29 CFR 1910 · General Industry · Subpart R

1910.269(l): Working On or Near Exposed Energized Parts

By Black Belt Safety Editorial Team Official text as of October 15, 2026 Data updated October 24, 2026 12 min read

In plain words:

Only qualified employees may work on exposed energized lines or parts, or in areas with unguarded, uninsulated energized parts at 50 volts or more, and lines must be treated as energized unless deenergized per the rule. At least two employees must be present for listed work involving parts energized at more than 600 volts, with limited exceptions such as routine switching.

Key takeaways

  • 1910.269(l) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart R).
  • OSHA cited it 75 times in the last 3 years, in 49 inspections, with $487,447 in current penalties.
  • 8 deaths are linked to inspections that cited this rule.
  • Most citations: NY (8), MO (7), NC (5).
  • Related part: 1910.269(l)(3) Minimum approach distances (28 citations).
  • Free 5-minute toolbox talk for your crew below.
75citations, 3 years
$487,447current penalties
49inspections
8linked deaths
In this article
  1. What this rule covers
  2. Official text
  3. Injuries linked to this rule
  4. Where and how often it was cited
  5. Free toolbox talk
  6. OSHA interpretation letters
  7. Related parts of this rule
  8. Get your crew competent
  9. Frequently asked questions
  10. About this page

What this rule covers

29 CFR 1910.269(l) ("Working on or near exposed energized parts") is one requirement inside 1910.269 Electric power generation, transmission, and distribution, an OSHA general industry standard (Part 1910, Subpart R). It includes 62 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(l) Working on or near exposed energized parts. This paragraph applies to work on exposed live parts, or near enough to them to expose the employee to any hazard they present. 75 citations

(1) General. Open (l)(1) 13 citations

(i) Only qualified employees may work on or with exposed energized lines or parts of equipment. Open (l)(1)(i) 1 citations

(ii) Only qualified employees may work in areas containing unguarded, uninsulated energized lines or parts of equipment operating at 50 volts or more. Open (l)(1)(ii) 6 citations

(iii) Electric lines and equipment shall be considered and treated as energized unless they have been deenergized in accordance with paragraph (d) or (m) of this section. Open (l)(1)(iii) 5 citations

(2) At least two employees. Open (l)(2) 4 citations

(i) Except as provided in paragraph (l)(2)(ii) of this section, at least two employees shall be present while any employees perform the following types of work: Open (l)(2)(i) 4 citations

(A) Installation, removal, or repair of lines energized at more than 600 volts,

(B) Installation, removal, or repair of deenergized lines if an employee is exposed to contact with other parts energized at more than 600 volts, 1 citations

(C) Installation, removal, or repair of equipment, such as transformers, capacitors, and regulators, if an employee is exposed to contact with parts energized at more than 600 volts, 1 citations

(D) Work involving the use of mechanical equipment, other than insulated aerial lifts, near parts energized at more than 600 volts, and

(E) Other work that exposes an employee to electrical hazards greater than, or equal to, the electrical hazards posed by operations listed specifically in paragraphs (l)(2)(i)(A) through (l)(2)(i)(D) of this section. Open (l)(2)(i)(e) 1 citations

(ii) Paragraph (l)(2)(i) of this section does not apply to the following operations:

(A) Routine circuit switching, when the employer can demonstrate that conditions at the site allow safe performance of this work,

(B) Work performed with live-line tools when the position of the employee is such that he or she is neither within reach of, nor otherwise exposed to contact with, energized parts, and

(C) Emergency repairs to the extent necessary to safeguard the general public.

(3) Minimum approach distances. Open (l)(3) 28 citations

(i) The employer shall establish minimum approach distances no less than the distances computed by Table R-3 for ac systems or Table R-8 for dc systems. Open (l)(3)(i) 2 citations

(ii) No later than April 1, 2015, for voltages over 72.5 kilovolts, the employer shall determine the maximum anticipated per-unit transient overvoltage, phase-to-ground, through an engineering analysis or assume a maximum anticipated per-unit transient overvoltage, phase-to-ground, in accordance with Table R-9. When the employer uses portable protective gaps to control the maximum transient overvoltage, the value of the maximum anticipated per-unit transient overvoltage, phase-to-ground, must provide for five standard deviations between the statistical sparkover voltage of the gap and the statistical withstand voltage corresponding to the electrical component of the minimum approach distance. The employer shall make any engineering analysis conducted to determine maximum anticipated per-unit transient overvoltage available upon request to employees and to the Assistant Secretary or designee for examination and copying. Open (l)(3)(ii)

See appendix B to this section for information on how to calculate the maximum anticipated per-unit transient overvoltage, phase-to-ground, when the employer uses portable protective gaps to reduce maximum transient overvoltages.

(iii) The employer shall ensure that no employee approaches or takes any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless: Open (l)(3)(iii) 26 citations

(A) The employee is insulated from the energized part (rubber insulating gloves or rubber insulating gloves and sleeves worn in accordance with paragraph (l)(4) of this section constitutes insulation of the employee from the energized part upon which the employee is working provided that the employee has control of the part in a manner sufficient to prevent exposure to uninsulated portions of the employee's body), or Open (l)(3)(iii)(a) 5 citations

(B) The energized part is insulated from the employee and from any other conductive object at a different potential, or Open (l)(3)(iii)(b) 3 citations

(C) The employee is insulated from any other exposed conductive object in accordance with the requirements for live-line barehand work in paragraph (q)(3) of this section. Open (l)(3)(iii)(c) 2 citations

(4) Type of insulation. Open (l)(4) 4 citations

(i) When an employee uses rubber insulating gloves as insulation from energized parts (under paragraph (l)(3)(iii)(A) of this section), the employer shall ensure that the employee also uses rubber insulating sleeves. However, an employee need not use rubber insulating sleeves if: 2 citations

(A) Exposed energized parts on which the employee is not working are insulated from the employee; and

(B) When installing insulation for purposes of paragraph (l)(4)(i)(A) of this section, the employee installs the insulation from a position that does not expose his or her upper arm to contact with other energized parts.

(ii) When an employee uses rubber insulating gloves or rubber insulating gloves and sleeves as insulation from energized parts (under paragraph (l)(3)(iii)(A) of this section), the employer shall ensure that the employee: Open (l)(4)(ii) 2 citations

(A) Puts on the rubber insulating gloves and sleeves in a position where he or she cannot reach into the minimum approach distance, established by the employer under paragraph (l)(3)(i) of this section; and

(B) Does not remove the rubber insulating gloves and sleeves until he or she is in a position where he or she cannot reach into the minimum approach distance, established by the employer under paragraph (l)(3)(i) of this section. Open (l)(4)(ii)(b) 2 citations

(5) Working position. Open (l)(5) 6 citations

(i) The employer shall ensure that each employee, to the extent that other safety-related conditions at the worksite permit, works in a position from which a slip or shock will not bring the employee's body into contact with exposed, uninsulated parts energized at a potential different from the employee's. 1 citations

(ii) When an employee performs work near exposed parts energized at more than 600 volts, but not more than 72.5 kilovolts, and is not wearing rubber insulating gloves, being protected by insulating equipment covering the energized parts, performing work using live-line tools, or performing live-line barehand work under paragraph (q)(3) of this section, the employee shall work from a position where he or she cannot reach into the minimum approach distance, established by the employer under paragraph (l)(3)(i) of this section. Open (l)(5)(ii) 5 citations

(6) Making connections. The employer shall ensure that employees make connections as follows: Open (l)(6) 2 citations

(i) In connecting deenergized equipment or lines to an energized circuit by means of a conducting wire or device, an employee shall first attach the wire to the deenergized part;

(ii) When disconnecting equipment or lines from an energized circuit by means of a conducting wire or device, an employee shall remove the source end first; and 1 citations

(iii) When lines or equipment are connected to or disconnected from energized circuits, an employee shall keep loose conductors away from exposed energized parts. Open (l)(6)(iii) 1 citations

(7) Conductive articles. When an employee performs work within reaching distance of exposed energized parts of equipment, the employer shall ensure that the employee removes or renders nonconductive all exposed conductive articles, such as keychains or watch chains, rings, or wrist watches or bands, unless such articles do not increase the hazards associated with contact with the energized parts.

(8) Protection from flames and electric arcs. Open (l)(8) 18 citations

(i) The employer shall assess the workplace to identify employees exposed to hazards from flames or from electric arcs. 3 citations

(ii) For each employee exposed to hazards from electric arcs, the employer shall make a reasonable estimate of the incident heat energy to which the employee would be exposed. Open (l)(8)(ii) 3 citations

Appendix E to this section provides guidance on estimating available heat energy. The Occupational Safety and Health Administration will deem employers following the guidance in appendix E to this section to be in compliance with paragraph (l)(8)(ii) of this section. An employer may choose a method of calculating incident heat energy not included in appendix E to this section if the chosen method reasonably predicts the incident energy to which the employee would be exposed.

This paragraph does not require the employer to estimate the incident heat energy exposure for every job task performed by each employee. The employer may make broad estimates that cover multiple system areas provided the employer uses reasonable assumptions about the energy-exposure distribution throughout the system and provided the estimates represent the maximum employee exposure for those areas. For example, the employer could estimate the heat energy just outside a substation feeding a radial distribution system and use that estimate for all jobs performed on that radial system.

(iii) The employer shall ensure that each employee who is exposed to hazards from flames or electric arcs does not wear clothing that could melt onto his or her skin or that could ignite and continue to burn when exposed to flames or the heat energy estimated under paragraph (l)(8)(ii) of this section. 3 citations

This paragraph prohibits clothing made from acetate, nylon, polyester, rayon and polypropylene, either alone or in blends, unless the employer demonstrates that the fabric has been treated to withstand the conditions that may be encountered by the employee or that the employee wears the clothing in such a manner as to eliminate the hazard involved.

(iv) The employer shall ensure that the outer layer of clothing worn by an employee, except for clothing not required to be arc rated under paragraphs (l)(8)(v)(A) through (l)(8)(v)(E) of this section, is flame resistant under any of the following conditions:

(A) The employee is exposed to contact with energized circuit parts operating at more than 600 volts,

(B) An electric arc could ignite flammable material in the work area that, in turn, could ignite the employee's clothing,

(C) Molten metal or electric arcs from faulted conductors in the work area could ignite the employee's clothing, or

This paragraph does not apply to conductors that are capable of carrying, without failure, the maximum available fault current for the time the circuit protective devices take to interrupt the fault.

(D) The incident heat energy estimated under paragraph (l)(8)(ii) of this section exceeds 2.0 cal/cm2.

(v) The employer shall ensure that each employee exposed to hazards from electric arcs wears protective clothing and other protective equipment with an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeds 2.0 cal/cm2. This protective equipment shall cover the employee's entire body, except as follows: Open (l)(8)(v) 9 citations

(A) Arc-rated protection is not necessary for the employee's hands when the employee is wearing rubber insulating gloves with protectors or, if the estimated incident energy is no more than 14 cal/cm2, heavy-duty leather work gloves with a weight of at least 407 gm/m2 (12 oz/yd2),

(B) Arc-rated protection is not necessary for the employee's feet when the employee is wearing heavy-duty work shoes or boots,

(C) Arc-rated protection is not necessary for the employee's head when the employee is wearing head protection meeting § 1910.135 if the estimated incident energy is less than 9 cal/cm2 for exposures involving single-phase arcs in open air or 5 cal/cm2 for other exposures,

(D) The protection for the employee's head may consist of head protection meeting § 1910.135 and a faceshield with a minimum arc rating of 8 cal/cm2 if the estimated incident-energy exposure is less than 13 cal/cm2 for exposures involving single-phase arcs in open air or 9 cal/cm2 for other exposures, and 1 citations

(E) For exposures involving single-phase arcs in open air, the arc rating for the employee's head and face protection may be 4 cal/cm2 less than the estimated incident energy.

See appendix E to this section for further information on the selection of appropriate protection.

(vi) Dates.

(A) The obligation in paragraph (l)(8)(ii) of this section for the employer to make reasonable estimates of incident energy commences January 1, 2015.

(B) The obligation in paragraph (l)(8)(iv)(D) of this section for the employer to ensure that the outer layer of clothing worn by an employee is flame-resistant when the estimated incident heat energy exceeds 2.0 cal/cm2 commences April 1, 2015.

(C) The obligation in paragraph (l)(8)(v) of this section for the employer to ensure that each employee exposed to hazards from electric arcs wears the required arc-rated protective equipment commences April 1, 2015.

(9) Fuse handling. When an employee must install or remove fuses with one or both terminals energized at more than 300 volts, or with exposed parts energized at more than 50 volts, the employer shall ensure that the employee uses tools or gloves rated for the voltage. When an employee installs or removes expulsion-type fuses with one or both terminals energized at more than 300 volts, the employer shall ensure that the employee wears eye protection meeting the requirements of subpart I of this part, uses a tool rated for the voltage, and is clear of the exhaust path of the fuse barrel.

(10) Covered (noninsulated) conductors. The requirements of this section that pertain to the hazards of exposed live parts also apply when an employee performs work in proximity to covered (noninsulated) wires.

(11) Non-current-carrying metal parts. Non-current-carrying metal parts of equipment or devices, such as transformer cases and circuit-breaker housings, shall be treated as energized at the highest voltage to which these parts are exposed, unless the employer inspects the installation and determines that these parts are grounded before employees begin performing the work.

(12) Opening and closing circuits under load.

(i) The employer shall ensure that devices used by employees to open circuits under load conditions are designed to interrupt the current involved.

(ii) The employer shall ensure that devices used by employees to close circuits under load conditions are designed to safely carry the current involved.

Table R-3—AC Live-Line Work Minimum Approach Distance

[The minimum approach distance (MAD; in meters) shall conform to the following equations.]

For phase-to-phase system voltages of 50 V to 300 V: 1
MAD = avoid contact
For phase-to-phase system voltages of 301 V to 5 kV: 1
MAD = M + D, where
D = 0.02 m the electrical component of the minimum approach distance.
M = 0.31 m for voltages up to 750 V and 0.61 m otherwise the inadvertent movement factor.
For phase-to-phase system voltages of 5.1 kV to 72.5 kV: 1 4
MAD = M + AD, where
M = 0.61 m the inadvertent movement factor.
A = the applicable value from Table R-5 the altitude correction factor.
D = the value from Table R-4 corresponding to the voltage and exposure or the value of the electrical component of the minimum approach distance calculated using the method provided in appendix B to this section the electrical component of the minimum approach distance.
For phase-to-phase system voltages of more than 72.5 kV, nominal: 2 4
MAD = 0.3048(C + a)V L-G TA + M
C = 0.01 for phase-to-ground exposures that the employer can demonstrate consist only of air across the approach distance (gap),
0.01 for phase-to-phase exposures if the employer can demonstrate that no insulated tool spans the gap and that no large conductive object is in the gap, or
0.011 otherwise
VL-G = phase-to-ground rms voltage, in kV
T = maximum anticipated per-unit transient overvoltage; for phase-to-ground exposures, T equals TL-G, the maximum per-unit transient overvoltage, phase-to-ground, determined by the employer under paragraph (l)(3)(ii) of this section; for phase-to-phase exposures, T equals 1.35TL-G + 0.45
A = altitude correction factor from Table R-5
M = 0.31 m, the inadvertent movement factor
a = saturation factor, as follows:
Phase-to-Ground Exposures
V Peak = T L-G V L-G√2 635 kV or less 635.1 to 915 kV 915.1 to 1,050 kV More than 1,050 kV
a 0 (V Peak-635)/140,000 (V Peak-645)/135,000 (V Peak-675)/125,000
Phase-to-Phase Exposures 3
V Peak = (1.35T L-G + 0.45)V L-G√2 630 kV or less 630.1 to 848 kV 848.1 to 1,131 kV 1,131.1 to 1,485 kV More than 1,485 kV
a 0 (V Peak-630)/155,000 (V Peak-633.6)/152,207 (V Peak-628)/153,846 (V Peak-350.5)/203,666
1 Employers may use the minimum approach distances in Table R-6. If the worksite is at an elevation of more than 900 meters (3,000 feet), see footnote 1 to Table R-6.
2 Employers may use the minimum approach distances in Table R-7, except that the employer may not use the minimum approach distances in Table R-7 for phase-to-phase exposures if an insulated tool spans the gap or if any large conductive object is in the gap. If the worksite is at an elevation of more than 900 meters (3,000 feet), see footnote 1 to Table R-7. Employers may use the minimum approach distances in Table 14 through Table 21 in appendix B to this section, which calculated MAD for various values of T, provided the employer follows the notes to those tables.
3 Use the equations for phase-to-ground exposures (with V Peak for phase-to-phase exposures) unless the employer can demonstrate that no insulated tool spans the gap and that no large conductive object is in the gap.
4 Until March 31, 2015, employers may use the minimum approach distances in Table 6 through Table 13 in Appendix B to this section.

Table R-4—Electrical Component of the Minimum Approach Distance at 5.1 to 72.5 kV

[D; In meters]

Nominal voltage (kV)
phase-to-phase
Phase-to-ground exposure Phase-to-phase exposure
D (m) D (m)
5.1 to 15.0 0.04 0.07
15.1 to 36.0 0.16 0.28
36.1 to 46.0 0.23 0.37
46.1 to 72.5 0.39 0.59

Table R-5—Altitude Correction Factor

Altitude above sea level
(m)
A
0 to 900 1.00
901 to 1,200 1.02
1,201 to 1,500 1.05
1,501 to 1,800 1.08
1,801 to 2,100 1.11
2,101 to 2,400 1.14
2,401 to 2,700 1.17
2,701 to 3,000 1.20
3,001 to 3,600 1.25
3,601 to 4,200 1.30
4,201 to 4,800 1.35
4,801 to 5,400 1.39
5,401 to 6,000 1.44

Table R-6—Alternative Minimum Approach Distances for Voltages of 72.5 kV and Less 1

Nominal voltage (kV)
phase-to-phase
Distance
Phase-to-ground exposure Phase-to-phase exposure
m ft m ft
0.050 to 0.300 2 Avoid Contact Avoid Contact
0.301 to 0.750 2 0.33 1.09 0.33 1.09
0.751 to 5.0 0.63 2.07 0.63 2.07
5.1 to 15.0 0.65 2.14 0.68 2.24
15.1 to 36.0 0.77 2.53 0.89 2.92
36.1 to 46.0 0.84 2.76 0.98 3.22
46.1 to 72.5 1.00 3.29 1.20 3.94
1 Employers may use the minimum approach distances in this table provided the worksite is at an elevation of 900 meters (3,000 feet) or less. If employees will be working at elevations greater than 900 meters (3,000 feet) above mean sea level, the employer shall determine minimum approach distances by multiplying the distances in this table by the correction factor in Table R-5 corresponding to the altitude of the work.
2 For single-phase systems, use voltage-to-ground.

Table R-7—Alternative Minimum Approach Distances for Voltages of More Than 72.5 kV1 2 3

Voltage range phase to phase (kV) Phase-to-ground exposure Phase-to-phase exposure
m ft m ft
72.6 to 121.0 1.13 3.71 1.42 4.66
121.1 to 145.0 1.30 4.27 1.64 5.38
145.1 to 169.0 1.46 4.79 1.94 6.36
169.1 to 242.0 2.01 6.59 3.08 10.10
242.1 to 362.0 3.41 11.19 5.52 18.11
362.1 to 420.0 4.25 13.94 6.81 22.34
420.1 to 550.0 5.07 16.63 8.24 27.03
550.1 to 800.0 6.88 22.57 11.38 37.34
1 Employers may use the minimum approach distances in this table provided the worksite is at an elevation of 900 meters (3,000 feet) or less. If employees will be working at elevations greater than 900 meters (3,000 feet) above mean sea level, the employer shall determine minimum approach distances by multiplying the distances in this table by the correction factor in Table R-5 corresponding to the altitude of the work.
2 Employers may use the phase-to-phase minimum approach distances in this table provided that no insulated tool spans the gap and no large conductive object is in the gap.
3 The clear live-line tool distance shall equal or exceed the values for the indicated voltage ranges.

Table R-8—DC Live-Line Minimum Approach Distance with Overvoltage Factor 1

[In meters]

Maximum anticipated per-unit
transient overvoltage
Distance (m)
maximum line-to-ground voltage (kV)
250 400 500 600 750
1.5 or less 1.12 1.60 2.06 2.62 3.61
1.6 1.17 1.69 2.24 2.86 3.98
1.7 1.23 1.82 2.42 3.12 4.37
1.8 1.28 1.95 2.62 3.39 4.79
1 The distances specified in this table are for air, bare-hand, and live-line tool conditions. If employees will be working at elevations greater than 900 meters (3,000 feet) above mean sea level, the employer shall determine minimum approach distances by multiplying the distances in this table by the correction factor in Table R-5 corresponding to the altitude of the work.

Table R-9—Assumed Maximum Per-Unit Transient Overvoltage

Voltage range
(kV)
Type of current
(ac or dc)
Assumed
maximum per-unit transient
overvoltage
72.6 to 420.0 ac 3.5
420.1 to 550.0 ac 3.0
550.1 to 800.0 ac 2.5
250 to 750 dc 1.8

Source: eCFR, text current as of 2026-10-15. Read all of 1910.269.

Injuries linked to this rule

8 deaths are linked to inspections where OSHA cited 1910.269(l).

Employee dies from electrocution and arc flash injuries whil
2025-01-07 · Fatal · TAMPA, FL

At 2:45 p.m. on January 7, 2025, an employee was locating underground power lines when he reached inside a transformer to retrieve a wire connected to the transformer. The employee sustained an arc flash and electrocution injury after contacting a live 7,200 volt gang switch.…

See all 8 cases

Full case list with employer, penalty, filters and download is part of OSHA Data (Purple Belt).

Unlock with Purple Belt

Where and how often it was cited

YearCitations
202311
202431
202517
202616

Top states: NY (8), MO (7), NC (5), VA (5), KY (5)

Largest penalties

EmployerLocationPenalty for this rule
AMPERSAND NEW YORK OPERATIONS CO, LLCTROY, NY$45,166
TAMPA ELECTRIC COMPANYTAMPA, FL$33,100
NAESPLEASANT HILL, MO$33,100
AMEREN MISSOURIJEFFERSON CITY, MO$33,100
157859 - DUKE ENERGY PROGRESS, LLCSANFORD, NC$32,262

Free toolbox talk

A 5-minute crew talk on 1910.269(l), plus alerts when this rule changes. Free.




OSHA interpretation letters

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey, Dana Reyes

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

Who may work on exposed energized lines?

Only qualified employees.

When are lines considered energized?

Electric lines and equipment must be treated as energized unless deenergized in accordance with paragraph (d) or (m).

When are at least two employees required?

For listed work such as installation, removal or repair of lines energized at more than 600 volts, unless an exception applies.

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Scroll to top