposed to sparks which might drop through the floor. The same precautions shall be observed with regard to cracks or holes in walls, open doorways and open or broken windows. 3 citations
(ii) Fire extinquishers. Suitable fire extinguishing equipment shall be maintained in a state of readiness for instant use. Such equipment may consist of pails of water, buckets of sand, hose or portable extinguishers depending upon the nature and quantity of the combustible material exposed. Open (a)(2)(ii) 10 citations
(iii) Fire watch. Open (a)(2)(iii) 13 citations
(A) Fire watchers shall be required whenever welding or cutting is performed in locations where other than a minor fire might develop, or any of the following conditions exist: Open (a)(2)(iii)(a) 9 citations
(1) Appreciable combustible material, in building construction or contents, closer than 35 feet (10.7 m) to the point of operation.
(2) Appreciable combustibles are more than 35 feet (10.7 m) away but are easily ignited by sparks.
(3) Wall or floor openings within a 35-foot (10.7 m) radius expose combustible material in adjacent areas including concealed spaces in walls or floors.
(4) Combustible materials are adjacent to the opposite side of metal partitions, walls, ceilings, or roofs and are likely to be ignited by conduction or radiation.
(B) Fire watchers shall have fire extinguishing equipment readily available and be trained in its use. They shall be familiar with facilities for sounding an alarm in the event of a fire. They shall watch for fires in all exposed areas, try to extinguish them only when obviously within the capacity of the equipment available, or otherwise sound the alarm. A fire watch shall be maintained for at least a half hour after completion of welding or cutting operations to detect and extinguish possible smoldering fires. 4 citations
(iv) Authorization. Before cutting or welding is permitted, the area shall be inspected by the individual responsible for authorizing cutting and welding operations. He shall designate precautions to be followed in granting authorization to proceed preferably in the form of a written permit. Open (a)(2)(iv) 13 citations
(v) Floors. Where combustible materials such as paper clippings, wood shavings, or textile fibers are on the floor, the floor shall be swept clean for a radius of 35 feet (10.7 m). Combustible floors shall be kept wet, covered with damp sand, or protected by fire-resistant shields. Where floors have been wet down, personnel operating arc welding or cutting equipment shall be protected from possible shock. 4 citations
(vi) Prohibited areas. Cutting or welding shall not be permitted in the following situations: Open (a)(2)(vi) 20 citations
(A) In areas not authorized by management.
(B) In sprinklered buildings while such protection is impaired. Open (a)(2)(vi)(b)
(C) In the presence of explosive atmospheres (mixtures of flammable gases, vapors, liquids, or dusts with air), or explosive atmospheres that may develop inside uncleaned or improperly prepared tanks or equipment which have previously contained such materials, or that may develop in areas with an accumulation of combustible dusts. Open (a)(2)(vi)(c) 19 citations
(D) In areas near the storage of large quantities of exposed, readily ignitible materials such as bulk sulfur, baled paper, or cotton.
(vii) Relocation of combustibles. Where practicable, all combustibles shall be relocated at least 35 feet (10.7 m) from the work site. Where relocation is impracticable, combustibles shall be protected with flameproofed covers or otherwise shielded with metal or asbestos guards or curtains. Open (a)(2)(vii) 28 citations
(viii) Ducts. Ducts and conveyor systems that might carry sparks to distant combustibles shall be suitably protected or shut down.
(ix) Combustible walls. Where cutting or welding is done near walls, partitions, ceiling or roof of combustible construction, fire-resistant shields or guards shall be provided to prevent ignition. 3 citations
(x) Noncombustible walls. If welding is to be done on a metal wall, partition, ceiling or roof, precautions shall be taken to prevent ignition of combustibles on the other side, due to conduction or radiation, preferably by relocating combustibles. Where combustibles are not relocated, a fire watch on the opposite side from the work shall be provided.
(xi) Combustible cover. Welding shall not be attempted on a metal partition, wall, ceiling or roof having a combustible covering nor on walls or partitions of combustible sandwich-type panel construction.
(xii) Pipes. Cutting or welding on pipes or other metal in contact with combustible walls, partitions, ceilings or roofs shall not be undertaken if the work is close enough to cause ignition by conduction.
(xiii) Management. Management shall recognize its responsibility for the safe usage of cutting and welding equipment on its property and: Open (a)(2)(xiii) 28 citations
(A) Based on fire potentials of plant facilities, establish areas for cutting and welding, and establish procedures for cutting and welding, in other areas. Open (a)(2)(xiii)(a) 4 citations
(B) Designate an individual responsible for authorizing cutting and welding operations in areas not specifically designed for such processes. 1 citations
(C) Insist that cutters or welders and their supervisors are suitably trained in the safe operation of their equipment and the safe use of the process. Open (a)(2)(xiii)(c) 16 citations
(D) Advise all contractors about flammable materials or hazardous conditions of which they may not be aware. 3 citations
(xiv) Supervisor. The Supervisor: Open (a)(2)(xiv) 9 citations
(A) Shall be responsible for the safe handling of the cutting or welding equipment and the safe use of the cutting or welding process. Open (a)(2)(xiv)(a) 3 citations
(B) Shall determine the combustible materials and hazardous areas present or likely to be present in the work location. 4 citations
(C) Shall protect combustibles from ignition by the following: 2 citations
(1) Have the work moved to a location free from dangerous combustibles.
(2) If the work cannot be moved, have the combustibles moved to a safe distance from the work or have the combustibles properly shielded against ignition.
(3) See that cutting and welding are so scheduled that plant operations that might expose combustibles to ignition are not started during cutting or welding.
(D) Shall secure authorization for the cutting or welding operations from the designated management representative.
(E) Shall determine that the cutter or welder secures his approval that conditions are safe before going ahead.
(F) Shall determine that fire protection and extinguishing equipment are properly located at the site.
(G) Where fire watches are required, he shall see that they are available at the site.
(xv) Fire prevention precautions. Cutting or welding shall be permitted only in areas that are or have been made fire safe. When work cannot be moved practically, as in most construction work, the area shall be made safe by removing combustibles or protecting combustibles from ignition sources. Open (a)(2)(xv) 7 citations
Source: eCFR, text current as of 2026-10-15. Read all of 1910.252.
Injuries linked to this rule
4 deaths are linked to inspections where OSHA cited 1910.252(a)(2).
At 8:00 a.m. on February 10, 2025, Employee #1 was using an acetylene torch to cut a piece of steel, resting the material on two empty methanol barrels. Residual vapor or liquid inside one of the barrels ignited, causing a deflagration. Employee #1 was struck…
Full case list with employer, penalty, filters and download is part of OSHA Data (Purple Belt).
Unlock with Purple BeltWhere and how often it was cited
| Year | Citations |
|---|---|
| 2023 | 7 |
| 2024 | 38 |
| 2025 | 62 |
| 2026 | 31 |
Top states: TX (24), VA (10), GA (10), WI (9), NY (8)
Largest penalties
| Employer | Location | Penalty for this rule |
|---|---|---|
| KIRK WILLIAMS COMPANY INC. | GROVE CITY, OH | $49,650 |
| FOSS ENERGY SERVICES, INC. | BIG SPRING, TX | $44,685 |
| RESOURCE RECYCLING, INC. | LIMA, OH | $39,196 |
| BOYCE EXCAVATING CO., INC. | SLATE HILL, NY | $34,755 |
| TRACTOR & EQUIPMENT COMPANY | KENNESAW, GA | $22,342 |
Free toolbox talk
A 5-minute crew talk on 1910.252(a)(2), plus alerts when this rule changes. Free.
OSHA interpretation letters
- Citation policy regarding automatic sprinkler systems. (1999-01-14)
- Training and competency for oxygen-fuel gas welding equipment use (1998-05-13)
Related parts of this rule
- 1910.252(a) Fire prevention and protection 192 citations
- 1910.252(a)(3) Welding or cutting containers 40 citations
- 1910.252(a)(3)(i) Used containers 33 citations
- 1910.252(a)(2)(vii) Relocation of combustibles 28 citations
- 1910.252(a)(2)(xiii) Management 28 citations
- 1910.252(a)(2)(vi) Prohibited areas 20 citations
- 1910.252(a)(2)(vi)(C) 19 citations
- 1910.252(a)(2)(xiii)(C) 16 citations
- 1910.252(a)(1) Basic precautions 14 citations
- 1910.252(a)(2)(iii) Fire watch 13 citations
- 1910.252(a)(2)(iv) Authorization 13 citations
- 1910.252(a)(2)(ii) Fire extinquishers 10 citations
Get your crew competent
Trainers on Black Belt Safety: Marc Harvey, Dana Reyes
Trainers and suppliers: feature your business on this rule for $25/month.
Frequently asked questions
When is a fire watch required for welding?
Where other than a minor fire might develop, or listed conditions exist such as appreciable combustible material closer than 35 feet to the work.
What extinguishing equipment is acceptable?
Suitable equipment such as pails of water, buckets of sand, hose or portable extinguishers, depending on the combustibles exposed.
What must fire watchers know?
They must be trained to use the extinguishing equipment and be familiar with how to sound an alarm.
About this page
Sources
- 29 CFR 1910.252 (eCFR), text current as of 2026-10-15
- U.S. Department of Labor enforcement data: OSHA inspections, citations and accident records, copied nightly; data as of 2026-10-20
3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.