1910.305(j)(4): Motor Disconnecting Means

By Black Belt Safety Editorial Team Official text as of octubre 15, 2026 Data updated octubre 20, 2026 5 min read

In plain words:

Each motor controller must have its own disconnecting means within sight of the controller, meaning visible and not more than 50 feet away, with limited exceptions. The disconnect must cut the motor and controller from all ungrounded supply conductors, clearly show if it is open (off) or closed (on), and be readily accessible.

Key takeaways

  • 1910.305(j)(4) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
  • OSHA cited it 13 times in the last 3 years, in 13 inspections, with $51,253 in current penalties.
  • Most citations: NJ (4), AL (2), TX (2).
  • Related part: 1910.305(j) Equipment for general use (359 citations).
  • Free 5-minute toolbox talk for your crew below.
13citations, 3 years
$51,253current penalties
13inspections
0linked injury cases
In this article
  1. What this rule covers
  2. Official text
  3. Where and how often it was cited
  4. Free toolbox talk
  5. OSHA interpretation letters
  6. Related parts of this rule
  7. Get your crew competent
  8. Frequently asked questions
  9. About this page

What this rule covers

29 CFR 1910.305(j)(4) ("Motors") is one requirement inside 1910.305 Wiring methods, components, and equipment for general use, an OSHA general industry standard (Part 1910, Subpart S). It includes 11 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(4) Motors. This paragraph applies to motors, motor circuits, and controllers. 13 citations

(i) If specified in paragraph (j)(4) of this section that one piece of equipment shall be “within sight of” another piece of equipment, the piece of equipment shall be visible and not more than 15.24 m (50.0 ft) from the other.

(ii) An individual disconnecting means shall be provided for each controller. A disconnecting means shall be located within sight of the controller location. However, a single disconnecting means may be located adjacent to a group of coordinated controllers mounted adjacent to each other on a multi-motor continuous process machine. The controller disconnecting means for motor branch circuits over 600 volts, nominal, may be out of sight of the controller, if the controller is marked with a warning label giving the location and identification of the disconnecting means that is to be locked in the open position. 4 citations

(iii) The disconnecting means shall disconnect the motor and the controller from all ungrounded supply conductors and shall be so designed that no pole can be operated independently. Open (j)(4)(iii)

(iv) The disconnecting means shall plainly indicate whether it is in the open (off) or closed (on) position.

(v) The disconnecting means shall be readily accessible. If more than one disconnect is provided for the same equipment, only one need be readily accessible. 9 citations

(vi) An individual disconnecting means shall be provided for each motor, but a single disconnecting means may be used for a group of motors under any one of the following conditions:

(A) If a number of motors drive several parts of a single machine or piece of apparatus, such as a metal or woodworking machine, crane, or hoist;

(B) If a group of motors is under the protection of one set of branch-circuit protective devices; or

(C) If a group of motors is in a single room within sight of the location of the disconnecting means.

(vii) Motors, motor-control apparatus, and motor branch-circuit conductors shall be protected against overheating due to motor overloads or failure to start, and against short-circuits or ground faults. These provisions do not require overload protection that will stop a motor where a shutdown is likely to introduce additional or increased hazards, as in the case of fire pumps, or where continued operation of a motor is necessary for a safe shutdown of equipment or process and motor overload sensing devices are connected to a supervised alarm.

(viii) Where live parts of motors or controllers operating at over 150 volts to ground are guarded against accidental contact only by location, and where adjustment or other attendance may be necessary during the operation of the apparatus, suitable insulating mats or platforms shall be provided so that the attendant cannot readily touch live parts unless standing on the mats or platforms.

Source: eCFR, text current as of 2026-10-15. Read all of 1910.305.

Where and how often it was cited

YearCitations
20245
20252
20266

Top states: NJ (4), AL (2), TX (2), VA (1), PA (1)

Largest penalties

EmployerLocationPenalty for this rule
MDLG, INC.PHENIX CITY, AL$16,131
QUALITY TRAILER PRODUCTS LLCSEAGOVILLE, TX$7,803
CINNAMINSON BOE TRANSPORTATION & MAINTENANCE FACILITIESCINNAMINSON, NJ$7,000
MAPLE SHADE BOARD OF EDUCATION BUILDINGS & GROUNDSMAPLE SHADE, NJ$7,000
WISEMAN MINISTRIES, INC.DE BERRY, TX$3,354

Free toolbox talk

A 5-minute crew talk on 1910.305(j)(4), plus alerts when this rule changes. Free.




OSHA interpretation letters

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey, Dana Reyes

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

What does within sight mean for motors?

Visible and not more than 15.24 m (50.0 ft) from the other equipment.

Must a disconnect show its position?

Yes. It must plainly indicate whether it is in the open (off) or closed (on) position.

Can one disconnect serve several motors?

Yes, under listed conditions, such as motors driving parts of a single machine.

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Desplácese hacia arriba