29 CFR 1910 · General Industry · Subpart S

1910.304(b)(4): Outlet Device Ratings

By Black Belt Safety Editorial Team Official text as of octubre 15, 2026 Data updated octubre 20, 2026 3 min read

In plain words:

Employers must make sure outlet devices have an ampere rating not less than the load they serve. On branch circuits over 20 amps, lampholders must be heavy-duty, and receptacles must meet rating rules: a single receptacle on its own circuit must be rated at least the circuit rating, and receptacles on multi-outlet circuits must follow Tables S-4 and S-5.

Key takeaways

  • 1910.304(b)(4) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
  • OSHA cited it 137 times in the last 3 years, in 136 inspections, with $181,351 in current penalties.
  • Most citations: MN (43), TN (43), NJ (17).
  • Related part: 1910.304(b) Branch circuits (279 citations).
  • Free 5-minute toolbox talk for your crew below.
137citations, 3 years
$181,351current penalties
136inspections
0linked injury cases
In this article
  1. What this rule covers
  2. Official text
  3. Where and how often it was cited
  4. Free toolbox talk
  5. OSHA interpretation letters
  6. Related parts of this rule
  7. Get your crew competent
  8. Frequently asked questions
  9. About this page

What this rule covers

29 CFR 1910.304(b)(4) ("Outlet devices") is one requirement inside 1910.304 Wiring design and protection, an OSHA general industry standard (Part 1910, Subpart S). It includes 5 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(4) Outlet devices. Outlet devices shall have an ampere rating not less than the load to be served and shall comply with the following provisions: 137 citations

(i) Where connected to a branch circuit having a rating in excess of 20 amperes, lampholders shall be of the heavy-duty type. A heavy-duty lampholder shall have a rating of not less than 660 watts if of the admedium type and not less than 750 watts if of any other type; and

(ii) Receptacle outlets shall comply with the following provisions: Open (b)(4)(ii) 70 citations

(A) A single receptacle installed on an individual branch circuit shall have an ampere rating of not less than that of the branch circuit;

(B) Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle may not supply a total cord- and plug-connected load in excess of the maximum specified in Table S-4; and Open (b)(4)(ii)(b) 70 citations

(C) Where connected to a branch circuit supplying two or more receptacles or outlets, receptacle ratings shall conform to the values listed in Table S-5; or, where larger than 50 amperes, the receptacle rating may not be less than the branch-circuit rating. However, receptacles of cord- and plug-connected arc welders may have ampere ratings not less than the minimum branch-circuit conductor ampacity.

Source: eCFR, text current as of 2026-10-15. Read all of 1910.304.

Where and how often it was cited

YearCitations
20237
202460
202541
202629

Top states: MN (43), TN (43), NJ (17), CT (12), NV (10)

Largest penalties

EmployerLocationPenalty for this rule
CLASSIC FLOORS & INTERIORS, LLCLAS VEGAS, NV$11,524
IGNITE TEEN TREATMENT LLCLAS VEGAS, NV$10,046
HACKETTSTOWN PUBLIC SCHOOL DISTRICTHACKETTSTOWN, NJ$7,000
HACKETTSTOWN PUBLIC SCHOOLSHACKETTSTOWN, NJ$7,000
HACKETTSTOWN PUBLIC SCHOOLSHACKETTSTOWN, NJ$7,000

Free toolbox talk

A 5-minute crew talk on 1910.304(b)(4), plus alerts when this rule changes. Free.




OSHA interpretation letters

None exist. OSHA has not published a letter of interpretation for 1910.304(b)(4).

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey, Dana Reyes

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

What is the basic rule for outlet devices?

They must have an ampere rating not less than the load to be served.

What lampholders are required on circuits over 20 amps?

Heavy-duty lampholders, rated not less than 660 watts if admedium type and not less than 750 watts for other types.

What rating does a single receptacle on its own branch circuit need?

An ampere rating of not less than that of the branch circuit.

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Desplácese hacia arriba