1910.269(o): High-Voltage and High-Power Testing
Employers doing high-voltage or high-power testing in labs, shops, substations or the field must set and enforce work practices to protect each worker at all test areas. These must include test area safeguarding, grounding, safe use of measuring and control circuits, and periodic safety checks of field test areas. Employees must be trained on first assignment to a test area, and routine metering, relaying and normal line work are not covered.
Key takeaways
- 1910.269(o) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart R).
- OSHA cited it 6 times in the last 3 years, in 5 inspections, with $45,508 in current penalties.
- 1 death is linked to inspections that cited this rule.
- Related part: 1910.269(o)(3) Safeguarding of test areas (1 citations).
- Free 5-minute toolbox talk for your crew below.
Get the free 5-minute toolbox talk on 1910.269(o) ↓
In this article
What this rule covers
29 CFR 1910.269(o) ("Testing and test facilities") is one requirement inside 1910.269 Electric power generation, transmission, and distribution, an OSHA general industry standard (Part 1910, Subpart R). It includes 39 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.
Official text
(o) Testing and test facilities — 6 citations
(1) Application. Paragraph (o) of this section provides for safe work practices for high-voltage and high-power testing performed in laboratories, shops, and substations, and in the field and on electric transmission and distribution lines and equipment. It applies only to testing involving interim measurements using high voltage, high power, or combinations of high voltage and high power, and not to testing involving continuous measurements as in routine metering, relaying, and normal line work.
OSHA considers routine inspection and maintenance measurements made by qualified employees to be routine line work not included in the scope of paragraph (o) of this section, provided that the hazards related to the use of intrinsic high-voltage or high-power sources require only the normal precautions associated with routine work specified in the other paragraphs of this section. Two typical examples of such excluded test work procedures are “phasing-out” testing and testing for a “no-voltage” condition.
(2) General requirements. 4 citations
(i) The employer shall establish and enforce work practices for the protection of each worker from the hazards of high-voltage or high-power testing at all test areas, temporary and permanent. Such work practices shall include, as a minimum, test area safeguarding, grounding, the safe use of measuring and control circuits, and a means providing for periodic safety checks of field test areas. 3 citations
(ii) The employer shall ensure that each employee, upon initial assignment to the test area, receives training in safe work practices, with retraining provided as required by paragraph (a)(2) of this section. 1 citations
(3) Safeguarding of test areas. Open (o)(3) 1 citations
(i) The employer shall provide safeguarding within test areas to control access to test equipment or to apparatus under test that could become energized as part of the testing by either direct or inductive coupling and to prevent accidental employee contact with energized parts. Open (o)(3)(i) 1 citations
(ii) The employer shall guard permanent test areas with walls, fences, or other barriers designed to keep employees out of the test areas.
(iii) In field testing, or at a temporary test site not guarded by permanent fences and gates, the employer shall ensure the use of one of the following means to prevent employees without authorization from entering:
(A) Distinctively colored safety tape supported approximately waist high with safety signs attached to it,
(B) A barrier or barricade that limits access to the test area to a degree equivalent, physically and visually, to the barricade specified in paragraph (o)(3)(iii)(A) of this section, or
(C) One or more test observers stationed so that they can monitor the entire area.
(iv) The employer shall ensure the removal of the safeguards required by paragraph (o)(3)(iii) of this section when employees no longer need the protection afforded by the safeguards.
(4) Grounding practices.
(i) The employer shall establish and implement safe grounding practices for the test facility.
(A) The employer shall maintain at ground potential all conductive parts accessible to the test operator while the equipment is operating at high voltage.
(B) Wherever ungrounded terminals of test equipment or apparatus under test may be present, they shall be treated as energized until tests demonstrate that they are deenergized.
(ii) The employer shall ensure either that visible grounds are applied automatically, or that employees using properly insulated tools manually apply visible grounds, to the high-voltage circuits after they are deenergized and before any employee performs work on the circuit or on the item or apparatus under test. Common ground connections shall be solidly connected to the test equipment and the apparatus under test.
(iii) In high-power testing, the employer shall provide an isolated ground-return conductor system designed to prevent the intentional passage of current, with its attendant voltage rise, from occurring in the ground grid or in the earth. However, the employer need not provide an isolated ground-return conductor if the employer can demonstrate that both of the following conditions exist:
(A) The employer cannot provide an isolated ground-return conductor due to the distance of the test site from the electric energy source, and
(B) The employer protects employees from any hazardous step and touch potentials that may develop during the test.
See appendix C to this section for information on measures that employers can take to protect employees from hazardous step and touch potentials.
(iv) For tests in which using the equipment grounding conductor in the equipment power cord to ground the test equipment would result in greater hazards to test personnel or prevent the taking of satisfactory measurements, the employer may use a ground clearly indicated in the test set-up if the employer can demonstrate that this ground affords protection for employees equivalent to the protection afforded by an equipment grounding conductor in the power supply cord.
(v) The employer shall ensure that, when any employee enters the test area after equipment is deenergized, a ground is placed on the high-voltage terminal and any other exposed terminals.
(A) Before any employee applies a direct ground, the employer shall discharge high capacitance equipment through a resistor rated for the available energy.
(B) A direct ground shall be applied to the exposed terminals after the stored energy drops to a level at which it is safe to do so.
(vi) If the employer uses a test trailer or test vehicle in field testing, its chassis shall be grounded. The employer shall protect each employee against hazardous touch potentials with respect to the vehicle, instrument panels, and other conductive parts accessible to employees with bonding, insulation, or isolation.
(5) Control and measuring circuits. 1 citations
(i) The employer may not run control wiring, meter connections, test leads, or cables from a test area unless contained in a grounded metallic sheath and terminated in a grounded metallic enclosure or unless the employer takes other precautions that it can demonstrate will provide employees with equivalent safety.
(ii) The employer shall isolate meters and other instruments with accessible terminals or parts from test personnel to protect against hazards that could arise should such terminals and parts become energized during testing. If the employer provides this isolation by locating test equipment in metal compartments with viewing windows, the employer shall provide interlocks to interrupt the power supply when someone opens the compartment cover.
(iii) The employer shall protect temporary wiring and its connections against damage, accidental interruptions, and other hazards. To the maximum extent possible, the employer shall keep signal, control, ground, and power cables separate from each other. 1 citations
(iv) If any employee will be present in the test area during testing, a test observer shall be present. The test observer shall be capable of implementing the immediate deenergizing of test circuits for safety purposes.
(6) Safety check.
(i) Safety practices governing employee work at temporary or field test areas shall provide, at the beginning of each series of tests, for a routine safety check of such test areas.
(ii) The test operator in charge shall conduct these routine safety checks before each series of tests and shall verify at least the following conditions:
(A) Barriers and safeguards are in workable condition and placed properly to isolate hazardous areas;
(B) System test status signals, if used, are in operable condition;
(C) Clearly marked test-power disconnects are readily available in an emergency;
(D) Ground connections are clearly identifiable;
(E) Personal protective equipment is provided and used as required by Subpart I of this part and by this section; and
(F) Proper separation between signal, ground, and power cables.
Source: eCFR, text current as of 2026-10-15. Read all of 1910.269.
Export the list: 5 inspections cited 1910.269(o) in the last 3 years, with employer, location, penalty and date.
Purple Belt, $59/moInjuries linked to this rule
1 death is linked to inspections where OSHA cited 1910.269(o).
At 7:00 p.m. on November 12, 2023, an employee climbed a ladder to access the top of an electrical transformer. The employee was verifying the test equipmentwas hooked up appropriately and turned around to exit on the ladder. The employee came into contact with electricity,…
Where and how often it was cited
Free toolbox talk
A 5-minute crew talk on 1910.269(o), plus alerts when this rule changes. Free.
OSHA interpretation letters
None exist. OSHA has not published a letter of interpretation for 1910.269(o).
Related parts of this rule
- 1910.269(o)(3) Safeguarding of test areas 1 citations
- 1910.269(o)(3)(i) 1 citations
Get your crew competent
Trainers on Black Belt Safety: Marc Harvey
Trainers and suppliers: feature your business on this rule for $25/month.
Frequently asked questions
Does this apply to routine metering?
No. It does not apply to continuous measurements as in routine metering, relaying and normal line work.
What work practices are required at a minimum?
Test area safeguarding, grounding, safe use of measuring and control circuits, and periodic safety checks of field test areas.
When must test area workers be trained?
Upon initial assignment to the test area, with retraining as required by paragraph (a)(2).