1910.268(b): Telecommunications Centers: General Rules

By Black Belt Safety Editorial Team Official text as of October 15, 2026 Data updated November 17, 2026 6 min read

In plain words:

Employers must provide adequate lighting in telecommunications centers, with extra lighting for tasks like splicing that need it. The rule also covers guard rails on frame mezzanines, aisles that are not exit routes, special doors usable for emergency egress, marking near uncovered rotating machinery, and eye protection when measuring battery specific gravity.

Key takeaways

  • 1910.268(b) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart R).
  • OSHA cited it 22 times in the last 3 years, in 21 inspections, with $166,747 in current penalties.
  • 4 deaths are linked to inspections that cited this rule.
  • Most citations: OH (4), TX (4), KY (3).
  • Related part: 1910.268(b)(7) Approach distances to exposed energized overhead power lines and parts (18 citations).
  • Free 5-minute toolbox talk for your crew below.

Get the free 5-minute toolbox talk on 1910.268(b) ↓

22citations, 3 years
$166,747current penalties
21inspections
4linked deaths
In this article
  1. What this rule covers
  2. Official text
  3. Injuries linked to this rule
  4. Where and how often it was cited
  5. Free toolbox talk
  6. OSHA interpretation letters
  7. Related parts of this rule
  8. Get your crew competent
  9. Frequently asked questions
  10. About this page

What this rule covers

29 CFR 1910.268(b) ("General") is one requirement inside 1910.268 Telecommunications, an OSHA general industry standard (Part 1910, Subpart R). It includes 19 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(b) General — 22 citations

(1) Buildings containing telecommunications centers —

(i) Illumination. Lighting in telecommunication centers shall be provided in an adequate amount such that continuing work operations, routine observations, and the passage of employees can be carried out in a safe and healthful manner. Certain specific tasks in centers, such as splicing cable and the maintenance and repair of equipment frame lineups, may require a higher level of illumination. In such cases, the employer shall install permanent lighting or portable supplemental lighting to attain a higher level of illumination shall be provided as needed to permit safe performance of the required task.

(ii) Working surfaces. Guard rails and toe boards may be omitted on distribution frame mezzanine platforms to permit access to equipment. This exemption applies only on the side or sides of the platform facing the frames and only on those portions of the platform adjacent to equipped frames.

(iii) Working spaces. Maintenance aisles, or wiring aisles, between equipment frame lineups are working spaces and are not an exit route for purposes of 29 CFR 1910.34.

(iv) Special doors. When blastproof or power actuated doors are installed in specially designed hardsite security buildings and spaces, they shall be designed and installed so that they can be used as a means of egress in emergencies.

(v) Equipment, machinery and machine guarding. When power plant machinery in telecommunications centers is operated with commutators and couplings uncovered, the adjacent housing shall be clearly marked to alert personnel to the rotating machinery.

(2) Battery handling.

(i) Eye protection devices which provide side as well as frontal eye protection for employees shall be provided when measuring storage battery specific gravity or handling electrolyte, and the employer shall ensure that such devices are used by the employees. The employer shall also ensure that acid resistant gloves and aprons shall be worn for protection against spattering. Facilities for quick drenching or flushing of the eyes and body shall be provided unless the storage batteries are of the enclosed type and equipped with explosion proof vents, in which case sealed water rinse or neutralizing packs may be substituted for the quick drenching or flushing facilities. Employees assigned to work with storage batteries shall be instructed in emergency procedures such as dealing with accidental acid spills.

(ii) Electrolyte (acid or base, and distilled water) for battery cells shall be mixed in a well ventilated room. Acid or base shall be poured gradually, while stirring, into the water. Water shall never be poured into concentrated (greater than 75 percent) acid solutions. Electrolyte shall never be placed in metal containers nor stirred with metal objects.

(iii) When taking specific gravity readings, the open end of the hydrometer shall be covered with an acid resistant material while moving it from cell to cell to avoid splashing or throwing the electrolyte.

(3) Employers must provide employees with readily accessible, adequate, and appropriate first aid supplies. A non-mandatory example of appropriate supplies is listed in appendix A to 29 CFR 1910.151. 1 citations

(4) Hazardous materials. Highway mobile vehicles and trailers stored in garages in accordance with § 1910.110 may be equipped to carry more than one LP-gas container, but the total capacity of LP-gas containers per work vehicle stored in garages shall not exceed 100 pounds of LP-gas. All container valves shall be closed when not in use.

(5) Compressed gas. When using or transporting nitrogen cylinders in a horizontal position, special compartments, racks, or adequate blocking shall be provided to prevent cylinder movement. Regulators shall be removed or guarded before a cylinder is transported.

(6) Support structures. No employee, or any material or equipment, may be supported or permitted to be supported on any portion of a pole structure, platform, ladder, walkway or other elevated structure or aerial device unless the employer ensures that the support structure is first inspected by a competent person and it is determined to be adequately strong, in good working condition and properly secured in place. 3 citations

(7) Approach distances to exposed energized overhead power lines and parts. The employer shall ensure that no employee approaches or takes any conductive object closer to any electrically energized overhead power lines and parts than prescribed in Table R-2, unless: Open (b)(7) 18 citations

(i) The employee is insulated or guarded from the energized parts (insulating gloves rated for the voltage involved shall be considered adequate insulation), or

(ii) The energized parts are insulated or guarded from the employee and any other conductive object at a different potential, or

(iii) The power conductors and equipment are deenergized and grounded.

Table R-2—Approach Distances to Exposed Energized Overhead Power Lines and Parts

Voltage range (phase to phase, RMS) Approach distance (inches)
300 V and less (1)
Over 300V, not over 750V 12
Over 750V not over 2 kV 18
Over 2 kV, not over 15 kV 24
Over 15 kV, not over 37 kV 36
Over 37 kV, not over 87.5 kV 42
Over 87.5 kV, not over 121 kV 48
Over 121 kV, not over 140 kV 54
1 Avoid contact.

(8) Illumination of field work. Whenever natural light is insufficient to adequately illuminate the worksite, artificial illumination shall be provided to enable the employee to perform the work safely.

Source: eCFR, text current as of 2026-10-15. Read all of 1910.268.

See every company cited for this rule.

Export the list: 21 inspections cited 1910.268(b) in the last 3 years, with employer, location, penalty and date.

Purple Belt, $59/mo

Injuries linked to this rule

4 deaths are linked to inspections where OSHA cited 1910.268(b).

Employee dies from electrocution while installing fiber opti
2024-10-08 · Fatal · NAVARRE, OH

At approximately 3:30 p.m. on October 8, 2024, Employee #1, a 29-year-old male technician, was installing fiber optic cable at a residential location. Employee#1 was working from an aerial bucket truck when he unexpectedly made contact with an energized 7,200-volt overhead power line. The employee…

See all 4 cases

Full case list with employer, penalty, filters and download is part of OSHA Data (Purple Belt).

Unlock with Purple Belt

Where and how often it was cited

YearCitations
20232
20247
20255
20268

Top states: OH (4), TX (4), KY (3), PR (2), MI (2)

Largest penalties

EmployerLocationPenalty for this rule
J B NASSER INCFRONT ROYAL, VA$16,285
CHARTER COMMUNICATIONS INC.EAST BERNE, NY$16,131
MASSILLON CABLE TV, INC.NAVARRE, OH$16,131
MOLDCABLE, INC.LIBERTY HILL, TX$14,895
IMON COMMUNICATIONSIOWA CITY, IA$12,500

Free toolbox talk

A 5-minute crew talk on 1910.268(b), plus alerts when this rule changes. Free.




OSHA interpretation letters

None exist. OSHA has not published a letter of interpretation for 1910.268(b).

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

What lighting is required in telecommunications centers?

Enough to let work, routine observations and passage of employees be done safely, with permanent or portable extra lighting for tasks that need more.

Are maintenance aisles exit routes?

No. Maintenance or wiring aisles between equipment frame lineups are working spaces, not exit routes under 1910.34.

What eye protection is needed for battery work?

Eye protection with side and frontal protection when measuring storage battery specific gravity.

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Scroll to top