29 CFR 1910 · General Industry · Subpart S

1910.304(f): Overcurrent Protection

By Black Belt Safety Editorial Team Official text as of October 15, 2026 Data updated October 21, 2026 6 min read

In plain words:

Employers must protect conductors and equipment from overcurrent according to their ability to safely carry current. For circuits 600 volts or less, the rule sets requirements for disconnecting means ahead of fuses, keeps overcurrent devices readily accessible and away from physical damage and easily ignitable material, and requires fuses and breakers to be located or shielded so workers are not burned or struck when they operate.

Key takeaways

  • 1910.304(f) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
  • OSHA cited it 136 times in the last 3 years, in 136 inspections, with $197,006 in current penalties.
  • Most citations: NY (25), VA (23), HI (18).
  • Related part: 1910.304(f)(1) 600 volts, nominal, or less (136 citations).
  • Free 5-minute toolbox talk for your crew below.
136citations, 3 years
$197,006current penalties
136inspections
0linked injury cases
In this article
  1. What this rule covers
  2. Official text
  3. Where and how often it was cited
  4. Free toolbox talk
  5. OSHA interpretation letters
  6. Related parts of this rule
  7. Get your crew competent
  8. Frequently asked questions
  9. About this page

What this rule covers

29 CFR 1910.304(f) ("Overcurrent protection") is one requirement inside 1910.304 Wiring design and protection, an OSHA general industry standard (Part 1910, Subpart S). It includes 19 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(f) Overcurrent protection — 136 citations

(1) 600 volts, nominal, or less. The following requirements apply to overcurrent protection of circuits rated 600 volts, nominal, or less. Open (f)(1) 136 citations

(i) Conductors and equipment shall be protected from overcurrent in accordance with their ability to safely conduct current. 2 citations

(ii) Except for motor running overload protection, overcurrent devices may not interrupt the continuity of the grounded conductor unless all conductors of the circuit are opened simultaneously.

(iii) A disconnecting means shall be provided on the supply side of all fuses in circuits over 150 volts to ground and cartridge fuses in circuits of any voltage where accessible to other than qualified persons so that each individual circuit containing fuses can be independently disconnected from the source of power. However, a current-limiting device without a disconnecting means is permitted on the supply side of the service disconnecting means. In addition, a single disconnecting means is permitted on the supply side of more than one set of fuses as permitted by the exception in § 1910.305(j)(4)(vi) for group operation of motors, and a single disconnecting means is permitted for fixed electric space-heating equipment.

(iv) Overcurrent devices shall be readily accessible to each employee or authorized building management personnel. These overcurrent devices may not be located where they will be exposed to physical damage or in the vicinity of easily ignitable material. Open (f)(1)(iv) 101 citations

(v) Fuses and circuit breakers shall be so located or shielded that employees will not be burned or otherwise injured by their operation. Handles or levers of circuit breakers, and similar parts that may move suddenly in such a way that persons in the vicinity are likely to be injured by being struck by them, shall be guarded or isolated. 1 citations

(vi) Circuit breakers shall clearly indicate whether they are in the open (off) or closed (on) position. 1 citations

(vii) Where circuit breaker handles on switchboards are operated vertically rather than horizontally or rotationally, the up position of the handle shall be the closed (on) position.

(viii) Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits shall be listed and marked “SWD.” Open (f)(1)(viii) 31 citations

(ix) A circuit breaker with a straight voltage rating, such as 240 V or 480 V, may only be installed in a circuit in which the nominal voltage between any two conductors does not exceed the circuit breaker's voltage rating. A two-pole circuit breaker may not be used for protecting a 3-phase, corner-grounded delta circuit unless the circuit breaker is marked 1Φ—3Φ to indicate such suitability. A circuit breaker with a slash rating, such as 120/240 V or 480Y/277 V, may only be installed in a circuit where the nominal voltage of any conductor to ground does not exceed the lower of the two values of the circuit breaker's voltage rating and the nominal voltage between any two conductors does not exceed the higher value of the circuit breaker's voltage rating.

(2) Feeders and branch circuits over 600 volts, nominal. The following requirements apply to feeders and branch circuits energized at more than 600 volts, nominal:

(i) Feeder and branch-circuit conductors shall have overcurrent protection in each ungrounded conductor located at the point where the conductor receives its supply or at a location in the circuit determined under engineering supervision;

(A) Circuit breakers used for overcurrent protection of three-phase circuits shall have a minimum of three overcurrent relays operated from three current transformers. On three-phase, three-wire circuits, an overcurrent relay in the residual circuit of the current transformers may replace one of the phase relays. An overcurrent relay, operated from a current transformer that links all phases of a three-phase, three-wire circuit, may replace the residual relay and one other phase-conductor current transformer. Where the neutral is not grounded on the load side of the circuit, the current transformer may link all three phase conductors and the grounded circuit conductor (neutral); and

(B) If fuses are used for overcurrent protection, a fuse shall be connected in series with each ungrounded conductor;

(ii) Each protective device shall be capable of detecting and interrupting all values of current that can occur at its location in excess of its trip setting or melting point;

(iii) The operating time of the protective device, the available short-circuit current, and the conductor used shall be coordinated to prevent damaging or dangerous temperatures in conductors or conductor insulation under short-circuit conditions; and

(iv) The following additional requirements apply to feeders only:

(A) The continuous ampere rating of a fuse may not exceed three times the ampacity of the conductors. The long-time trip element setting of a breaker or the minimum trip setting of an electronically actuated fuse may not exceed six times the ampacity of the conductor. For fire pumps, conductors may be protected for short circuit only; and

(B) Conductors tapped to a feeder may be protected by the feeder overcurrent device where that overcurrent device also protects the tap conductor.

Source: eCFR, text current as of 2026-10-15. Read all of 1910.304.

Where and how often it was cited

YearCitations
20239
202454
202549
202624

Top states: NY (25), VA (23), HI (18), TX (16), PR (12)

Largest penalties

EmployerLocationPenalty for this rule
FAMILY DOLLAR STORES OF VIRGINIA INC.COVINGTON, VA$25,519
THE GOODYEAR TIRE & RUBBER COMPANYDANVILLE, VA$10,220
PYRAMID SPA PRODUCTS, LLC.BROOKSHIRE, TX$10,141
CHART INC.BEASLEY, TX$7,835
RACK BUILDERS, INC.QUINCY, IL$7,661

Free toolbox talk

A 5-minute crew talk on 1910.304(f), plus alerts when this rule changes. Free.




OSHA interpretation letters

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey, Dana Reyes

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

Where may circuit breakers and fuses be located?

They must be readily accessible to employees or authorized building management, and not where they are exposed to physical damage or near easily ignitable material.

Do breaker handles need guarding?

Handles or levers that may move suddenly in a way likely to injure people nearby must be guarded or isolated.

What is the basic overcurrent rule?

Conductors and equipment must be protected from overcurrent in accordance with their ability to safely conduct current.

About this page

Sources