29 CFR 1910 · General Industry · Subpart S

1910.305(g): Flexible cords and cables

By Black Belt Safety Editorial Team Official text as of octubre 15, 2026 Data updated octubre 20, 2026 5 min read

In plain words:

Flexible cords and cables must be approved for where and how they are used, and may be used only for listed purposes such as pendants, portable lamps and appliances, crane and hoist wiring, connecting equipment that is moved often, and temporary wiring. Cords may not replace a building's fixed wiring, be run through holes in walls, ceilings or floors, through doorways or windows, be attached to or hidden behind building surfaces, or be run in raceways unless the subpart allows it. Cords used for portable lamps and appliances need an attachment plug and must be powered from a receptacle.

Key takeaways

  • 1910.305(g) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
  • OSHA cited it 3,738 times in the last 3 years, in 3,069 inspections, with $3,408,714 in current penalties.
  • 10 deaths are linked to inspections that cited this rule.
  • Most citations: TN (512), MN (235), VA (218).
  • Related part: 1910.305(g)(1) Use of flexible cords and cables (2,566 citations).
  • Free 5-minute toolbox talk for your crew below.
3,738citations, 3 years
$3,408,714current penalties
3,069inspections
10linked deaths
In this article
  1. What this rule covers
  2. Official text
  3. Injuries linked to this rule
  4. Where and how often it was cited
  5. Free toolbox talk
  6. OSHA interpretation letters
  7. Related parts of this rule
  8. Get your crew competent
  9. Frequently asked questions
  10. About this page

What this rule covers

29 CFR 1910.305(g) ("Flexible cords and cables") is one requirement inside 1910.305 Wiring methods, components, and equipment for general use, an OSHA general industry standard (Part 1910, Subpart S). It includes 28 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(g) Flexible cords and cables — 3,738 citations

(1) Use of flexible cords and cables. Open (g)(1) 2,566 citations

(i) Flexible cords and cables shall be approved for conditions of use and location. Open (g)(1)(i) 20 citations

(ii) Flexible cords and cables may be used only for: Open (g)(1)(ii) 9 citations

(A) Pendants; 5 citations

(B) Wiring of fixtures;

(C) Connection of portable lamps or appliances; 1 citations

(D) Portable and mobile signs;

(E) Elevator cables;

(F) Wiring of cranes and hoists;

(G) Connection of stationary equipment to facilitate their frequent interchange;

(H) Prevention of the transmission of noise or vibration;

(I) Appliances where the fastening means and mechanical connections are designed to permit removal for maintenance and repair;

(J) Data processing cables approved as a part of the data processing system;

(K) Connection of moving parts; and

(L) Temporary wiring as permitted in paragraph (a)(2) of this section.

(iii) If used as permitted in paragraphs (g)(1)(ii)(C), (g)(1)(ii)(G), or (g)(1)(ii)(I) of this section, the flexible cord shall be equipped with an attachment plug and shall be energized from an approved receptacle outlet. Open (g)(1)(iii) 14 citations

(iv) Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used: Open (g)(1)(iv) 2,522 citations

(A) As a substitute for the fixed wiring of a structure; Open (g)(1)(iv)(a) 1,437 citations

(B) Where run through holes in walls, ceilings, or floors; Open (g)(1)(iv)(b) 267 citations

(C) Where run through doorways, windows, or similar openings; Open (g)(1)(iv)(c) 145 citations

(D) Where attached to building surfaces; Open (g)(1)(iv)(d) 225 citations

(E) Where concealed behind building walls, ceilings, or floors; or Open (g)(1)(iv)(e) 12 citations

(F) Where installed in raceways, except as otherwise permitted in this subpart.

(v) Flexible cords used in show windows and showcases shall be Type S, SE, SEO, SEOO, SJ, SJE, SJEO, SJEOO, SJO, SJOO, SJT, SJTO, SJTOO, SO, SOO, ST, STO, or STOO, except for the wiring of chain-supported lighting fixtures and supply cords for portable lamps and other merchandise being displayed or exhibited.

(2) Identification, splices, and terminations. Open (g)(2) 1,172 citations

(i) A conductor of a flexible cord or cable that is used as a grounded conductor or an equipment grounding conductor shall be distinguishable from other conductors. Types S, SC, SCE, SCT, SE, SEO, SEOO, SJ, SJE, SJEO, SJEOO, SJO, SJT, SJTO, SJTOO, SO, SOO, ST, STO, and STOO flexible cords and Types G, G-GC, PPE, and W flexible cables shall be durably marked on the surface at intervals not exceeding 610 mm (24 in.) with the type designation, size, and number of conductors.

(ii) Flexible cords may be used only in continuous lengths without splice or tap. Hard-service cord and junior hard-service cord No. 14 and larger may be repaired if spliced so that the splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced. Open (g)(2)(ii) 173 citations

(iii) Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws. Open (g)(2)(iii) 997 citations

Source: eCFR, text current as of 2026-10-15. Read all of 1910.305.

Injuries linked to this rule

10 deaths are linked to inspections where OSHA cited 1910.305(g).

Employee sustains head injury when struck by forklift, later
2025-02-28 · Fatal · HOUSTON, TX

At 9:00 a.m. on February 28, 2025, Employee #1 exited the forklift without setting the parking brake. The forklift rolled and trapped the employee's foot, pinning him between the forklift and the container. Employee #1 was found unconscious after he fell backwards striking his head.…

See all 10 cases

Full case list with employer, penalty, filters and download is part of OSHA Data (Purple Belt).

Unlock with Purple Belt

Where and how often it was cited

YearCitations
2023280
20241,284
20251,332
2026842

Top states: TN (512), MN (235), VA (218), MD (216), PR (162)

Largest penalties

EmployerLocationPenalty for this rule
THE GOODYEAR TIRE & RUBBER COMPANYDANVILLE, VA$45,165
ALBERTSON'S LLCLAS VEGAS, NV$39,012
NUMEAT PACKING INCSAN JUAN, PR$25,536
NEXTRISE USA INC.SEALY, TX$21,000
CZT ENERGY USA, INC.SEALY, TX$21,000

Free toolbox talk

A 5-minute crew talk on 1910.305(g), plus alerts when this rule changes. Free.




OSHA interpretation letters

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey, Dana Reyes

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

Can an extension cord be used as permanent wiring?

No. Flexible cords and cables may not be used as a substitute for the fixed wiring of a structure.

Can a cord be run through a doorway or a hole in the wall?

No. Cords may not be run through holes in walls, ceilings or floors, or through doorways, windows or similar openings, unless the subpart specifically permits it.

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Desplácese hacia arriba