29 CFR 1910 · General Industry · Subpart H

1910.106(d)(4)(iv): Ventilation for Inside Storage Rooms

By Black Belt Safety Editorial Team Official text as of octubre 15, 2026 Data updated octubre 21, 2026 3 min read

In plain words:

Employers must give every inside flammable liquid storage room a gravity or mechanical exhaust ventilation system that changes the room's air at least six times per hour. A mechanical system must be switched from outside the door, on the same switch as the lights, with a pilot light when certain flammable liquids are dispensed inside. Gravity systems need both the fresh air intake and exhaust outlet on the building's exterior.

Key takeaways

  • 1910.106(d)(4)(iv) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart H).
  • OSHA cited it 22 times in the last 3 years, in 22 inspections, with $54,426 in current penalties.
  • Most citations: VA (5), MI (3), IL (2).
  • Related part: 1910.106(d) Container and portable tank storage (357 citations).
  • Free 5-minute toolbox talk for your crew below.
22citations, 3 years
$54,426current penalties
22inspections
0linked injury cases
In this article
  1. What this rule covers
  2. Official text
  3. Where and how often it was cited
  4. Free toolbox talk
  5. OSHA interpretation letters
  6. Related parts of this rule
  7. Get your crew competent
  8. Frequently asked questions
  9. About this page

What this rule covers

29 CFR 1910.106(d)(4)(iv) ("Ventilation") is one requirement inside 1910.106 Flammable liquids, an OSHA general industry standard (Part 1910, Subpart H). The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(iv) Ventilation. Every inside storage room shall be provided with either a gravity or a mechanical exhaust ventilation system. Such system shall be designed to provide for a complete change of air within the room at least six times per hour. If a mechanical exhaust system is used, it shall be controlled by a switch located outside of the door. The ventilating equipment and any lighting fixtures shall be operated by the same switch. A pilot light shall be installed adjacent to the switch if Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), are dispensed within the room. Where gravity ventilation is provided, the fresh air intake, as well as the exhaust outlet from the room, shall be on the exterior of the building in which the room is located. 22 citations

Source: eCFR, text current as of 2026-10-15. Read all of 1910.106.

Where and how often it was cited

YearCitations
20233
20245
202510
20264

Top states: VA (5), MI (3), IL (2), WI (2), NH (1)

Largest penalties

EmployerLocationPenalty for this rule
THE GOODYEAR TIRE & RUBBER COMPANYDANVILLE, VA$13,415
KAIZEN AUTO CARE, LLCBRIGHTON, CO$9,930
VIRGINIA TRANSFORMER CORP.TROUTVILLE, VA$6,440
OPUS WATER INC.TONAWANDA, NY$5,020
JENSEN-SOUDERS & ASSOCIATES, INC.ITASCA, IL$4,800

Free toolbox talk

A 5-minute crew talk on 1910.106(d)(4)(iv), plus alerts when this rule changes. Free.




OSHA interpretation letters

None exist. OSHA has not published a letter of interpretation for 1910.106(d)(4)(iv).

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey, Dana Reyes

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

How many air changes are required in an inside storage room?

A complete change of air at least six times per hour.

Where must the mechanical ventilation switch be?

Outside of the door, and it must also operate the lighting fixtures.

When is a pilot light required?

When Category 1 or 2 flammable liquids, or Category 3 with a flashpoint below 100 °F (37.8 °C), are dispensed within the room.

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Desplácese hacia arriba