1910.263(l)(9): Oven Safety Devices and Burners
Oven protecting devices must be maintained in working order and inspected at intervals of not less than twice a month by a trained bakery employee and not less than once a year by the oven manufacturer's representatives. Pilot failure must automatically shut off fuel, burners over 150,000 B.t.u. per hour with electric ignition need quick-acting combustion safeguards, and safety shutoff valves are required when fuel is used at line pressure.
Key takeaways
- 1910.263(l)(9) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart R).
- OSHA cited it 50 times in the last 3 years, in 49 inspections, with $154,160 in current penalties.
- Most citations: PR (35), MN (7), TX (2).
- Related part: 1910.263(l) Ovens (50 citations).
- Free 5-minute toolbox talk for your crew below.
Get the free 5-minute toolbox talk on 1910.263(l)(9) ↓
In this article
What this rule covers
29 CFR 1910.263(l)(9) ("General requirements") is one requirement inside 1910.263 Bakery equipment, an OSHA general industry standard (Part 1910, Subpart R). It includes 10 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.
Official text
(9) General requirements. 50 citations
(i) Protecting devices shall be properly maintained and kept in working order. Open (l)(9)(i) 1 citations
(ii) All safety devices on ovens shall be inspected at intervals of not less than twice a month by an especially appointed, properly instructed bakery employee, and not less than once a year by representatives of the oven manufacturers. Open (l)(9)(ii) 47 citations
(iii) 1 citations
(a) Protection of gas pilot lights shall be provided when it is impracticable to protect the main flame of the burner and where the pilot flame cannot contact the flame electrode without being in the path of the main flame of the burner. Failure of any gas pilot shall automatically shut off the fuel supply to the burner.
(b) Ovens with multiple burners shall be equipped with individual atmospheric pilot lights where there is sufficient secondary air in the baking chamber and where gas is available; or else each burner shall be equipped with an electric spark-type ignition device.
(iv) Burners of a capacity exceeding 150,000 B.t.u. per hour equipped with electric ignition shall be protected in addition by quick-acting combustion safeguards. Open (l)(9)(iv)
(a) The high-tension current for any electric spark-type ignition device shall originate in a power supply line which is interlocked with the fuel supply for the oven in such a way that in case of current failure both the source of electricity to the high-tension circuits and the fuel supply shall be turned off simultaneously.
(b) [Reserved]
(c) Combustion safeguards used in connection with electric ignition systems on ovens shall be so designed as to prevent an explosive mixture from accumulating inside the oven before ignition has taken place.
(v) When fuel is supplied and used at line pressure, safety shutoff valves shall be provided in the fuel line leading to the burner. 1 citations
(a) When fuel is supplied in excess of line pressure, safety shutoff valves shall be provided in the fuel line leading to the burners, unless the fuel supply lines are equipped with other automatic valves which will prevent the flow of fuel when the compressing equipment is stopped.
(b) The safety shutoff valve shall be positively tight and shall be tested at least twice monthly.
(c)-(d) [Reserved]
(e) A safety shutoff valve shall require manual operation for reopening after it has closed, or the electric circuit shall be so arranged that it will require a manual operation for reopening the safety shutoff valve.
(f) Manual reset-type safety shutoff valves shall be so arranged that they cannot be locked in an open position by external means.
(g) Where blowers are used for supplying the air for combustion the safety shutoff valve shall be interlocked so that it will close in case of air failure.
(h) Where gas or electric ignition is used, the safety shutoff valve shall close in case of ignition failure. On burners equipped with combustion safeguards, the valve shall close in case of burner flame failure.
(vi) One main, manually operated, fuel shutoff valve shall be provided on each oven, and shall be located ahead of all other valves in the system.
(vii) All individual gas or oil burners with a heating capacity over 150,000 B.t.u. per hour shall be protected by a safeguard which is actuated by the flame and which will react to flame failure in a time interval not to exceed 2 seconds. All safeguards, once having shut down a gas or oil burner, shall require manual resetting and starting of the burner or burners.
(viii) Any space in an oven (except direct fired ovens) which could be filled with an explosive mixture shall be protected by explosion vents. Explosion vents shall be made of minimum weight consistent with adequate insulation.
(a) Explosion doors which have a substantial weight shall be attached by chains or similar means to prevent flying parts from injuring the personnel in case of an explosion.
(b) Where explosion vents are so located that flying parts or gases might endanger the personnel working on or near the oven, internal or external protecting means shall be provided in the form of heavily constructed shields or deflectors made from noncombustible material.
(c) Specifically exempted from the provisions of paragraph paragraph (l)(8)(viii) of this section are heating systems on ovens in which the fuel is admitted only to enclosed spaces which shall have been tested to prove that their construction will resist repeated explosions without deformation are exempt from the requirements of paragraph (l)(8)(viii) (a) and (b) of this section.
(ix)-(x) [Reserved]
(xi) Where the gas supply pressure is substantially higher than that at which the burners of an oven are designed to operate, a gas pressure regulator shall be employed.
(a)-(c) [Reserved]
(d) A relief valve shall be placed on the outlet side of gas pressure regulators where gas is supplied at high pressure. The discharge from this valve shall be piped to the outside of the building.
Source: eCFR, text current as of 2026-10-15. Read all of 1910.263.
Export the list: 49 inspections cited 1910.263(l)(9) in the last 3 years, with employer, location, penalty and date.
Purple Belt, $59/moWhere and how often it was cited
| Year | Citations |
|---|---|
| 2023 | 2 |
| 2024 | 9 |
| 2025 | 7 |
| 2026 | 32 |
Top states: PR (35), MN (7), TX (2), HI (1), MA (1)
Largest penalties
| Employer | Location | Penalty for this rule |
|---|---|---|
| ARTISAN CHEF MANUFACTURING, LLC | LAWRENCE, MA | $15,625 |
| THE ORLANDO BAKING COMPANY | CLEVELAND, OH | $14,000 |
| PARGUERA PLAZA, INC. | LAJAS, PR | $9,931 |
| ALO AND JOHN INC. | HORMIGUEROS, PR | $7,094 |
| GUANAJUATO BAKERY | FORT WORTH, TX | $6,775 |
Free toolbox talk
A 5-minute crew talk on 1910.263(l)(9), plus alerts when this rule changes. Free.
OSHA interpretation letters
None exist. OSHA has not published a letter of interpretation for 1910.263(l)(9).
Related parts of this rule
- 1910.263(l) Ovens 50 citations
- 1910.263(l)(9)(ii) 47 citations
- 1910.263(l)(9)(i) 1 citations
- 1910.263(l)(9)(iv)
Get your crew competent
Trainers on Black Belt Safety: Marc Harvey
Trainers and suppliers: feature your business on this rule for $25/month.
Frequently asked questions
Who inspects oven safety devices?
An especially appointed, properly instructed bakery employee, and representatives of the oven manufacturers.
What must happen if a gas pilot fails?
Failure of any gas pilot shall automatically shut off the fuel supply to the burner.
When are quick-acting combustion safeguards needed?
On burners of a capacity exceeding 150,000 B.t.u. per hour equipped with electric ignition.
About this page
Sources
- 29 CFR 1910.263 (eCFR), text current as of 2026-10-15
- U.S. Department of Labor enforcement data: OSHA inspections, citations and accident records, copied nightly; data as of 2026-11-01
3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.