1910.304(g): Grounding Electrical Systems and Equipment
Employers must ground electrical systems, circuits and equipment as this paragraph requires. It lists which DC and AC systems must be grounded, such as many 50 to 1000 volt AC systems, and which special systems are exempt, and it sets rules for grounding connections and the grounding path.
Key takeaways
- 1910.304(g) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
- OSHA cited it 598 times in the last 3 years, in 591 inspections, with $1,141,614 in current penalties.
- 2 deaths are linked to inspections that cited this rule.
- Most citations: TN (104), MN (78), NV (76).
- Related part: 1910.304(g)(5) Grounding path (556 citations).
- Free 5-minute toolbox talk for your crew below.
In this article
What this rule covers
29 CFR 1910.304(g) ("Grounding") is one requirement inside 1910.304 Wiring design and protection, an OSHA general industry standard (Part 1910, Subpart S). It includes 76 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.
Official text
(g) Grounding. Paragraphs (g)(1) through (g)(9) of this section contain grounding requirements for systems, circuits, and equipment. 598 citations
(1) Systems to be grounded. Systems that supply premises wiring shall be grounded as follows: 2 citations
(i) All 3-wire dc systems shall have their neutral conductor grounded; 2 citations
(ii) Two-wire dc systems operating at over 50 volts through 300 volts between conductors shall be grounded unless:
(A) They supply only industrial equipment in limited areas and are equipped with a ground detector;
(B) They are rectifier-derived from an ac system complying with paragraphs (g)(1)(iii), (g)(1)(iv), and (g)(1)(v) of this section; or
(C) They are fire-alarm circuits having a maximum current of 0.030 amperes;
(iii) AC circuits of less than 50 volts shall be grounded if they are installed as overhead conductors outside of buildings or if they are supplied by transformers and the transformer primary supply system is ungrounded or exceeds 150 volts to ground;
(iv) AC systems of 50 volts to 1000 volts shall be grounded under any of the following conditions, unless exempted by paragraph (g)(1)(v) of this section:
(A) If the system can be so grounded that the maximum voltage to ground on the ungrounded conductors does not exceed 150 volts;
(B) If the system is nominally rated three-phase, four-wire wye connected in which the neutral is used as a circuit conductor;
(C) If the system is nominally rated three-phase, four-wire delta connected in which the midpoint of one phase is used as a circuit conductor; or
(D) If a service conductor is uninsulated;
(v) AC systems of 50 volts to 1000 volts are not required to be grounded under any of the following conditions:
(A) If the system is used exclusively to supply industrial electric furnaces for melting, refining, tempering, and the like;
(B) If the system is separately derived and is used exclusively for rectifiers supplying only adjustable speed industrial drives;
(C) If the system is separately derived and is supplied by a transformer that has a primary voltage rating less than 1000 volts, provided all of the following conditions are met:
(1) The system is used exclusively for control circuits;
(2) The conditions of maintenance and supervision ensure that only qualified persons will service the installation;
(3) Continuity of control power is required; and
(4) Ground detectors are installed on the control system;
(D) If the system is an isolated power system that supplies circuits in health care facilities; or
(E) If the system is a high-impedance grounded neutral system in which a grounding impedance, usually a resistor, limits the ground-fault current to a low value for 3-phase ac systems of 480 volts to 1000 volts provided all of the following conditions are met:
(1) The conditions of maintenance and supervision ensure that only qualified persons will service the installation;
(2) Continuity of power is required;
(3) Ground detectors are installed on the system; and
(4) Line-to-neutral loads are not served.
(2) Conductor to be grounded. The conductor to be grounded for ac premises wiring systems required to be grounded by paragraph (g)(1) of this section shall be as follows: 4 citations
(i) One conductor of a single-phase, two-wire system shall be grounded;
(ii) The neutral conductor of a single-phase, three-wire system shall be grounded; 4 citations
(iii) The common conductor of a multiphase system having one wire common to all phases shall be grounded;
(iv) One phase conductor of a multiphase system where one phase is grounded shall be grounded; and
(v) The neutral conductor of a multiphase system in which one phase is used as a neutral conductor shall be grounded.
(3) Portable and vehicle-mounted generators.
(i) The frame of a portable generator need not be grounded and may serve as the grounding electrode for a system supplied by the generator under the following conditions:
(A) The generator supplies only equipment mounted on the generator or cord- and plug-connected equipment through receptacles mounted on the generator, or both; and
(B) The noncurrent-carrying metal parts of equipment and the equipment grounding conductor terminals of the receptacles are bonded to the generator frame.
(ii) The frame of a vehicle need not be grounded and may serve as the grounding electrode for a system supplied by a generator located on the vehicle under the following conditions:
(A) The frame of the generator is bonded to the vehicle frame;
(B) The generator supplies only equipment located on the vehicle and cord- and plug-connected equipment through receptacles mounted on the vehicle;
(C) The noncurrent-carrying metal parts of equipment and the equipment grounding conductor terminals of the receptacles are bonded to the generator frame; and
(D) The system complies with all other provisions of paragraph (g) of this section.
(iii) A system conductor that is required to be grounded by the provisions of paragraph (g)(2) of this section shall be bonded to the generator frame where the generator is a component of a separately derived system.
(4) Grounding connections.
(i) For a grounded system, a grounding electrode conductor shall be used to connect both the equipment grounding conductor and the grounded circuit conductor to the grounding electrode. Both the equipment grounding conductor and the grounding electrode conductor shall be connected to the grounded circuit conductor on the supply side of the service disconnecting means or on the supply side of the system disconnecting means or overcurrent devices if the system is separately derived.
(ii) For an ungrounded service-supplied system, the equipment grounding conductor shall be connected to the grounding electrode conductor at the service equipment. For an ungrounded separately derived system, the equipment grounding conductor shall be connected to the grounding electrode conductor at, or ahead of, the system disconnecting means or overcurrent devices.
(iii) On extensions of existing branch circuits that do not have an equipment grounding conductor, grounding-type receptacles may be grounded to a grounded cold water pipe near the equipment if the extension was installed before August 13, 2007. When any element of this branch circuit is replaced, the entire branch circuit shall use an equipment grounding conductor that complies with all other provisions of paragraph (g) of this section.
(5) Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective. Open (g)(5) 556 citations
(6) Supports, enclosures, and equipment to be grounded. Open (g)(6) 34 citations
(i) Metal cable trays, metal raceways, and metal enclosures for conductors shall be grounded, except that:
(A) Metal enclosures such as sleeves that are used to protect cable assemblies from physical damage need not be grounded; and
(B) Metal enclosures for conductors added to existing installations of open wire, knob-and-tube wiring, and nonmetallic-sheathed cable need not be grounded if all of the following conditions are met:
(1) Runs are less than 7.62 meters (25.0 ft);
(2) Enclosures are free from probable contact with ground, grounded metal, metal laths, or other conductive materials; and
(3) Enclosures are guarded against employee contact.
(ii) Metal enclosures for service equipment shall be grounded.
(iii) Frames of electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, and metal outlet or junction boxes that are part of the circuit for these appliances shall be grounded. 1 citations
(iv) Exposed noncurrent-carrying metal parts of fixed equipment that may become energized shall be grounded under any of the following conditions: 3 citations
(A) If within 2.44 m (8 ft) vertically or 1.52 m (5 ft) horizontally of ground or grounded metal objects and subject to employee contact;
(B) If located in a wet or damp location and not isolated; 3 citations
(C) If in electrical contact with metal;
(D) If in a hazardous (classified) location;
(E) If supplied by a metal-clad, metal-sheathed, or grounded metal raceway wiring method; or
(F) If equipment operates with any terminal at over 150 volts to ground.
(v) Notwithstanding the provisions of paragraph (g)(6)(iv) of this section, exposed noncurrent-carrying metal parts of the following types of fixed equipment need not be grounded:
(A) Enclosures for switches or circuit breakers used for other than service equipment and accessible to qualified persons only;
(B) Electrically heated appliances that are permanently and effectively insulated from ground;
(C) Distribution apparatus, such as transformer and capacitor cases, mounted on wooden poles, at a height exceeding 2.44 m (8.0 ft) above ground or grade level; and
(D) Listed equipment protected by a system of double insulation, or its equivalent, and distinctively marked as such.
(vi) Exposed noncurrent-carrying metal parts of cord- and plug-connected equipment that may become energized shall be grounded under any of the following conditions: Open (g)(6)(vi) 29 citations
(A) If in hazardous (classified) locations (see § 1910.307);
(B) If operated at over 150 volts to ground, except for guarded motors and metal frames of electrically heated appliances if the appliance frames are permanently and effectively insulated from ground;
(C) If the equipment is of the following types: Open (g)(6)(vi)(c) 27 citations
(1) Refrigerators, freezers, and air conditioners;
(2) Clothes-washing, clothes-drying, and dishwashing machines, sump pumps, and electric aquarium equipment;
(3) Hand-held motor-operated tools, stationary and fixed motor-operated tools, and light industrial motor-operated tools;
(4) Motor-operated appliances of the following types: hedge clippers, lawn mowers, snow blowers, and wet scrubbers;
(5) Cord- and plug-connected appliances used in damp or wet locations, or by employees standing on the ground or on metal floors or working inside of metal tanks or boilers;
(6) Portable and mobile X-ray and associated equipment;
(7) Tools likely to be used in wet and conductive locations; and
(8 Portable hand lamps.
(vii) Notwithstanding the provisions of paragraph (g)(6)(vi) of this section, the following equipment need not be grounded:
(A) Tools likely to be used in wet and conductive locations if supplied through an isolating transformer with an ungrounded secondary of not over 50 volts; and
(B) Listed or labeled portable tools and appliances if protected by an approved system of double insulation, or its equivalent, and distinctively marked.
(7) Nonelectrical equipment. The metal parts of the following nonelectrical equipment shall be grounded: frames and tracks of electrically operated cranes and hoists; frames of nonelectrically driven elevator cars to which electric conductors are attached; hand-operated metal shifting ropes or cables of electric elevators; and metal partitions, grill work, and similar metal enclosures around equipment of over 750 volts between conductors.
(8) Methods of grounding fixed equipment. 1 citations
(i) Noncurrent-carrying metal parts of fixed equipment, if required to be grounded by this subpart, shall be grounded by an equipment grounding conductor that is contained within the same raceway, cable, or cord, or runs with or encloses the circuit conductors. For dc circuits only, the equipment grounding conductor may be run separately from the circuit conductors. 1 citations
(ii) Electric equipment is considered to be effectively grounded if it is secured to, and in electrical contact with, a metal rack or structure that is provided for its support and the metal rack or structure is grounded by the method specified for the noncurrent-carrying metal parts of fixed equipment in paragraph (g)(8)(i) of this section. Metal car frames supported by metal hoisting cables attached to or running over metal sheaves or drums of grounded elevator machines are also considered to be effectively grounded.
(iii) For installations made before April 16, 1981, electric equipment is also considered to be effectively grounded if it is secured to, and in metallic contact with, the grounded structural metal frame of a building. When any element of this branch circuit is replaced, the entire branch circuit shall use an equipment grounding conductor that complies with all other provisions of paragraph (g) of this section.
(9) Grounding of systems and circuits of 1000 volts and over (high voltage). If high voltage systems are grounded, they shall comply with all applicable provisions of paragraphs (g)(1) through (g)(8) of this section as supplemented and modified by the following requirements: 1 citations
(i) Systems supplying portable or mobile high voltage equipment, other than substations installed on a temporary basis, shall comply with the following:
(A) The system shall have its neutral grounded through an impedance. If a delta-connected high voltage system is used to supply the equipment, a system neutral shall be derived.
(B) Exposed noncurrent-carrying metal parts of portable and mobile equipment shall be connected by an equipment grounding conductor to the point at which the system neutral impedance is grounded.
(C) Ground-fault detection and relaying shall be provided to automatically deenergize any high voltage system component that has developed a ground fault. The continuity of the equipment grounding conductor shall be continuously monitored so as to deenergize automatically the high voltage feeder to the portable equipment upon loss of continuity of the equipment grounding conductor.
(D) The grounding electrode to which the portable equipment system neutral impedance is connected shall be isolated from and separated in the ground by at least 6.1 m (20.0 ft) from any other system or equipment grounding electrode, and there shall be no direct connection between the grounding electrodes, such as buried pipe, fence, and so forth.
(ii) All noncurrent-carrying metal parts of portable equipment and fixed equipment, including their associated fences, housings, enclosures, and supporting structures, shall be grounded. However, equipment that is guarded by location and isolated from ground need not be grounded. Additionally, pole-mounted distribution apparatus at a height exceeding 2.44 m (8.0 ft) above ground or grade level need not be grounded. 1 citations
[46 FR 4056, Jan. 16, 1981, as amended at 73 FR 64205, Oct. 29, 2008]
Source: eCFR, text current as of 2026-10-15. Read all of 1910.304.
Injuries linked to this rule
2 deaths are linked to inspections where OSHA cited 1910.304(g).
At 12:00 a.m. on August 15, 2024, Employee #1 was working alone at a residentialproperty, performing drain cleaning services using a pipe cleaning snake auger. The owner of Rapid Rooter attempted to contact Employee #1 multiple times throughout the day without success. Upon arriving at…
Full case list with employer, penalty, filters and download is part of OSHA Data (Purple Belt).
Unlock with Purple BeltWhere and how often it was cited
| Year | Citations |
|---|---|
| 2023 | 34 |
| 2024 | 198 |
| 2025 | 220 |
| 2026 | 146 |
Top states: TN (104), MN (78), NV (76), HI (63), VA (42)
Largest penalties
| Employer | Location | Penalty for this rule |
|---|---|---|
| THE BURKS COMPANIES, INC | STATELINE, NV | $35,465 |
| MOCK, INC | TUSCALOOSA, AL | $16,550 |
| AEKO KULA LLC | HONOLULU, HI | $16,550 |
| PATTERSON-UTI DRILLING COMPANY LLC | CARLSBAD, NM | $15,442 |
| THE HOME DEPOT #0457 | SCOTTSDALE, AZ | $15,211 |
Free toolbox talk
A 5-minute crew talk on 1910.304(g), plus alerts when this rule changes. Free.
OSHA interpretation letters
None exist. OSHA has not published a letter of interpretation for 1910.304(g).
Related parts of this rule
- 1910.304(g)(5) Grounding path 556 citations
- 1910.304(g)(6) Supports, enclosures, and equipment to be grounded 34 citations
- 1910.304(g)(6)(vi) 29 citations
- 1910.304(g)(6)(vi)(C) 27 citations
Get your crew competent
Trainers on Black Belt Safety: Marc Harvey, Dana Reyes
Trainers and suppliers: feature your business on this rule for $25/month.
Frequently asked questions
Which AC systems from 50 to 1000 volts must be grounded?
Those meeting listed conditions, such as when grounding keeps voltage to ground at 150 volts or less, or a three-phase four-wire wye system uses the neutral as a circuit conductor.
Are any systems exempt from grounding?
Yes. Examples include systems used only for industrial electric furnaces and certain separately derived control circuit systems meeting listed conditions.
Why does grounding matter?
Grounding gives fault current a safe path, which helps protect people from shock.