1910.305(b): Electrical cabinets, boxes and fittings
Conductors entering electrical boxes, cabinets and fittings must be protected from abrasion, and the openings they enter through must be effectively closed. Unused openings must also be closed, and each cable must be secured to the cabinet or box, with a narrow exception for certain nonmetallic cables run through short raceways. Pull boxes, junction boxes and fittings need covers made for the purpose, and metal covers must be grounded.
Key takeaways
- 1910.305(b) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
- OSHA cited it 2,745 times in the last 3 years, in 2,437 inspections, with $4,055,489 in current penalties.
- 14 deaths are linked to inspections that cited this rule.
- Most citations: TN (317), MD (189), VA (170).
- Related part: 1910.305(b)(2) Covers and canopies (1,373 citations).
- Free 5-minute toolbox talk for your crew below.
In this article
What this rule covers
29 CFR 1910.305(b) ("Cabinets, boxes, and fittings") is one requirement inside 1910.305 Wiring methods, components, and equipment for general use, an OSHA general industry standard (Part 1910, Subpart S). It includes 18 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.
Official text
(b) Cabinets, boxes, and fittings — 2,745 citations
(1) Conductors entering boxes, cabinets, or fittings. Open (b)(1) 1,314 citations
(i) Conductors entering cutout boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. Open (b)(1)(i) 202 citations
(ii) Unused openings in cabinets, boxes, and fittings shall be effectively closed. Open (b)(1)(ii) 1,058 citations
(iii) Where cable is used, each cable shall be secured to the cabinet, cutout box, or meter socket enclosure. However, where cable with an entirely nonmetallic sheath enters the top of a surface-mounted enclosure through one or more nonflexible raceways not less than 457 mm (18 in.) or more than 3.05 m (10.0 ft) in length, the cable need not be secured to the cabinet, box, or enclosure provided all of the following conditions are met: Open (b)(1)(iii) 21 citations
(A) Each cable is fastened within 305 mm (12 in.) of the outer end of the raceway, measured along the sheath;
(B) The raceway extends directly above the enclosure and does not penetrate a structural ceiling;
(C) A fitting is provided on each end of the raceway to protect the cable from abrasion, and the fittings remain accessible after installation;
(D) The raceway is sealed or plugged at the outer end using approved means so as to prevent access to the enclosure through the raceway; 7 citations
(E) The cable sheath is continuous through the raceway and extends into the enclosure not less than 6.35 mm (0.25 in.) beyond the fitting;
(F) The raceway is fastened at its outer end and at other points as necessary; and 8 citations
(G) Where installed as conduit or tubing, the allowable cable fill does not exceed that permitted for complete conduit or tubing systems.
(2) Covers and canopies. Open (b)(2) 1,373 citations
(i) All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear. Open (b)(2)(i) 1,349 citations
(ii) Where a fixture canopy or pan is used, any combustible wall or ceiling finish exposed between the edge of the canopy or pan and the outlet box shall be covered with noncombustible material.
(3) Pull and junction boxes for systems over 600 volts, nominal. In addition to other requirements in this section, the following requirements apply to pull and junction boxes for systems over 600 volts, nominal: Open (b)(3) 58 citations
(i) Boxes shall provide a complete enclosure for the contained conductors or cables. 9 citations
(ii) Boxes shall be closed by suitable covers securely fastened in place. Open (b)(3)(ii) 46 citations
Underground box covers that weigh over 45.4 kg (100 lbs) meet this requirement.
(iii) Covers for boxes shall be permanently marked “HIGH VOLTAGE.” The marking shall be on the outside of the box cover and shall be readily visible and legible. 3 citations
Source: eCFR, text current as of 2026-10-15. Read all of 1910.305.
Injuries linked to this rule
14 deaths are linked to inspections where OSHA cited 1910.305(b).
At 7:00 p.m. on February 24, 2025, Employee #1 entered a grain bin while operating an auger and became caught in the sweep auger. The employee was fatally injured.
Full case list with employer, penalty, filters and download is part of OSHA Data (Purple Belt).
Unlock with Purple BeltWhere and how often it was cited
| Year | Citations |
|---|---|
| 2023 | 189 |
| 2024 | 1,016 |
| 2025 | 937 |
| 2026 | 603 |
Top states: TN (317), MD (189), VA (170), NY (141), PR (136)
Largest penalties
| Employer | Location | Penalty for this rule |
|---|---|---|
| THE GOODYEAR TIRE & RUBBER COMPANY | DANVILLE, VA | $47,625 |
| DCR | BAYAMON, PR | $35,000 |
| FLORENCE HARDWOODS, LLC | FLORENCE, WI | $34,378 |
| NUCO FOODS, LLC | ELIZABETHTOWN, PA | $32,770 |
| LOWE'S HOME CENTERS LLC | HONOLULU, HI | $23,646 |
Free toolbox talk
A 5-minute crew talk on 1910.305(b), plus alerts when this rule changes. Free.
OSHA interpretation letters
- Fixed Wiring in Research Facilities and High Voltage Cable Tray Systems at Department of Energy (DOE) Research Laboratories (2004-03-31)
- Guidance on approval requirments for general circuit breaker panel swich lockouts in General Industry. (2002-06-24)
- "Approval" of flexible corrugated plastic covers and generic circuit breaker panel switch lockouts. (2000-06-28)
Related parts of this rule
- 1910.305(b)(2) Covers and canopies 1,373 citations
- 1910.305(b)(2)(i) 1,349 citations
- 1910.305(b)(1) Conductors entering boxes, cabinets, or fittings 1,314 citations
- 1910.305(b)(1)(ii) 1,058 citations
- 1910.305(b)(1)(i) 202 citations
- 1910.305(b)(3) Pull and junction boxes for systems over 600 volts, nominal 58 citations
- 1910.305(b)(3)(ii) 46 citations
- 1910.305(b)(1)(iii) 21 citations
Get your crew competent
Trainers on Black Belt Safety: Marc Harvey, Dana Reyes
Trainers and suppliers: feature your business on this rule for $25/month.
Frequently asked questions
Is an open knockout in an electrical box a violation?
Yes. Unused openings in cabinets, boxes and fittings must be effectively closed.
Do junction boxes need covers?
Yes. All pull boxes, junction boxes and fittings must have covers identified for the purpose, and metal covers must be grounded.
About this page
Sources
- 29 CFR 1910.305 (eCFR), text current as of 2026-10-15
- U.S. Department of Labor enforcement data: OSHA inspections, citations and accident records, copied nightly; data as of 2026-10-20
3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.