1910.303(b): Examining, installing and using electrical equipment
Electrical equipment must be free from recognized hazards likely to cause death or serious harm. Its safety is judged by things like whether it is suitable for the use (listing or labeling is evidence of that), its strength and durability, insulation, heating and arcing effects, and its rating for voltage and current. Listed or labeled equipment must be installed and used according to the instructions in its listing or labeling, finished wiring must be free of short circuits and unintended grounds, and equipment that interrupts fault current must have an adequate interrupting rating.
Key takeaways
- 1910.303(b) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
- OSHA cited it 3,837 times in the last 3 years, in 3,450 inspections, with $6,212,780 in current penalties.
- 12 deaths are linked to inspections that cited this rule.
- Most citations: TN (391), NY (275), NV (252).
- Related part: 1910.303(b)(2) Installation and use (2,289 citations).
- Free 5-minute toolbox talk for your crew below.
In this article
What this rule covers
29 CFR 1910.303(b) ("Examination, installation, and use of equipment") is one requirement inside 1910.303 General, an OSHA general industry standard (Part 1910, Subpart S). It includes 23 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.
Official text
(b) Examination, installation, and use of equipment — 3,837 citations
(1) Examination. Electric equipment shall be free from recognized hazards that are likely to cause death or serious physical harm to employees. Safety of equipment shall be determined using the following considerations: Open (b)(1) 489 citations
(i) Suitability for installation and use in conformity with the provisions of this subpart; Open (b)(1)(i) 24 citations
Suitability of equipment for an identified purpose may be evidenced by listing or labeling for that identified purpose.
(ii) Mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided; Open (b)(1)(ii) 38 citations
(iii) Wire-bending and connection space;
(iv) Electrical insulation; Open (b)(1)(iv) 47 citations
(v) Heating effects under all conditions of use; 1 citations
(vi) Arcing effects; 3 citations
(vii) Classification by type, size, voltage, current capacity, and specific use; and 8 citations
(viii) Other factors that contribute to the practical safeguarding of persons using or likely to come in contact with the equipment. Open (b)(1)(viii) 20 citations
(2) Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. Open (b)(2) 2,289 citations
(3) Insulation integrity. Completed wiring installations shall be free from short circuits and from grounds other than those required or permitted by this subpart. 6 citations
(4) Interrupting rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating sufficient for the nominal circuit voltage and the current that is available at the line terminals of the equipment. Equipment intended to interrupt current at other than fault levels shall have an interrupting rating at nominal circuit voltage sufficient for the current that must be interrupted. 5 citations
(5) Circuit impedance and other characteristics. The overcurrent protective devices, the total impedance, the component short-circuit current ratings, and other characteristics of the circuit to be protected shall be selected and coordinated to permit the circuit protective devices used to clear a fault to do so without the occurrence of extensive damage to the electrical components of the circuit. This fault shall be assumed to be either between two or more of the circuit conductors, or between any circuit conductor and the grounding conductor or enclosing metal raceway. 1 citations
(6) Deteriorating agents. Unless identified for use in the operating environment, no conductors or equipment shall be located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that have a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures. Open (b)(6) 75 citations
(7) Mechanical execution of work. Electric equipment shall be installed in a neat and workmanlike manner. Open (b)(7) 827 citations
(i) Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment. Open (b)(7)(i) 349 citations
(ii) Conductors shall be racked to provide ready and safe access in underground and subsurface enclosures that persons enter for installation and maintenance.
(iii) Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, may not be damaged or contaminated by foreign materials such as paint, plaster, cleaners, abrasives, or corrosive residues. Open (b)(7)(iii) 11 citations
(iv) There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating. Open (b)(7)(iv) 398 citations
(8) Mounting and cooling of equipment. Open (b)(8) 145 citations
(i) Electric equipment shall be firmly secured to the surface on which it is mounted. Open (b)(8)(i) 143 citations
Wooden plugs driven into holes in masonry, concrete, plaster, or similar materials are not considered secure means of fastening electric equipment.
(ii) Electric equipment that depends on the natural circulation of air and convection principles for cooling of exposed surfaces shall be installed so that room airflow over such surfaces is not prevented by walls or by adjacent installed equipment. For equipment designed for floor mounting, clearance between top surfaces and adjacent surfaces shall be provided to dissipate rising warm air.
(iii) Electric equipment provided with ventilating openings shall be installed so that walls or other obstructions do not prevent the free circulation of air through the equipment. 2 citations
Source: eCFR, text current as of 2026-10-15. Read all of 1910.303.
Injuries linked to this rule
12 deaths are linked to inspections where OSHA cited 1910.303(b).
At 9:00 a.m. on February 28, 2025, Employee #1 exited the forklift without setting the parking brake. The forklift rolled and trapped the employee's foot, pinning him between the forklift and the container. Employee #1 was found unconscious after he fell backwards striking his head.…
Full case list with employer, penalty, filters and download is part of OSHA Data (Purple Belt).
Unlock with Purple BeltWhere and how often it was cited
| Year | Citations |
|---|---|
| 2023 | 271 |
| 2024 | 1,350 |
| 2025 | 1,291 |
| 2026 | 925 |
Top states: TN (391), NY (275), NV (252), VA (245), CT (209)
Largest penalties
| Employer | Location | Penalty for this rule |
|---|---|---|
| MAPS PH MANAGEMENT LLC | QUAKERTOWN, PA | $130,000 |
| STRATEGIC MATERIALS, INC | MIDLOTHIAN, TX | $71,000 |
| THE GOODYEAR TIRE & RUBBER COMPANY | DANVILLE, VA | $59,405 |
| ABC SUPPLY CO. INC. | KANSAS CITY, KS | $35,765 |
| JINDAL TUBULAR USA LLC | BAY SAINT LOUIS, MS | $30,422 |
Free toolbox talk
A 5-minute crew talk on 1910.303(b), plus alerts when this rule changes. Free.
OSHA interpretation letters
- Confidentiality of employee post-exposure evaluations as it pertains to the Bloodborne Pathogens Standard; use of portable fans in phlebotomy collection rooms. (2009-11-10)
- Approval of employee-furnished equipment for use in hazardous locations; definition of "electric utilization equipment." (2006-07-24)
- Acceptability of using a light switch as a disconnecting means for the electrical lockout/tagout standard. (2005-10-27)
- Use of personal cooling fans listed for "residential use only" in an industrial setting. (2005-02-01)
- Requirements for protecting against the automatic restart of low-voltage light-duty woodworking and metalworking equipment following an unscheduled electrical outage. (2005-01-31)
- Electrical equipment approved by a NRTL is acceptable to OSHA. (2004-05-11)
- Installation and use of electrical equipment must be consistent with NRTL intructions for that equipment. (2003-08-26)
- Workplace use of electrical equipment designated as "Household Use Only" and recordkeeping requirements. (2003-07-16)
- Electrical conductors and equipment must be approved and used according to its listing/label. (2003-05-27)
- Compliance requirements for relocatable power taps or "power strips" (2002-11-18)
- Applicable OSHA standards and safety considerations for microwave device use in a laboratory (2002-08-08)
- Clarification of under voltage protection on metal-working equipment and emergency stop devices. (1999-04-28)
- Acceptable job-made extension cords. (1992-06-17)
- The listing requirements in the U.S. for Industrial Packaging equipment. (1990-02-28)
Related parts of this rule
- 1910.303(b)(2) Installation and use 2,289 citations
- 1910.303(b)(7) Mechanical execution of work 827 citations
- 1910.303(b)(1) Examination 489 citations
- 1910.303(b)(7)(iv) 398 citations
- 1910.303(b)(7)(i) 349 citations
- 1910.303(b)(8) Mounting and cooling of equipment 145 citations
- 1910.303(b)(8)(i) 143 citations
- 1910.303(b)(6) Deteriorating agents 75 citations
- 1910.303(b)(1)(iv) 47 citations
- 1910.303(b)(1)(ii) 38 citations
- 1910.303(b)(1)(i) 24 citations
- 1910.303(b)(1)(viii) 20 citations
Get your crew competent
Trainers on Black Belt Safety: Marc Harvey, Dana Reyes
Trainers and suppliers: feature your business on this rule for $25/month.
Frequently asked questions
Do we have to follow the manufacturer's instructions for listed equipment?
Yes. Listed or labeled equipment must be installed and used in accordance with the instructions included in the listing or labeling.
How is electrical equipment judged safe?
By its suitability for the installation and use, mechanical strength and durability, wire-bending and connection space, insulation, heating and arcing effects, its classification and rating, and other factors that protect people.
About this page
Sources
- 29 CFR 1910.303 (eCFR), text current as of 2026-10-15
- U.S. Department of Labor enforcement data: OSHA inspections, citations and accident records, copied nightly; data as of 2026-10-20
3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.