1910.269(w): Special Conditions for Electrical Work

By Black Belt Safety Editorial Team Official text as of October 15, 2026 Data updated November 6, 2026 5 min read

In plain words:

Employers must follow added rules for special conditions, including capacitors, current transformer secondaries and series streetlighting. Capacitors must be disconnected and short circuited, waiting at least 5 minutes after disconnection, and lines connected to capacitors must be short circuited before being treated as deenergized. Current transformer secondaries must not be opened while energized.

Key takeaways

  • 1910.269(w) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart R).
  • OSHA cited it 2 times in the last 3 years, in 2 inspections, with $17,039 in current penalties.
  • 1 death is linked to inspections that cited this rule.
  • Related part: 1910.269(w)(7) Backfeed (1 citations).
  • Free 5-minute toolbox talk for your crew below.

Get the free 5-minute toolbox talk on 1910.269(w) ↓

2citations, 3 years
$17,039current penalties
2inspections
1linked deaths
In this article
  1. What this rule covers
  2. Official text
  3. Injuries linked to this rule
  4. Where and how often it was cited
  5. Free toolbox talk
  6. OSHA interpretation letters
  7. Related parts of this rule
  8. Get your crew competent
  9. Frequently asked questions
  10. About this page

What this rule covers

29 CFR 1910.269(w) ("Special conditions") is one requirement inside 1910.269 Electric power generation, transmission, and distribution, an OSHA general industry standard (Part 1910, Subpart R). It includes 22 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(w) Special conditions — 2 citations

(1) Capacitors. The following additional requirements apply to work on capacitors and on lines connected to capacitors.

See paragraphs (m) and (n) of this section for requirements pertaining to the deenergizing and grounding of capacitor installations.

(i) Before employees work on capacitors, the employer shall disconnect the capacitors from energized sources and short circuit the capacitors. The employer shall ensure that the employee short circuiting the capacitors waits at least 5 minutes from the time of disconnection before applying the short circuit,

(ii) Before employees handle the units, the employer shall short circuit each unit in series-parallel capacitor banks between all terminals and the capacitor case or its rack. If the cases of capacitors are on ungrounded substation racks, the employer shall bond the racks to ground.

(iii) The employer shall short circuit any line connected to capacitors before the line is treated as deenergized.

(2) Current transformer secondaries. The employer shall ensure that employees do not open the secondary of a current transformer while the transformer is energized. If the employer cannot deenergize the primary of the current transformer before employees perform work on an instrument, a relay, or other section of a current transformer secondary circuit, the employer shall bridge the circuit so that the current transformer secondary does not experience an open-circuit condition.

(3) Series streetlighting.

(i) If the open-circuit voltage exceeds 600 volts, the employer shall ensure that employees work on series streetlighting circuits in accordance with paragraph (q) or (t) of this section, as appropriate.

(ii) Before any employee opens a series loop, the employer shall deenergize the streetlighting transformer and isolate it from the source of supply or shall bridge the loop to avoid an open-circuit condition.

(4) Illumination. The employer shall provide sufficient illumination to enable the employee to perform the work safely.

(5) Protection against drowning.

(i) Whenever an employee may be pulled or pushed, or might fall, into water where the danger of drowning exists, the employer shall provide the employee with, and shall ensure that the employee uses, a U.S. Coast Guard-approved personal flotation device.

(ii) The employer shall maintain each personal flotation device in safe condition and shall inspect each personal flotation device frequently enough to ensure that it does not have rot, mildew, water saturation, or any other condition that could render the device unsuitable for use.

(iii) An employee may cross streams or other bodies of water only if a safe means of passage, such as a bridge, is available.

(6) Employee protection in public work areas. 1 citations

(i) Traffic-control signs and traffic-control devices used for the protection of employees shall meet § 1926.200(g)(2) of this chapter. 1 citations

(ii) Before employees begin work in the vicinity of vehicular or pedestrian traffic that may endanger them, the employer shall place warning signs or flags and other traffic-control devices in conspicuous locations to alert and channel approaching traffic.

(iii) The employer shall use barricades where additional employee protection is necessary.

(iv) The employer shall protect excavated areas with barricades.

(v) The employer shall display warning lights prominently at night.

(7) Backfeed. When there is a possibility of voltage backfeed from sources of cogeneration or from the secondary system (for example, backfeed from more than one energized phase feeding a common load), the requirements of paragraph (l) of this section apply if employees will work the lines or equipment as energized, and the requirements of paragraphs (m) and (n) of this section apply if employees will work the lines or equipment as deenergized. Open (w)(7) 1 citations

(8) Lasers. The employer shall install, adjust, and operate laser equipment in accordance with § 1926.54 of this chapter.

(9) Hydraulic fluids. Hydraulic fluids used for the insulated sections of equipment shall provide insulation for the voltage involved.

Source: eCFR, text current as of 2026-10-15. Read all of 1910.269.

See every company cited for this rule.

Export the list: 2 inspections cited 1910.269(w) in the last 3 years, with employer, location, penalty and date.

Purple Belt, $59/mo

Injuries linked to this rule

1 death is linked to inspections where OSHA cited 1910.269(w).

Employee is electrocuted and killed
2023-11-12 · Fatal · JACKSON, MO

At 7:00 p.m. on November 12, 2023, an employee climbed a ladder to access the top of an electrical transformer. The employee was verifying the test equipmentwas hooked up appropriately and turned around to exit on the ladder. The employee came into contact with electricity,…

Where and how often it was cited

Free toolbox talk

A 5-minute crew talk on 1910.269(w), plus alerts when this rule changes. Free.




OSHA interpretation letters

None exist. OSHA has not published a letter of interpretation for 1910.269(w).

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

How long must a worker wait before short circuiting a disconnected capacitor?

At least 5 minutes from the time of disconnection.

Can a current transformer secondary be opened while energized?

No. If the primary cannot be deenergized, the employer must bridge the circuit so the secondary does not experience an open-circuit condition.

What applies to series streetlighting over 600 volts?

If the open-circuit voltage exceeds 600 volts, employees must work on series streetlighting circuits under paragraph (q) or (t) of 1910.269, as appropriate.

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Scroll to top