29 CFR 1910 · General Industry · Subpart S

1910.333(a): Electrical Safe Work Practices: Deenergize First

By Black Belt Safety Editorial Team Official text as of October 15, 2026 Data updated October 20, 2026 4 min read

In plain words:

Employers must use safety-related work practices to prevent shock and other injuries when work is done on or near equipment or circuits that are or may be energized. Live parts an employee may be exposed to must be deenergized before work, unless the employer can show deenergizing creates more hazards or is infeasible. Parts under 50 volts to ground need not be deenergized if there is no increased exposure to burns or arc explosion.

Key takeaways

  • 1910.333(a) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
  • OSHA cited it 190 times in the last 3 years, in 184 inspections, with $1,219,809 in current penalties.
  • 15 deaths are linked to inspections that cited this rule.
  • Most citations: OH (20), MI (15), MA (15).
  • Related part: 1910.333(a)(1) Deenergized parts (113 citations).
  • Free 5-minute toolbox talk for your crew below.
190citations, 3 years
$1,219,809current penalties
184inspections
15linked deaths
In this article
  1. What this rule covers
  2. Official text
  3. Injuries linked to this rule
  4. Where and how often it was cited
  5. Free toolbox talk
  6. OSHA interpretation letters
  7. Related parts of this rule
  8. Get your crew competent
  9. Frequently asked questions
  10. About this page

What this rule covers

29 CFR 1910.333(a) ("General") is one requirement inside 1910.333 Selection and use of work practices, an OSHA general industry standard (Part 1910, Subpart S). It includes 2 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(a) General. Safety-related work practices shall be employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work is performed near or on equipment or circuits which are or may be energized. The specific safety-related work practices shall be consistent with the nature and extent of the associated electrical hazards. 190 citations

(1) Deenergized parts. Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs. Open (a)(1) 113 citations

Examples of increased or additional hazards include interruption of life support equipment, deactivation of emergency alarm systems, shutdown of hazardous location ventilation equipment, or removal of illumination for an area.

Examples of work that may be performed on or near energized circuit parts because of infeasibility due to equipment design or operational limitations include testing of electric circuits that can only be performed with the circuit energized and work on circuits that form an integral part of a continuous industrial process in a chemical plant that would otherwise need to be completely shut down in order to permit work on one circuit or piece of equipment.

Work on or near deenergized parts is covered by paragraph (b) of this section.

(2) Energized parts. If the exposed live parts are not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices shall be used to protect employees who may be exposed to the electrical hazards involved. Such work practices shall protect employees against contact with energized circuit parts directly with any part of their body or indirectly through some other conductive object. The work practices that are used shall be suitable for the conditions under which the work is to be performed and for the voltage level of the exposed electric conductors or circuit parts. Specific work practice requirements are detailed in paragraph (c) of this section. Open (a)(2) 30 citations

Source: eCFR, text current as of 2026-10-15. Read all of 1910.333.

Injuries linked to this rule

15 deaths are linked to inspections where OSHA cited 1910.333(a).

Employee is electrocuted while replacing fuses on electrical
2025-02-25 · Fatal · NEWARK, NJ

At approximately 4:20 a.m. on February 25, 2025, Employee #1 was working on an AirTrain switch electrical panel, attempting to replace blown fuses. During the task, the employee came into contact with energized components and received a 600-volt electric shock. Employee #1 was fatally electrocuted.

See all 15 cases

Full case list with employer, penalty, filters and download is part of OSHA Data (Purple Belt).

Unlock with Purple Belt

Where and how often it was cited

YearCitations
202312
202467
202571
202640

Top states: OH (20), MI (15), MA (15), TX (13), NY (11)

Largest penalties

EmployerLocationPenalty for this rule
S.J. SERVICESBOSTON, MA$165,514
FUYAO GLASS AMERICA INC.MORAINE, OH$70,938
WESTERN EXTRUSIONS CORPORATIONCARROLLTON, TX$16,550
ALSTOM TRANSPORTATION USA INC.NEWARK, NJ$16,550
MIDDLETON INC.LITTLE ROCK, AR$16,550

Free toolbox talk

A 5-minute crew talk on 1910.333(a), plus alerts when this rule changes. Free.




OSHA interpretation letters

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey, Dana Reyes

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

When can work be done on live parts?

Only if the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations.

Must parts under 50 volts be deenergized?

Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs.

What is an example of an increased hazard?

Interruption of life support equipment, deactivation of emergency alarms, shutdown of hazardous location ventilation, or removal of lighting for an area.

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Scroll to top