1910.333(b)(2)(v): Reenergizing equipment
Key takeaways
- 1910.333(b)(2)(v) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
- OSHA cited it 4 times in the last 3 years, in 4 inspections, with $0 in current penalties.
- Related part: 1910.333(b) Working on or near exposed deenergized parts (225 citations).
- Free 5-minute toolbox talk for your crew below.
In this article
What this rule covers
29 CFR 1910.333(b)(2)(v) ("Reenergizing equipment") is one requirement inside 1910.333 Selection and use of work practices, an OSHA general industry standard (Part 1910, Subpart S). It includes 4 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.
Official text
(v) Reenergizing equipment. These requirements shall be met, in the order given, before circuits or equipment are reenergized, even temporarily. 4 citations
(A) A qualified person shall conduct tests and visual inspections, as necessary, to verify that all tools, electrical jumpers, shorts, grounds, and other such devices have been removed, so that the circuits and equipment can be safely energized. 2 citations
(B) Employees exposed to the hazards associated with reenergizing the circuit or equipment shall be warned to stay clear of circuits and equipment. 1 citations
(C) Each lock and tag shall be removed by the employee who applied it or under his or her direct supervision. However, if this employee is absent from the workplace, then the lock or tag may be removed by a qualified person designated to perform this task provided that: Open (b)(2)(v)(c)
(1) The employer ensures that the employee who applied the lock or tag is not available at the workplace, and
(2) The employer ensures that the employee is aware that the lock or tag has been removed before he or she resumes work at that workplace.
(D) There shall be a visual determination that all employees are clear of the circuits and equipment.
Source: eCFR, text current as of 2026-10-15. Read all of 1910.333.
Where and how often it was cited
Free toolbox talk
A 5-minute crew talk on 1910.333(b)(2)(v), plus alerts when this rule changes. Free.
OSHA interpretation letters
- Evaluation of proposed modifications to the Bureau of Prisons' Lockout/Tagout (LOTO) procedures. (2000-07-10)
Related parts of this rule
- 1910.333(b) Working on or near exposed deenergized parts 225 citations
- 1910.333(b)(2) Lockout and tagging 223 citations
- 1910.333(b)(2)(i) Procedures 61 citations
- 1910.333(b)(2)(iv) 31 citations
- 1910.333(b)(2)(ii) Deenergizing equipment 31 citations
- 1910.333(b)(2)(iv)(B) 24 citations
- 1910.333(b)(2)(iii) Application of locks and tags 20 citations
- 1910.333(b)(2)(iii)(A) 18 citations
- 1910.333(b)(2)(ii)(A) 18 citations
- 1910.333(b)(2)(ii)(B) 12 citations
- 1910.333(b)(1) Application 2 citations
- 1910.333(b)(2)(iv)(A) 2 citations
Get your crew competent
Trainers on Black Belt Safety: Marc Harvey, Dana Reyes
Trainers and suppliers: feature your business on this rule for $25/month.
About this page
Sources
- 29 CFR 1910.333 (eCFR), text current as of 2026-10-15
- U.S. Department of Labor enforcement data: OSHA inspections, citations and accident records, copied nightly; data as of 2026-10-20