29 CFR 1910 · General Industry · Subpart H

1910.107(b)(5)(i): Spray Booth Air Velocity

By Black Belt Safety Editorial Team Official text as of October 15, 2026 Data updated November 17, 2026 3 min read

In plain words:

Spray booths, except for electrostatic spraying, must be designed, installed and maintained so the average air velocity over the open face of the booth is not less than 100 linear feet per minute. Electrostatic spraying may use not less than 60 linear feet per minute, or more depending on the material. Visible gauges, audible alarms or pressure devices must show the required velocity is maintained, and filter rolls must be inspected for proper replacement.

Key takeaways

  • 1910.107(b)(5)(i) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart H).
  • OSHA cited it 150 times in the last 3 years, in 148 inspections, with $292,002 in current penalties.
  • Most citations: TN (13), NC (13), MN (12).
  • Related part: 1910.107(b) Spray booths (564 citations).
  • Free 5-minute toolbox talk for your crew below.

Get the free 5-minute toolbox talk on 1910.107(b)(5)(i) ↓

150citations, 3 years
$292,002current penalties
148inspections
0linked injury cases
In this article
  1. What this rule covers
  2. Official text
  3. Where and how often it was cited
  4. Free toolbox talk
  5. OSHA interpretation letters
  6. Related parts of this rule
  7. Get your crew competent
  8. Frequently asked questions
  9. About this page

What this rule covers

29 CFR 1910.107(b)(5)(i) is one requirement inside 1910.107 Spray finishing using flammable and combustible materials, an OSHA general industry standard (Part 1910, Subpart H). The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(i) The spraying operations except electrostatic spraying operations shall be so designed, installed and maintained that the average air velocity over the open face of the booth (or booth cross section during spraying operations) shall be not less than 100 linear feet per minute. Electrostatic spraying operations may be conducted with an air velocity over the open face of the booth of not less than 60 linear feet per minute, or more, depending on the volume of the finishing material being applied and its flammability and explosion characteristics. Visible gauges or audible alarm or pressure activated devices shall be installed to indicate or insure that the required air velocity is maintained. Filter rolls shall be inspected to insure proper replacement of filter media. 150 citations

Source: eCFR, text current as of 2026-10-15. Read all of 1910.107.

See every company cited for this rule.

Export the list: 148 inspections cited 1910.107(b)(5)(i) in the last 3 years, with employer, location, penalty and date.

Purple Belt, $59/mo

Where and how often it was cited

YearCitations
20232
202450
202554
202644

Top states: TN (13), NC (13), MN (12), MD (10), VA (10)

Largest penalties

EmployerLocationPenalty for this rule
VTCU, CORP.POCATELLO, ID$16,550
159902 - TRIPLE CROWN TRAILERS NC, LLCHICKORY, NC$11,585
VTCU, CORP.POCATELLO, ID$11,408
OUTDOOR FURNITURE REFINISHING, INC.HOUSTON, TX$11,292
METHODS MACHINE TOOLS, INC.SUDBURY, MA$9,218

Free toolbox talk

A 5-minute crew talk on 1910.107(b)(5)(i), plus alerts when this rule changes. Free.




OSHA interpretation letters

None exist. OSHA has not published a letter of interpretation for 1910.107(b)(5)(i).

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

What air velocity is required in a spray booth?

Not less than 100 linear feet per minute over the open face, except for electrostatic spraying.

What about electrostatic spraying?

Not less than 60 linear feet per minute, or more depending on the volume, flammability and explosion characteristics of the material.

How is the velocity monitored?

With visible gauges, audible alarms or pressure activated devices.

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Scroll to top