What this rule covers
29 CFR 1910.269(l)(8)(v) is one requirement inside 1910.269 Electric power generation, transmission, and distribution, an OSHA general industry standard (Part 1910, Subpart R). It includes 5 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.
Official text
(v) The employer shall ensure that each employee exposed to hazards from electric arcs wears protective clothing and other protective equipment with an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeds 2.0 cal/cm2. This protective equipment shall cover the employee's entire body, except as follows: 9 citations
(A) Arc-rated protection is not necessary for the employee's hands when the employee is wearing rubber insulating gloves with protectors or, if the estimated incident energy is no more than 14 cal/cm2, heavy-duty leather work gloves with a weight of at least 407 gm/m2 (12 oz/yd2),
(B) Arc-rated protection is not necessary for the employee's feet when the employee is wearing heavy-duty work shoes or boots,
(C) Arc-rated protection is not necessary for the employee's head when the employee is wearing head protection meeting § 1910.135 if the estimated incident energy is less than 9 cal/cm2 for exposures involving single-phase arcs in open air or 5 cal/cm2 for other exposures,
(D) The protection for the employee's head may consist of head protection meeting § 1910.135 and a faceshield with a minimum arc rating of 8 cal/cm2 if the estimated incident-energy exposure is less than 13 cal/cm2 for exposures involving single-phase arcs in open air or 9 cal/cm2 for other exposures, and 1 citations
(E) For exposures involving single-phase arcs in open air, the arc rating for the employee's head and face protection may be 4 cal/cm2 less than the estimated incident energy.
See appendix E to this section for further information on the selection of appropriate protection.
Source: eCFR, text current as of 2026-10-15. Read all of 1910.269.
Where and how often it was cited
Free toolbox talk
A 5-minute crew talk on 1910.269(l)(8)(v), plus alerts when this rule changes. Free.
OSHA interpretation letters
- Selecting protective clothing based on the IEEE National Electrical Safety Code, C-2, 2012, Table 410-1 (2015-07-13)
Related parts of this rule
- 1910.269(l) Working on or near exposed energized parts 75 citations
- 1910.269(l)(3) Minimum approach distances 28 citations
- 1910.269(l)(3)(iii) 26 citations
- 1910.269(l)(8) Protection from flames and electric arcs 18 citations
- 1910.269(l)(1) General 13 citations
- 1910.269(l)(1)(ii) 6 citations
- 1910.269(l)(5) Working position 6 citations
- 1910.269(l)(1)(iii) 5 citations
- 1910.269(l)(3)(iii)(A) 5 citations
- 1910.269(l)(5)(ii) 5 citations
- 1910.269(l)(2) At least two employees 4 citations
- 1910.269(l)(2)(i) 4 citations
Get your crew competent
Trainers on Black Belt Safety: Marc Harvey, Dana Reyes
Trainers and suppliers: feature your business on this rule for $25/month.
About this page
Sources
- 29 CFR 1910.269 (eCFR), text current as of 2026-10-15
- U.S. Department of Labor enforcement data: OSHA inspections, citations and accident records, copied nightly; data as of 2026-10-24
3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.