1926.960(g)(2): Estimate of available heat energy
Key takeaways
- 1926.960(g)(2) is part of OSHA's construction standards (29 CFR Part 1926, Subpart V).
- Related part: 1926.960(g) Protection from flames and electric arcs (4 citations).
- Free 5-minute toolbox talk for your crew below.
In this article
What this rule covers
29 CFR 1926.960(g)(2) ("Estimate of available heat energy") is one requirement inside 1926.960 Working on or near exposed energized parts, an OSHA construction standard (Part 1926, Subpart V). The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.
Official text
(2) Estimate of available heat energy. For each employee exposed to hazards from electric arcs, the employer shall make a reasonable estimate of the incident heat energy to which the employee would be exposed.
Appendix E to this subpart provides guidance on estimating available heat energy. The Occupational Safety and Health Administration will deem employers following the guidance in appendix E to this subpart to be in compliance with paragraph (g)(2) of this section. An employer may choose a method of calculating incident heat energy not included in appendix E to this subpart if the chosen method reasonably predicts the incident energy to which the employee would be exposed.
This paragraph does not require the employer to estimate the incident heat energy exposure for every job task performed by each employee. The employer may make broad estimates that cover multiple system areas provided the employer uses reasonable assumptions about the energy-exposure distribution throughout the system and provided the estimates represent the maximum employee exposure for those areas. For example, the employer could estimate the heat energy just outside a substation feeding a radial distribution system and use that estimate for all jobs performed on that radial system.
Source: eCFR, text current as of 2026-10-15. Read all of 1926.960.
Free toolbox talk
A 5-minute crew talk on 1926.960(g)(2), plus alerts when this rule changes. Free.
OSHA interpretation letters
- Selecting protective clothing based on the IEEE National Electrical Safety Code, C-2, 2012, Table 410-1 (2015-07-13)
- Requirements for protective clothing and equipment in the Electric Power Generation, Transmission and Distribution Standard. (2015-07-13)
Related parts of this rule
- 1926.960(g) Protection from flames and electric arcs 4 citations
- 1926.960(g)(5) Arc rating 1 citations
Get your crew competent
Trainers on Black Belt Safety: Marc Harvey
Trainers and suppliers: feature your business on this rule for $25/month.
About this page
Sources
- 29 CFR 1926.960 (eCFR), text current as of 2026-10-15
- U.S. Department of Labor enforcement data: OSHA inspections, citations and accident records, copied nightly
3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.