29 CFR 1910 · General Industry · Subpart S

1910.305(h): Portable Cables Over 600 Volts

By Black Belt Safety Editorial Team Official text as of octubre 15, 2026 Data updated noviembre 6, 2026 4 min read

In plain words:

Employers using portable cables above 600 volts must use No. 8 or larger flexible conductors, shield cables over 2,000 volts, ground all shields and provide grounding conductors. Connectors must lock firmly, splices must be an approved permanent type, and terminations must carry a high voltage warning and be reachable only by authorized, qualified employees.

Key takeaways

  • 1910.305(h) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
  • OSHA cited it 12 times in the last 3 years, in 12 inspections, with $24,844 in current penalties.
  • Most citations: TX (3), KS (2), PR (2).
  • Free 5-minute toolbox talk for your crew below.

Get the free 5-minute toolbox talk on 1910.305(h) ↓

12citations, 3 years
$24,844current penalties
12inspections
0linked injury cases
In this article
  1. What this rule covers
  2. Official text
  3. Where and how often it was cited
  4. Free toolbox talk
  5. OSHA interpretation letters
  6. Get your crew competent
  7. Frequently asked questions
  8. About this page

What this rule covers

29 CFR 1910.305(h) ("Portable cables over 600 volts, nominal") is one requirement inside 1910.305 Wiring methods, components, and equipment for general use, an OSHA general industry standard (Part 1910, Subpart S). It includes 8 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(h) Portable cables over 600 volts, nominal. This paragraph applies to portable cables used at more than 600 volts, nominal. 12 citations

(1) Conductor construction. Multiconductor portable cable for use in supplying power to portable or mobile equipment at over 600 volts, nominal, shall consist of No. 8 or larger conductors employing flexible stranding. However, the minimum size of the insulated ground-check conductor of Type G-GC cables shall be No. 10.

(2) Shielding. Cables operated at over 2,000 volts shall be shielded for the purpose of confining the voltage stresses to the insulation.

(3) Equipment grounding conductors. Grounding conductors shall be provided.

(4) Grounding shields. All shields shall be grounded.

(5) Minimum bending radii. The minimum bending radii for portable cables during installation and handling in service shall be adequate to prevent damage to the cable.

(6) Fittings. Connectors used to connect lengths of cable in a run shall be of a type that lock firmly together. Provisions shall be made to prevent opening or closing these connectors while energized. Strain relief shall be provided at connections and terminations. 7 citations

(7) Splices. Portable cables may not be operated with splices unless the splices are of the permanent molded, vulcanized, or other approved type. 5 citations

(8) Terminations. Termination enclosures shall be suitably marked with a high voltage hazard warning, and terminations shall be accessible only to authorized and qualified employees.

Source: eCFR, text current as of 2026-10-15. Read all of 1910.305.

See every company cited for this rule.

Export the list: 12 inspections cited 1910.305(h) in the last 3 years, with employer, location, penalty and date.

Purple Belt, $59/mo

Where and how often it was cited

YearCitations
20249
20251
20262

Top states: TX (3), KS (2), PR (2), KY (2), AZ (1)

Largest penalties

EmployerLocationPenalty for this rule
VIRGINIA TILE COWICHITA, KS$8,296
STAR PIPE USA, LLCCOFFEYVILLE, KS$5,807
BOWIE BAKERYEL PASO, TX$3,333
QANNEX CORP.EL PASO, TX$2,500
67774 - SMITH AND LOGSDON INCLOUISVILLE, KY$1,750

Free toolbox talk

A 5-minute crew talk on 1910.305(h), plus alerts when this rule changes. Free.




OSHA interpretation letters

None exist. OSHA has not published a letter of interpretation for 1910.305(h).

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

What conductor size is required?

No. 8 or larger with flexible stranding, though the ground-check conductor of Type G-GC cables may be No. 10.

When must cables be shielded?

Cables operated at over 2,000 volts must be shielded, and all shields must be grounded.

Can a portable high voltage cable be spliced?

Only if the splice is the permanent molded, vulcanized or other approved type.

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Desplácese hacia arriba