29 CFR 1910 · General Industry · Subpart S

1910.303(h): Electrical Installations Over 600 Volts

By Black Belt Safety Editorial Team Official text as of October 15, 2026 Data updated November 6, 2026 9 min read

In plain words:

Employers must make sure conductors and equipment on circuits over 600 volts meet the general electrical rules and these added rules. Installations in locked vaults, rooms or fenced areas are treated as accessible to qualified persons only, outdoor installations must be enclosed by a wall, screen or fence of the stated height, and indoor installations open to others must be metal-enclosed or locked and marked with caution signs.

Key takeaways

  • 1910.303(h) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
  • OSHA cited it 27 times in the last 3 years, in 25 inspections, with $69,972 in current penalties.
  • Most citations: NJ (5), NY (4), TX (3).
  • Related part: 1910.303(h)(5) Working space and guarding (16 citations).
  • Free 5-minute toolbox talk for your crew below.

Get the free 5-minute toolbox talk on 1910.303(h) ↓

27citations, 3 years
$69,972current penalties
25inspections
0linked injury cases
In this article
  1. What this rule covers
  2. Official text
  3. Where and how often it was cited
  4. Free toolbox talk
  5. OSHA interpretation letters
  6. Related parts of this rule
  7. Get your crew competent
  8. Frequently asked questions
  9. About this page

What this rule covers

29 CFR 1910.303(h) ("Over 600 volts, nominal") is one requirement inside 1910.303 General, an OSHA general industry standard (Part 1910, Subpart S). It includes 33 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(h) Over 600 volts, nominal — 27 citations

(1) General. Conductors and equipment used on circuits exceeding 600 volts, nominal, shall comply with all applicable provisions of the paragraphs (a) through (g) of this section and with the following provisions, which supplement or modify the preceding requirements. However, paragraphs (h)(2), (h)(3), and (h)(4) of this section do not apply to the equipment on the supply side of the service point.

(2) Enclosure for electrical installations. Open (h)(2) 6 citations

(i) Electrical installations in a vault, room, or closet or in an area surrounded by a wall, screen, or fence, access to which is controlled by lock and key or other approved means, are considered to be accessible to qualified persons only. The type of enclosure used in a given case shall be designed and constructed according to the hazards associated with the installation.

(ii) For installations other than equipment described in paragraph (h)(2)(v) of this section, a wall, screen, or fence shall be used to enclose an outdoor electrical installation to deter access by persons who are not qualified. A fence may not be less than 2.13 m (7.0 ft) in height or a combination of 1.80 m (6.0 ft) or more of fence fabric and a 305-mm (1-ft) or more extension utilizing three or more strands of barbed wire or equivalent. Open (h)(2)(ii)

(iii) The following requirements apply to indoor installations that are accessible to other than qualified persons: 1 citations

(A) The installations shall be made with metal-enclosed equipment or shall be enclosed in a vault or in an area to which access is controlled by a lock;

(B) Metal-enclosed switchgear, unit substations, transformers, pull boxes, connection boxes, and other similar associated equipment shall be marked with appropriate caution signs; and 1 citations

(C) Openings in ventilated dry-type transformers and similar openings in other equipment shall be designed so that foreign objects inserted through these openings will be deflected from energized parts.

(iv) Outdoor electrical installations having exposed live parts shall be accessible to qualified persons only.

(v) The following requirements apply to outdoor enclosed equipment accessible to unqualified employees: 5 citations

(A) Ventilating or similar openings in equipment shall be so designed that foreign objects inserted through these openings will be deflected from energized parts;

(B) Where exposed to physical damage from vehicular traffic, suitable guards shall be provided; 1 citations

(C) Nonmetallic or metal-enclosed equipment located outdoors and accessible to the general public shall be designed so that exposed nuts or bolts cannot be readily removed, permitting access to live parts;

(D) Where nonmetallic or metal-enclosed equipment is accessible to the general public and the bottom of the enclosure is less than 2.44 m (8.0 ft) above the floor or grade level, the enclosure door or hinged cover shall be kept locked; and 1 citations

(E) Except for underground box covers that weigh over 45.4 kg (100 lb), doors and covers of enclosures used solely as pull boxes, splice boxes, or junction boxes shall be locked, bolted, or screwed on. 2 citations

(3) Work space about equipment. Sufficient space shall be provided and maintained about electric equipment to permit ready and safe operation and maintenance of such equipment. Where energized parts are exposed, the minimum clear work space may not be less than 1.98 m (6.5 ft) high (measured vertically from the floor or platform) or less than 914 mm (3.0 ft) wide (measured parallel to the equipment). The depth shall be as required in paragraph (h)(5)(i) of this section. In all cases, the work space shall be adequate to permit at least a 90-degree opening of doors or hinged panels. 5 citations

(4) Entrance and access to work space.

(i) At least one entrance not less than 610 mm (24 in.) wide and 1.98 m (6.5 ft) high shall be provided to give access to the working space about electric equipment.

(A) On switchboard and control panels exceeding 1.83 m (6.0 ft) in width, there shall be one entrance at each end of such boards unless the location of the switchboards and control panels permits a continuous and unobstructed way of exit travel, or unless the work space required in paragraph (h)(5)(i) of this section is doubled.

(B) Where one entrance to the working space is permitted under the conditions described in paragraph (h)(4)(i)(A) of this section, the entrance shall be located so that the edge of the entrance nearest the switchboards and control panels is at least the minimum clear distance given in Table S-2 away from such equipment.

(C) Where bare energized parts at any voltage or insulated energized parts above 600 volts, nominal, to ground are located adjacent to such entrance, they shall be suitably guarded.

(ii) Permanent ladders or stairways shall be provided to give safe access to the working space around electric equipment installed on platforms, balconies, mezzanine floors, or in attic or roof rooms or spaces.

(5) Working space and guarding. Open (h)(5) 16 citations

(i) Except as elsewhere required or permitted in this subpart, the minimum clear working space in the direction of access to live parts of electric equipment may not be less than specified in Table S-2. Distances shall be measured from the live parts, if they are exposed, or from the enclosure front or opening, if they are enclosed. 5 citations

(ii) If switches, cutouts, or other equipment operating at 600 volts, nominal, or less, are installed in a room or enclosure where there are exposed live parts or exposed wiring operating at over 600 volts, nominal, the high-voltage equipment shall be effectively separated from the space occupied by the low-voltage equipment by a suitable partition, fence, or screen. However, switches or other equipment operating at 600 volts, nominal, or less, and serving only equipment within the high-voltage vault, room, or enclosure may be installed in the high-voltage enclosure, room, or vault if accessible to qualified persons only. 1 citations

(iii) The following requirements apply to the entrances to all buildings, rooms, or enclosures containing exposed live parts or exposed conductors operating at over 600 volts, nominal: 9 citations

(A) The entrances shall be kept locked unless they are under the observation of a qualified person at all times; and 1 citations

(B) Permanent and conspicuous warning signs shall be provided, reading substantially as follows: 8 citations

“DANGER—HIGH VOLTAGE—KEEP OUT.”

(iv) Illumination shall be provided for all working spaces about electric equipment. 1 citations

(A) The lighting outlets shall be arranged so that persons changing lamps or making repairs on the lighting system will not be endangered by live parts or other equipment.

(B) The points of control shall be located so that persons are prevented from contacting any live part or moving part of the equipment while turning on the lights.

(v) Unguarded live parts above working space shall be maintained at elevations not less than specified in Table S-3.

(vi) Pipes or ducts that are foreign to the electrical installation and that require periodic maintenance or whose malfunction would endanger the operation of the electrical system may not be located in the vicinity of service equipment, metal-enclosed power switchgear, or industrial control assemblies. Protection shall be provided where necessary to avoid damage from condensation leaks and breaks in such foreign systems.

Piping and other facilities are not considered foreign if provided for fire protection of the electrical installation.

Table S-2—Minimum Depth of Clear Working Space at Electric Equipment, Over 600 V

Nominal voltage to ground Minimum clear distance for condition 2 3
Condition A Condition B Condition C
m ft m ft m ft
601-2500 V 0.9 3.0 1.2 4.0 1.5 5.0
2501-9000 V 1.2 4.0 1.5 5.0 1.8 6.0
9001 V-25 kV 1.5 5.0 1.8 6.0 2.8 9.0
Over 25-75 kV 1 1.8 6.0 2.5 8.0 3.0 10.0
Above 75 kV 1 2.5 8.0 3.0 10.0 3.7 12.0
Notes to Table S-2:
1 Minimum depth of clear working space in front of electric equipment with a nominal voltage to ground above 25,000 volts may be the same as that for 25,000 volts under Conditions A, B, and C for installations built before April 16, 1981.
2 Conditions A, B, and C are as follows:
Condition A—Exposed live parts on one side and no live or grounded parts on the other side of the working space, or exposed live parts on both sides effectively guarded by suitable wood or other insulating material. Insulated wire or insulated busbars operating at not over 300 volts are not considered live parts.
Condition B—Exposed live parts on one side and grounded parts on the other side. Concrete, brick, and tile walls are considered as grounded surfaces.
Condition C—Exposed live parts on both sides of the work space (not guarded as provided in Condition A) with the operator between.
3 Working space is not required in back of equipment such as dead-front switchboards or control assemblies that has no renewable or adjustable parts (such as fuses or switches) on the back and where all connections are accessible from locations other than the back. Where rear access is required to work on the deenergized parts on the back of enclosed equipment, a minimum working space 762 mm (30 in.) horizontally shall be provided.

Table S-3—Elevation of Unguarded Live Parts Above Working Space

Nominal voltage between phases Elevation
m ft
601-7500 V 1 2.8 1 9.0.
7501 V-35 kV 2.8 9.0.
Over 35 kV 2.8 + 9.5 mm/kV over 35 kV 9.0 + 0.37 in./kV over 35 kV.
1 The minimum elevation may be 2.6 m (8.5 ft) for installations built before August 13, 2007. The minimum elevation may be 2.4 m (8.0 ft) for installations built before April 16, 1981, if the nominal voltage between phases is in the range of 601-6600 volts.

[46 FR 4056, Jan. 16, 1981, as amended at 73 FR 64205, Oct. 29, 2008]

Source: eCFR, text current as of 2026-10-15. Read all of 1910.303.

See every company cited for this rule.

Export the list: 25 inspections cited 1910.303(h) in the last 3 years, with employer, location, penalty and date.

Purple Belt, $59/mo

Where and how often it was cited

YearCitations
20231
20247
202514
20265

Top states: NJ (5), NY (4), TX (3), IL (3), PR (3)

Largest penalties

EmployerLocationPenalty for this rule
TRDI MAINTENANCE, INC.CORPUS CHRISTI, TX$16,131
FLEET FARMMASON CITY, IA$7,448
MODERN MACHINE SHOP, INC.LAREDO, TX$7,035
DCRBAYAMON, PR$7,000
PRINT 1 LLCLAS PIEDRAS, PR$5,600

Free toolbox talk

A 5-minute crew talk on 1910.303(h), plus alerts when this rule changes. Free.




OSHA interpretation letters

None exist. OSHA has not published a letter of interpretation for 1910.303(h).

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

Who can access high-voltage installations in locked areas?

Installations in a vault, room, closet or fenced area with access controlled by lock and key or other approved means are considered accessible to qualified persons only.

How tall must an outdoor fence be?

Not less than 2.13 m (7.0 ft), or 1.80 m (6.0 ft) or more of fence fabric plus a 305-mm (1-ft) or more extension with three or more strands of barbed wire or equivalent.

What about indoor installations open to others?

They must be metal-enclosed or in a vault or locked area, and associated equipment must be marked with caution signs.

About this page

Sources