1910.333(c): Working on or Near Exposed Energized Parts
Only qualified persons may work on electric circuit parts or equipment that have not been deenergized under the lockout rules, and they must know special precautionary techniques, PPE, insulating and shielding materials and insulated tools. Before work near overhead lines, employers must have the lines deenergized and grounded or provide other protective measures such as guarding, isolating or insulating that prevent direct or indirect contact.
Key takeaways
- 1910.333(c) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
- OSHA cited it 200 times in the last 3 years, in 157 inspections, with $930,111 in current penalties.
- 15 deaths are linked to inspections that cited this rule.
- Most citations: TX (27), NC (25), FL (24).
- Related part: 1910.333(c)(3) Overhead lines (110 citations).
- Free 5-minute toolbox talk for your crew below.
In this article
What this rule covers
29 CFR 1910.333(c) ("Working on or near exposed energized parts") is one requirement inside 1910.333 Selection and use of work practices, an OSHA general industry standard (Part 1910, Subpart S). It includes 23 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.
Official text
(c) Working on or near exposed energized parts — 200 citations
(1) Application. This paragraph applies to work performed on exposed live parts (involving either direct contact or contact by means of tools or materials) or near enough to them for employees to be exposed to any hazard they present.
(2) Work on energized equipment. Only qualified persons may work on electric circuit parts or equipment that have not been deenergized under the procedures of paragraph (b) of this section. Such persons shall be capable of working safely on energized circuits and shall be familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools. Open (c)(2) 61 citations
(3) Overhead lines. If work is to be performed near overhead lines, the lines shall be deenergized and grounded, or other protective measures shall be provided before work is started. If the lines are to be deenergized, arrangements shall be made with the person or organization that operates or controls the electric circuits involved to deenergize and ground them. If protective measures, such as guarding, isolating, or insulating are provided, these precautions shall prevent employees from contacting such lines directly with any part of their body or indirectly through conductive materials, tools, or equipment. Open (c)(3) 110 citations
The work practices used by qualified persons installing insulating devices on overhead power transmission or distribution lines are covered by § 1910.269 of this part, not by §§ 1910.332 through 1910.335 of this part. Under paragraph (c)(2) of this section, unqualified persons are prohibited from performing this type of work.
(i) Unqualified persons. Open (c)(3)(i) 46 citations
(A) When an unqualified person is working in an elevated position near overhead lines, the location shall be such that the person and the longest conductive object he or she may contact cannot come closer to any unguarded, energized overhead line than the following distances: Open (c)(3)(i)(a) 36 citations
(1) For voltages to ground 50kV or below—10 ft. (305 cm);
(2) For voltages to ground over 50kV—10 ft. (305 cm) plus 4 in. (10 cm) for every 10kV over 50kV.
(B) When an unqualified person is working on the ground in the vicinity of overhead lines, the person may not bring any conductive object closer to unguarded, energized overhead lines than the distances given in paragraph (c)(3)(i)(A) of this section. Open (c)(3)(i)(b) 10 citations
For voltages normally encountered with overhead power lines, objects which do not have an insulating rating for the voltage involved are considered to be conductive.
(ii) Qualified persons. When a qualified person is working in the vicinity of overhead lines, whether in an elevated position or on the ground, the person may not approach or take any conductive object without an approved insulating handle closer to exposed energized parts than shown in Table S-5 unless: 1 citations
(A) The person is insulated from the energized part (gloves, with sleeves if necessary, rated for the voltage involved are considered to be insulation of the person from the energized part on which work is performed), or
(B) The energized part is insulated both from all other conductive objects at a different potential and from the person, or
(C) The person is insulated from all conductive objects at a potential different from that of the energized part.
| Voltage range (phase to phase) | Minimum approach distance |
|---|---|
| 300V and less | Avoid contact. |
| Over 300V, not over 750V | 1 ft. 0 in. (30.5 cm). |
| Over 750V, not over 2kV | l ft. 6 in. (46 cm). |
| Over 2kV, not over 15kV | 2 ft. 0 in. (61 cm). |
| Over 15kV, not over 37kV | 3 ft. 0 in. (91 cm). |
| Over 37kV, not over 87.5kV | 3 ft. 6 in. (107 cm). |
| Over 87.5kV, not over 121kV | 4 ft. 0 in. (122 cm). |
| Over 121kV, not over 140kV | 4 ft. 6 in. (137 cm). |
(iii) Vehicular and mechanical equipment. Open (c)(3)(iii) 27 citations
(A) Any vehicle or mechanical equipment capable of having parts of its structure elevated near energized overhead lines shall be operated so that a clearance of 10 ft. (305 cm) is maintained. If the voltage is higher than 50kV, the clearance shall be increased 4 in. (10 cm) for every 10kV over that voltage. However, under any of the following conditions, the clearance may be reduced: Open (c)(3)(iii)(a) 26 citations
(1) If the vehicle is in transit with its structure lowered, the clearance may be reduced to 4 ft. (122 cm). If the voltage is higher than 50kV, the clearance shall be increased 4 in. (10 cm) for every 10kV over that voltage.
(2) If insulating barriers are installed to prevent contact with the lines, and if the barriers are rated for the voltage of the line being guarded and are not a part of or an attachment to the vehicle or its raised structure, the clearance may be reduced to a distance within the designed working dimensions of the insulating barrier.
(3) If the equipment is an aerial lift insulated for the voltage involved, and if the work is performed by a qualified person, the clearance (between the uninsulated portion of the aerial lift and the power line) may be reduced to the distance given in Table S-5.
(B) Employees standing on the ground may not contact the vehicle or mechanical equipment or any of its attachments, unless: 1 citations
(1) The employee is using protective equipment rated for the voltage; or
(2) The equipment is located so that no uninsulated part of its structure (that portion of the structure that provides a conductive path to employees on the ground) can come closer to the line than permitted in paragraph (c)(3)(iii) of this section.
(C) If any vehicle or mechanical equipment capable of having parts of its structure elevated near energized overhead lines is intentionally grounded, employees working on the ground near the point of grounding may not stand at the grounding location whenever there is a possibility of overhead line contact. Additional precautions, such as the use of barricades or insulation, shall be taken to protect employees from hazardous ground potentials, depending on earth resistivity and fault currents, which can develop within the first few feet or more outward from the grounding point.
(4) Illumination.
(i) Employees may not enter spaces containing exposed energized parts, unless illumination is provided that enables the employees to perform the work safely.
(ii) Where lack of illumination or an obstruction precludes observation of the work to be performed, employees may not perform tasks near exposed energized parts. Employees may not reach blindly into areas which may contain energized parts.
(5) Confined or enclosed work spaces. When an employee works in a confined or enclosed space (such as a manhole or vault) that contains exposed energized parts, the employer shall provide, and the employee shall use, protective shields, protective barriers, or insulating materials as necessary to avoid inadvertent contact with these parts. Doors, hinged panels, and the like shall be secured to prevent their swinging into an employee and causing the employee to contact exposed energized parts. 1 citations
(6) Conductive materials and equipment. Conductive materials and equipment that are in contact with any part of an employee's body shall be handled in a manner that will prevent them from contacting exposed energized conductors or circuit parts. If an employee must handle long dimensional conductive objects (such as ducts and pipes) in areas with exposed live parts, the employer shall institute work practices (such as the use of insulation, guarding, and material handling techniques) which will minimize the hazard. Open (c)(6) 10 citations
(7) Portable ladders. Portable ladders shall have nonconductive siderails if they are used where the employee or the ladder could contact exposed energized parts. Open (c)(7) 11 citations
(8) Conductive apparel. Conductive articles of jewelry and clothing (such as watch bands, bracelets, rings, key chains, necklaces, metalized aprons, cloth with conductive thread, or metal headgear) may not be worn if they might contact exposed energized parts. However, such articles may be worn if they are rendered nonconductive by covering, wrapping, or other insulating means. 4 citations
(9) Housekeeping duties. Where live parts present an electrical contact hazard, employees may not perform housekeeping duties at such close distances to the parts that there is a possibility of contact, unless adequate safeguards (such as insulating equipment or barriers) are provided. Electrically conductive cleaning materials (including conductive solids such as steel wool, metalized cloth, and silicon carbide, as well as conductive liquid solutions) may not be used in proximity to energized parts unless procedures are followed which will prevent electrical contact. 2 citations
(10) Interlocks. Only a qualified person following the requirements of paragraph (c) of this section may defeat an electrical safety interlock, and then only temporarily while he or she is working on the equipment. The interlock system shall be returned to its operable condition when this work is completed. 1 citations
[55 FR 32016, Aug. 6, 1990; 55 FR 46053, Nov. 1, 1990, as amended at 59 FR 4476, Jan. 31, 1994]
Source: eCFR, text current as of 2026-10-15. Read all of 1910.333.
Injuries linked to this rule
15 deaths are linked to inspections where OSHA cited 1910.333(c).
At 9:03 a.m. on February 6, 2025, Employee #1 working for a tree care company was trimming a tree from a self-propelled boom lift. Using a 21-foot aluminum pole saw to clear up the canopy on a residential property, he turned his body causing him…
Full case list with employer, penalty, filters and download is part of OSHA Data (Purple Belt).
Unlock with Purple BeltWhere and how often it was cited
| Year | Citations |
|---|---|
| 2023 | 24 |
| 2024 | 69 |
| 2025 | 63 |
| 2026 | 44 |
Top states: TX (27), NC (25), FL (24), NY (14), MA (11)
Largest penalties
| Employer | Location | Penalty for this rule |
|---|---|---|
| GAGE TREE SERVICE LLC | CHUGIAK, AK | $99,308 |
| HUNT FOREST PRODUCTS, LLC | POLLOCK, LA | $33,100 |
| 108756 - DISCOUNT TREE CARE INC | MAYER, MN | $25,000 |
| OSMOSE UTILITIES SERVICES, INC. | WEST HELENA, AR | $21,508 |
| BAGLEY & WEBB LANDSCAPING, LLC. | JACKSONVILLE, FL | $20,970 |
Free toolbox talk
A 5-minute crew talk on 1910.333(c), plus alerts when this rule changes. Free.
OSHA interpretation letters
- Electrical Busway Hot Swappable Plug-In Units (2025-08-25)
- Lockout/tagout of electrical hazards by workers who install, maintain, repair or replace premises wiring systems. (2015-08-05)
- Clarification about 29 CFR 1910.333 and 29 CFR 1910.147 as they relate to work inside an electrical panel and on related equipment. (2006-07-28)
- Qualifications for resetting circuits or replacing fuses; electrical enclosures must be approved. (2001-11-19)
- Qualified employee requirements for the servicing and maintenance of electrical equipment. (1993-09-09)
Related parts of this rule
- 1910.333(c)(3) Overhead lines 110 citations
- 1910.333(c)(2) Work on energized equipment 61 citations
- 1910.333(c)(3)(i) Unqualified persons 46 citations
- 1910.333(c)(3)(i)(A) 36 citations
- 1910.333(c)(3)(iii) Vehicular and mechanical equipment 27 citations
- 1910.333(c)(3)(iii)(A) 26 citations
- 1910.333(c)(7) Portable ladders 11 citations
- 1910.333(c)(6) Conductive materials and equipment 10 citations
- 1910.333(c)(3)(i)(B) 10 citations
Get your crew competent
Trainers on Black Belt Safety: Marc Harvey, Dana Reyes
Trainers and suppliers: feature your business on this rule for $25/month.
Frequently asked questions
Who can work on energized parts?
Only qualified persons, who must be capable of working safely on energized circuits and familiar with special techniques, PPE, insulating and shielding materials, and insulated tools.
What must happen before work near overhead lines?
The lines must be deenergized and grounded, or other protective measures provided before work is started.
Who arranges to deenergize overhead lines?
Arrangements must be made with the person or organization that operates or controls the electric circuits involved.
About this page
Sources
- 29 CFR 1910.333 (eCFR), text current as of 2026-10-15
- U.S. Department of Labor enforcement data: OSHA inspections, citations and accident records, copied nightly; data as of 2026-10-22
3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.