1926.404(f)(1)(iv): Grounding AC Systems of 50 to 1000 Volts

By Black Belt Safety Editorial Team Official text as of octubre 15, 2026 Data updated octubre 20, 2026 3 min read

In plain words:

AC systems of 50 volts to 1000 volts must be grounded if the system can be grounded so the maximum voltage to ground on ungrounded conductors does not exceed 150 volts, if it is a 480Y/277 or 240/120 volt 3-phase 4-wire system as described, or if a service conductor is uninsulated, unless exempted by (f)(1)(v).

Key takeaways

  • 1926.404(f)(1)(iv) is part of OSHA's construction standards (29 CFR Part 1926, Subpart K).
  • OSHA cited it 2 times in the last 3 years, in 2 inspections, with $15,527 in current penalties.
  • 1 death is linked to inspections that cited this rule.
  • Related part: 1926.404(f) Grounding (241 citations).
  • Free 5-minute toolbox talk for your crew below.
2citations, 3 years
$15,527current penalties
2inspections
1linked deaths
In this article
  1. What this rule covers
  2. Official text
  3. Injuries linked to this rule
  4. Where and how often it was cited
  5. Free toolbox talk
  6. OSHA interpretation letters
  7. Related parts of this rule
  8. Get your crew competent
  9. Frequently asked questions
  10. About this page

What this rule covers

29 CFR 1926.404(f)(1)(iv) ("AC systems, 50 volts to 1000 volts") is one requirement inside 1926.404 Wiring design and protection, an OSHA construction standard (Part 1926, Subpart K). It includes 4 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(iv) AC systems, 50 volts to 1000 volts. AC systems of 50 volts to 1000 volts shall be grounded under any of the following conditions, unless exempted by paragraph (f)(1)(v) of this section: 2 citations

(A) If the system can be so grounded that the maximum voltage to ground on the ungrounded conductors does not exceed 150 volts;

(B) If the system is nominally rated 480Y/277 volt, 3-phase, 4-wire in which the neutral is used as a circuit conductor;

(C) If the system is nominally rated 240/120 volt, 3-phase, 4-wire in which the midpoint of one phase is used as a circuit conductor; or

(D) If a service conductor is uninsulated.

Source: eCFR, text current as of 2026-10-15. Read all of 1926.404.

Injuries linked to this rule

1 death is linked to inspections where OSHA cited 1926.404(f)(1)(iv).

Employee is electrocuted while installing chiller system
2024-06-06 · Fatal · DALLAS, TX

At 1:40 p.m. on June 6, 2024, Employee #1, employed by a company installing a temporary cooling chiller system, was working on electrical connections. The employee was running 50-foot cables (4-AWG) from the rooftop to connect to the electrical panel and the chiller's disconnect on…

Where and how often it was cited

Free toolbox talk

A 5-minute crew talk on 1926.404(f)(1)(iv), plus alerts when this rule changes. Free.




OSHA interpretation letters

None exist. OSHA has not published a letter of interpretation for 1926.404(f)(1)(iv).

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey, Dana Reyes

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

When must a 50 to 1000 volt AC system be grounded?

Under any of the listed conditions, such as when the maximum voltage to ground on ungrounded conductors would not exceed 150 volts.

Does a 480Y/277 volt system need grounding?

Yes, if it is nominally rated 480Y/277 volt, 3-phase, 4-wire with the neutral used as a circuit conductor.

Are there exceptions?

Yes. Systems exempted by paragraph (f)(1)(v) are not required to be grounded.

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Desplácese hacia arriba