1910.331: Electrical Safe Work Practices Scope
This section sets who and what the electrical safe work practice rules in 1910.331 through 1910.335 cover. They apply to both qualified and unqualified persons working on, near or with premises wiring, wiring that connects to the supply, other outside conductors and optical fiber cable installed with electric conductors, but not to qualified persons working on utility generation, transmission and distribution installations.
Key takeaways
- 1910.331 is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
- Most-cited part: 1910.331(c)(1) Generation, transmission, and distribution installations.
- Free 5-minute toolbox talk for your crew below.
In this article
What this rule covers
29 CFR 1910.331, "Scope", is an OSHA general industry standard (Part 1910, Subpart S). It has 13 numbered paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.
Official text
Show the full text of 1910.331 (13 paragraphs)
(a) Covered work by both qualified and unqualified persons. The provisions of §§ 1910.331 through 1910.335 cover electrical safety-related work practices for both qualified persons (those who have training in avoiding the electrical hazards of working on or near exposed energized parts) and unqualified persons (those with little or no such training) working on, near, or with the following installations: Open (a)
(1) Premises wiring. Installations of electric conductors and equipment within or on buildings or other structures, and on other premises such as yards, carnival, parking, and other lots, and industrial substations;
(2) Wiring for connection to supply. Installations of conductors that connect to the supply of electricity; and
(3) Other wiring. Installations of other outside conductors on the premises.
(4) Optical fiber cable. Installations of optical fiber cable where such installations are made along with electric conductors.
See § 1910.399 for the definition of “qualified person.” See § 1910.332 for training requirements that apply to qualified and unqualified persons.
(b) Other covered work. The provisions of §§ 1910.331 through 1910.335 also cover: Open (b)
(1) Work performed by unqualified persons on, near, or with the installations listed in paragraphs (c)(1) through (4) of this section; and
(2) Work performed by qualified persons near the installations listed in paragraphs (c)(1) through (c)(4) of this section when that work is not on or directly associated with those installations.
(c) Excluded work by qualified persons. The provisions of §§ 1910.331 through 1910.335 do not apply to work performed by qualified persons on or directly associated with the following installations: Open (c)
(1) Generation, transmission, and distribution installations. Installations for the generation, control, transformation, transmission, and distribution of electric energy (including communication and metering) located in buildings used for such purposes or located outdoors. Open (c)(1)
Work on or directly associated with installations of utilization equipment used for purposes other than generating, transmitting, or distributing electric energy (such as installations which are in office buildings, warehouses, garages, machine shops, or recreational buildings, or other utilization installations which are not an integral part of a generating installation, substation, or control center) is covered under paragraph (a)(1) of this section.
For work on or directly associated with utilization installations, an employer who complies with the work practices of § 1910.269 (electric power generation, transmission, and distribution) will be deemed to be in compliance with §§ 1910.333(c) and 1910.335. However, the requirements of §§ 1910.332, 1910.333(a), 1910.333(b), and 1910.334 apply to all work on or directly associated with utilization installations, regardless of whether the work is performed by qualified or unqualified persons.
Work on or directly associated with generation, transmission, or distribution installations includes:
(1) Work performed directly on such installations, such as repairing overhead or underground distribution lines or repairing a feed-water pump for the boiler in a generating plant.
(2) Work directly associated with such installations, such as line-clearance tree trimming and replacing utility poles, when that work is covered by § 1910.269 (see § 1910.269(a)(1)(i)(D) and (E) and the definition of “line-clearance tree trimming” in § 1910.269(x)).
(3) Work on electric utilization circuits in a generating plant provided that:
(A) Such circuits are commingled with installations of power generation equipment or circuits, and
(B) The generation equipment or circuits present greater electrical hazards than those posed by the utilization equipment or circuits (such as exposure to higher voltages or lack of overcurrent protection).
This work is covered by § 1910.269.
(2) Communications installations. Installations of communication equipment to the extent that the work is covered under § 1910.268.
(3) Installations in vehicles. Installations in ships, watercraft, railway rolling stock, aircraft, or automotive vehicles other than mobile homes and recreational vehicles.
(4) Railway installations. Installations of railways for generation, transformation, transmission, or distribution of power used exclusively for operation of rolling stock or installations of railways used exclusively for signaling and communication purposes.
[55 FR 32016, Aug. 6, 1990, as amended at 59 FR 4476, Jan. 31, 1994; 79 FR 20692, Apr. 11, 2014; 80 FR 60039, Oct. 5, 2015]
Source: eCFR, text current as of 2026-10-15.
Free toolbox talk
A 5-minute crew talk on 1910.331, plus alerts when this rule changes. Free.
OSHA interpretation letters
- Clarification of the applicability of 29 CFR 1910.269 to line-clearance tree trimming (2015-02-18)
- 29 CFR 1910.269 and 29 CFR Part 1926, Subpart V-Enforcement dates (2015-02-18)
- Protection of workers operating mechanical equipment near overhead power lines (1999-12-07)
- Training and PPE for employees performing tests on equipment. (1998-06-22)
- Review of Panduit's lockout/tagout training video. (1992-11-19)
- Minimally acceptable levels of illumination; Resistor banks on overhead cranes; Overhead lines; Protective gloves on energized equipment. (1992-04-28)
- New electrical standards relating to sugar beet plant and sawmill (1991-06-14)
- Hazard communication program on site and standard covering electrical installation, maintenance or repair. (1990-10-18)
Most-cited parts of this rule
- 1910.331(c)(1) Generation, transmission, and distribution installations
- 1910.331(a) Covered work by both qualified and unqualified persons
- 1910.331(b) Other covered work
- 1910.331(c) Excluded work by qualified persons
Get your crew competent
Trainers on Black Belt Safety: Marc Harvey, Dana Reyes
Trainers and suppliers: feature your business on this rule for $25/month.
Frequently asked questions
Who is covered by the electrical safe work practice rules?
Both qualified persons, trained to avoid hazards of exposed energized parts, and unqualified persons with little or no such training.
Is optical fiber cable covered?
Yes, when it is installed along with electric conductors.
What work is excluded?
Work by qualified persons on or directly associated with installations for generation, transmission and distribution of power, among others listed.
About this page
Sources
- 29 CFR 1910.331 (eCFR), text current as of 2026-10-15
- U.S. Department of Labor enforcement data: OSHA inspections, citations and accident records, copied nightly
3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.