1910.333(b)(2)(iv)(B): Testing to Verify Circuits Are Deenergized

By Black Belt Safety Editorial Team Official text as of octubre 15, 2026 Data updated octubre 20, 2026 3 min read

In plain words:

A qualified person must use test equipment to test circuit elements and equipment parts employees will be exposed to and verify they are deenergized. The test must also check for induced voltage or unrelated backfeed. For circuits over 600 volts, nominal, the test equipment must be checked for proper operation immediately before and immediately after the test.

Key takeaways

  • 1910.333(b)(2)(iv)(B) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
  • OSHA cited it 24 times in the last 3 years, in 24 inspections, with $114,855 in current penalties.
  • 3 deaths are linked to inspections that cited this rule.
  • Most citations: VA (5), OK (3), MA (3).
  • Related part: 1910.333(b) Working on or near exposed deenergized parts (225 citations).
  • Free 5-minute toolbox talk for your crew below.
24citations, 3 years
$114,855current penalties
24inspections
3linked deaths
In this article
  1. What this rule covers
  2. Official text
  3. Injuries linked to this rule
  4. Where and how often it was cited
  5. Free toolbox talk
  6. OSHA interpretation letters
  7. Related parts of this rule
  8. Get your crew competent
  9. Frequently asked questions
  10. About this page

What this rule covers

29 CFR 1910.333(b)(2)(iv)(B) is one requirement inside 1910.333 Selection and use of work practices, an OSHA general industry standard (Part 1910, Subpart S). The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(B) A qualified person shall use test equipment to test the circuit elements and electrical parts of equipment to which employees will be exposed and shall verify that the circuit elements and equipment parts are deenergized. The test shall also determine if any energized condition exists as a result of inadvertently induced voltage or unrelated voltage backfeed even though specific parts of the circuit have been deenergized and presumed to be safe. If the circuit to be tested is over 600 volts, nominal, the test equipment shall be checked for proper operation immediately before and immediately after this test. 24 citations

Source: eCFR, text current as of 2026-10-15. Read all of 1910.333.

Injuries linked to this rule

3 deaths are linked to inspections where OSHA cited 1910.333(b)(2)(iv)(B).

Employee is electrocuted while replacing fuses on electrical
2025-02-25 · Fatal · NEWARK, NJ

At approximately 4:20 a.m. on February 25, 2025, Employee #1 was working on an AirTrain switch electrical panel, attempting to replace blown fuses. During the task, the employee came into contact with energized components and received a 600-volt electric shock. Employee #1 was fatally electrocuted.

See all 3 cases

Full case list with employer, penalty, filters and download is part of OSHA Data (Purple Belt).

Unlock with Purple Belt

Where and how often it was cited

YearCitations
202410
202510
20264

Top states: VA (5), OK (3), MA (3), TX (3), MI (3)

Largest penalties

EmployerLocationPenalty for this rule
UNIVERSITY OF VIRGINIACHARLOTTESVILLE, VA$16,285
UPS INSTRUMENT & ELECTRICAL SERVICES, LLCTULSA, OK$16,131
COMMUNICATIONS TEST DESIGN, INC.CAMBRIDGE, MA$16,131
NIDRA LLCCHESAPEAKE, VA$15,875
SOUTHERN TECHNICAL INSTITUTE, LLCTAMPA, FL$11,823

Free toolbox talk

A 5-minute crew talk on 1910.333(b)(2)(iv)(B), plus alerts when this rule changes. Free.




OSHA interpretation letters

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey, Dana Reyes

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

Who must test for absence of voltage?

A qualified person.

What must the test check besides the circuit itself?

Any energized condition from inadvertently induced voltage or unrelated voltage backfeed.

What extra step applies over 600 volts?

The test equipment must be checked for proper operation immediately before and immediately after the test.

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Desplácese hacia arriba