1910.106(d)(4): Inside Storage Rooms for Flammable Liquids

By Black Belt Safety Editorial Team Official text as of octubre 15, 2026 Data updated octubre 21, 2026 5 min read

In plain words:

Employers must build inside storage rooms for flammable liquids to the required fire-resistive rating, with self-closing fire doors, raised sills or ramps at least 4 inches high (or a floor 4 inches lower, or a draining trench), and liquid-tight wall-floor joints. Storage amounts and room sizes must follow Table H-13.

Key takeaways

  • 1910.106(d)(4) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart H).
  • OSHA cited it 67 times in the last 3 years, in 47 inspections, with $177,859 in current penalties.
  • Most citations: MI (11), PA (7), WI (7).
  • Related part: 1910.106(d) Container and portable tank storage (357 citations).
  • Free 5-minute toolbox talk for your crew below.
67citations, 3 years
$177,859current penalties
47inspections
0linked injury cases
In this article
  1. What this rule covers
  2. Official text
  3. Where and how often it was cited
  4. Free toolbox talk
  5. OSHA interpretation letters
  6. Related parts of this rule
  7. Get your crew competent
  8. Frequently asked questions
  9. About this page

What this rule covers

29 CFR 1910.106(d)(4) ("Design and construction of inside storage rooms") is one requirement inside 1910.106 Flammable liquids, an OSHA general industry standard (Part 1910, Subpart H). It includes 5 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(4) Design and construction of inside storage rooms — 67 citations

(i) Construction. Inside storage rooms shall be constructed to meet the required fire-resistive rating for their use. Such construction shall comply with the test specifications set forth in Standard Methods of Fire Tests of Building Construction and Materials, NFPA 251-1969. Where an automatic sprinkler system is provided, the system shall be designed and installed in an acceptable manner. Openings to other rooms or buildings shall be provided with noncombustible liquid-tight raised sills or ramps at least 4 inches in height, or the floor in the storage area shall be at least 4 inches below the surrounding floor. Openings shall be provided with approved self-closing fire doors. The room shall be liquid-tight where the walls join the floor. A permissible alternate to the sill or ramp is an open-grated trench inside of the room which drains to a safe location. Where other portions of the building or other properties are exposed, windows shall be protected as set forth in the Standard for Fire Doors and Windows, NFPA No. 80-1968, which is incorporated by reference as specified in § 1910.6, for Class E or F openings. Wood at least 1 inch nominal thickness may be used for shelving, racks, dunnage, scuffboards, floor overlay, and similar installations. Open (d)(4)(i) 26 citations

(ii) Rating and capacity. Storage in inside storage rooms shall comply with Table H-13. 1 citations

Table H-13—Storage in Inside Rooms

Fire protection 1 provided Fire resistance Maximum size Total allowable quantities (gals./sq. ft./floor area)
Yes 2 hours 500 sq. ft 10
No 2 hours 500 sq. ft 5
Yes 1 hour 150 sq. ft 4
No 1 hour 150 sq. ft 2
1 Fire protection system shall be sprinkler, water spray, carbon dioxide, or other system.

(iii) Wiring. Electrical wiring and equipment located in inside storage rooms used for Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), shall be approved under subpart S of this part for Class I, Division 2 Hazardous Locations; for Category 3 flammable liquids with a flashpoint at or above 100 °F (37.8 °C) and Category 4 flammable liquids, shall be approved for general use. Open (d)(4)(iii) 10 citations

(iv) Ventilation. Every inside storage room shall be provided with either a gravity or a mechanical exhaust ventilation system. Such system shall be designed to provide for a complete change of air within the room at least six times per hour. If a mechanical exhaust system is used, it shall be controlled by a switch located outside of the door. The ventilating equipment and any lighting fixtures shall be operated by the same switch. A pilot light shall be installed adjacent to the switch if Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), are dispensed within the room. Where gravity ventilation is provided, the fresh air intake, as well as the exhaust outlet from the room, shall be on the exterior of the building in which the room is located. Open (d)(4)(iv) 22 citations

(v) Storage in inside storage rooms. In every inside storage room there shall be maintained one clear aisle at least 3 feet wide. Containers over 30 gallons capacity shall not be stacked one upon the other. Dispensing shall be by approved pump or self-closing faucet only. 5 citations

Source: eCFR, text current as of 2026-10-15. Read all of 1910.106.

Where and how often it was cited

YearCitations
202310
202418
202526
202613

Top states: MI (11), PA (7), WI (7), VA (7), OK (4)

Largest penalties

EmployerLocationPenalty for this rule
CUSTOM CONTAINER SOLUTIONS, LLCMILTON, PA$14,000
THE GOODYEAR TIRE & RUBBER COMPANYDANVILLE, VA$13,415
KAIZEN AUTO CARE, LLCBRIGHTON, CO$9,930
WIKOFF COLOR CORPORATIONLISBON, WI$9,000
RANA MEAL SOLUTIONS, LLCBARTLETT, IL$8,593

Free toolbox talk

A 5-minute crew talk on 1910.106(d)(4), plus alerts when this rule changes. Free.




OSHA interpretation letters

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey, Dana Reyes

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

How high must the sill or ramp be?

At least 4 inches in height, or the floor in the storage area must be at least 4 inches below the surrounding floor.

What kind of doors are required?

Approved self-closing fire doors on openings.

Where are storage limits listed?

In Table H-13, based on fire protection, fire resistance and room size.

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Desplácese hacia arriba