1910.303(b): Examining, installing and using electrical equipment

By Black Belt Safety Editorial Team Official text as of October 15, 2026 Data updated October 20, 2026 6 min read

In plain words:

Electrical equipment must be free from recognized hazards likely to cause death or serious harm. Its safety is judged by things like whether it is suitable for the use (listing or labeling is evidence of that), its strength and durability, insulation, heating and arcing effects, and its rating for voltage and current. Listed or labeled equipment must be installed and used according to the instructions in its listing or labeling, finished wiring must be free of short circuits and unintended grounds, and equipment that interrupts fault current must have an adequate interrupting rating.

Key takeaways

  • 1910.303(b) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
  • OSHA cited it 3,837 times in the last 3 years, in 3,450 inspections, with $6,212,780 in current penalties.
  • 12 deaths are linked to inspections that cited this rule.
  • Most citations: TN (391), NY (275), NV (252).
  • Related part: 1910.303(b)(2) Installation and use (2,289 citations).
  • Free 5-minute toolbox talk for your crew below.
3,837citations, 3 years
$6,212,780current penalties
3,450inspections
12linked deaths
In this article
  1. What this rule covers
  2. Official text
  3. Injuries linked to this rule
  4. Where and how often it was cited
  5. Free toolbox talk
  6. OSHA interpretation letters
  7. Related parts of this rule
  8. Get your crew competent
  9. Frequently asked questions
  10. About this page

What this rule covers

29 CFR 1910.303(b) ("Examination, installation, and use of equipment") is one requirement inside 1910.303 General, an OSHA general industry standard (Part 1910, Subpart S). It includes 23 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(b) Examination, installation, and use of equipment — 3,837 citations

(1) Examination. Electric equipment shall be free from recognized hazards that are likely to cause death or serious physical harm to employees. Safety of equipment shall be determined using the following considerations: Open (b)(1) 489 citations

(i) Suitability for installation and use in conformity with the provisions of this subpart; Open (b)(1)(i) 24 citations

Suitability of equipment for an identified purpose may be evidenced by listing or labeling for that identified purpose.

(ii) Mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided; Open (b)(1)(ii) 38 citations

(iii) Wire-bending and connection space;

(iv) Electrical insulation; Open (b)(1)(iv) 47 citations

(v) Heating effects under all conditions of use; 1 citations

(vi) Arcing effects; 3 citations

(vii) Classification by type, size, voltage, current capacity, and specific use; and 8 citations

(viii) Other factors that contribute to the practical safeguarding of persons using or likely to come in contact with the equipment. Open (b)(1)(viii) 20 citations

(2) Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling. Open (b)(2) 2,289 citations

(3) Insulation integrity. Completed wiring installations shall be free from short circuits and from grounds other than those required or permitted by this subpart. 6 citations

(4) Interrupting rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating sufficient for the nominal circuit voltage and the current that is available at the line terminals of the equipment. Equipment intended to interrupt current at other than fault levels shall have an interrupting rating at nominal circuit voltage sufficient for the current that must be interrupted. 5 citations

(5) Circuit impedance and other characteristics. The overcurrent protective devices, the total impedance, the component short-circuit current ratings, and other characteristics of the circuit to be protected shall be selected and coordinated to permit the circuit protective devices used to clear a fault to do so without the occurrence of extensive damage to the electrical components of the circuit. This fault shall be assumed to be either between two or more of the circuit conductors, or between any circuit conductor and the grounding conductor or enclosing metal raceway. 1 citations

(6) Deteriorating agents. Unless identified for use in the operating environment, no conductors or equipment shall be located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that have a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures. Open (b)(6) 75 citations

(7) Mechanical execution of work. Electric equipment shall be installed in a neat and workmanlike manner. Open (b)(7) 827 citations

(i) Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment. Open (b)(7)(i) 349 citations

(ii) Conductors shall be racked to provide ready and safe access in underground and subsurface enclosures that persons enter for installation and maintenance.

(iii) Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, may not be damaged or contaminated by foreign materials such as paint, plaster, cleaners, abrasives, or corrosive residues. Open (b)(7)(iii) 11 citations

(iv) There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating. Open (b)(7)(iv) 398 citations

(8) Mounting and cooling of equipment. Open (b)(8) 145 citations

(i) Electric equipment shall be firmly secured to the surface on which it is mounted. Open (b)(8)(i) 143 citations

Wooden plugs driven into holes in masonry, concrete, plaster, or similar materials are not considered secure means of fastening electric equipment.

(ii) Electric equipment that depends on the natural circulation of air and convection principles for cooling of exposed surfaces shall be installed so that room airflow over such surfaces is not prevented by walls or by adjacent installed equipment. For equipment designed for floor mounting, clearance between top surfaces and adjacent surfaces shall be provided to dissipate rising warm air.

(iii) Electric equipment provided with ventilating openings shall be installed so that walls or other obstructions do not prevent the free circulation of air through the equipment. 2 citations

Source: eCFR, text current as of 2026-10-15. Read all of 1910.303.

Injuries linked to this rule

12 deaths are linked to inspections where OSHA cited 1910.303(b).

Employee sustains head injury when struck by forklift, later
2025-02-28 · Fatal · HOUSTON, TX

At 9:00 a.m. on February 28, 2025, Employee #1 exited the forklift without setting the parking brake. The forklift rolled and trapped the employee's foot, pinning him between the forklift and the container. Employee #1 was found unconscious after he fell backwards striking his head.…

See all 12 cases

Full case list with employer, penalty, filters and download is part of OSHA Data (Purple Belt).

Unlock with Purple Belt

Where and how often it was cited

YearCitations
2023271
20241,350
20251,291
2026925

Top states: TN (391), NY (275), NV (252), VA (245), CT (209)

Largest penalties

EmployerLocationPenalty for this rule
MAPS PH MANAGEMENT LLCQUAKERTOWN, PA$130,000
STRATEGIC MATERIALS, INCMIDLOTHIAN, TX$71,000
THE GOODYEAR TIRE & RUBBER COMPANYDANVILLE, VA$59,405
ABC SUPPLY CO. INC.KANSAS CITY, KS$35,765
JINDAL TUBULAR USA LLCBAY SAINT LOUIS, MS$30,422

Free toolbox talk

A 5-minute crew talk on 1910.303(b), plus alerts when this rule changes. Free.




OSHA interpretation letters

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey, Dana Reyes

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

Do we have to follow the manufacturer's instructions for listed equipment?

Yes. Listed or labeled equipment must be installed and used in accordance with the instructions included in the listing or labeling.

How is electrical equipment judged safe?

By its suitability for the installation and use, mechanical strength and durability, wire-bending and connection space, insulation, heating and arcing effects, its classification and rating, and other factors that protect people.

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Scroll to top