29 CFR 1910 · General Industry · Subpart S

1910.333(b): Working on or Near Exposed Deenergized Parts

By Black Belt Safety Editorial Team Official text as of octubre 15, 2026 Data updated octubre 20, 2026 7 min read

In plain words:

Employers must treat deenergized parts that have not been locked out or tagged as energized. While any employee is exposed to contact with parts of fixed electric equipment or circuits that have been deenergized, the circuits feeding them must be locked out, tagged or both, following the steps in order, with a written copy of the procedures kept available for employees and OSHA.

Key takeaways

  • 1910.333(b) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
  • OSHA cited it 225 times in the last 3 years, in 177 inspections, with $731,535 in current penalties.
  • 7 deaths are linked to inspections that cited this rule.
  • Most citations: VA (25), MI (18), TX (15).
  • Related part: 1910.333(b)(2) Lockout and tagging (223 citations).
  • Free 5-minute toolbox talk for your crew below.
225citations, 3 years
$731,535current penalties
177inspections
7linked deaths
In this article
  1. What this rule covers
  2. Official text
  3. Injuries linked to this rule
  4. Where and how often it was cited
  5. Free toolbox talk
  6. OSHA interpretation letters
  7. Related parts of this rule
  8. Get your crew competent
  9. Frequently asked questions
  10. About this page

What this rule covers

29 CFR 1910.333(b) ("Working on or near exposed deenergized parts") is one requirement inside 1910.333 Selection and use of work practices, an OSHA general industry standard (Part 1910, Subpart S). It includes 22 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(b) Working on or near exposed deenergized parts — 225 citations

(1) Application. This paragraph applies to work on exposed deenergized parts or near enough to them to expose the employee to any electrical hazard they present. Conductors and parts of electric equipment that have been deenergized but have not been locked out or tagged in accordance with paragraph (b) of this section shall be treated as energized parts, and paragraph (c) of this section applies to work on or near them. Open (b)(1) 2 citations

(2) Lockout and tagging. While any employee is exposed to contact with parts of fixed electric equipment or circuits which have been deenergized, the circuits energizing the parts shall be locked out or tagged or both in accordance with the requirements of this paragraph. The requirements shall be followed in the order in which they are presented (i.e., paragraph (b)(2)(i) first, then paragraph (b)(2)(ii), etc.). Open (b)(2) 223 citations

As used in this section, fixed equipment refers to equipment fastened in place or connected by permanent wiring methods.

Lockout and tagging procedures that comply with paragraphs (c) through (f) of § 1910.147 will also be deemed to comply with paragraph (b)(2) of this section provided that:

(1) The procedures address the electrical safety hazards covered by this Subpart; and

(2) The procedures also incorporate the requirements of paragraphs (b)(2)(iii)(D) and (b)(2)(iv)(B) of this section.

(i) Procedures. The employer shall maintain a written copy of the procedures outlined in paragraph (b)(2) and shall make it available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives. Open (b)(2)(i) 61 citations

The written procedures may be in the form of a copy of paragraph (b) of this section.

(ii) Deenergizing equipment. Open (b)(2)(ii) 31 citations

(A) Safe procedures for deenergizing circuits and equipment shall be determined before circuits or equipment are deenergized. Open (b)(2)(ii)(a) 18 citations

(B) The circuits and equipment to be worked on shall be disconnected from all electric energy sources. Control circuit devices, such as push buttons, selector switches, and interlocks, may not be used as the sole means for deenergizing circuits or equipment. Interlocks for electric equipment may not be used as a substitute for lockout and tagging procedures. Open (b)(2)(ii)(b) 12 citations

(C) Stored electric energy which might endanger personnel shall be released. Capacitors shall be discharged and high capacitance elements shall be short-circuited and grounded, if the stored electric energy might endanger personnel.

If the capacitors or associated equipment are handled in meeting this requirement, they shall be treated as energized.

(D) Stored non-electrical energy in devices that could reenergize electric circuit parts shall be blocked or relieved to the extent that the circuit parts could not be accidentally energized by the device. Open (b)(2)(ii)(d) 1 citations

(iii) Application of locks and tags. Open (b)(2)(iii) 20 citations

(A) A lock and a tag shall be placed on each disconnecting means used to deenergize circuits and equipment on which work is to be performed, except as provided in paragraphs (b)(2)(iii)(C) and (b)(2)(iii)(E) of this section. The lock shall be attached so as to prevent persons from operating the disconnecting means unless they resort to undue force or the use of tools. Open (b)(2)(iii)(a) 18 citations

(B) Each tag shall contain a statement prohibiting unauthorized operation of the disconnecting means and removal of the tag. Open (b)(2)(iii)(b) 1 citations

(C) If a lock cannot be applied, or if the employer can demonstrate that tagging procedures will provide a level of safety equivalent to that obtained by the use of a lock, a tag may be used without a lock. 1 citations

(D) A tag used without a lock, as permitted by paragraph (b)(2)(iii)(C) of this section, shall be supplemented by at least one additional safety measure that provides a level of safety equivalent to that obtained by the use of a lock. Examples of additional safety measures include the removal of an isolating circuit element, blocking of a controlling switch, or opening of an extra disconnecting device. Open (b)(2)(iii)(d)

(E) A lock may be placed without a tag only under the following conditions: Open (b)(2)(iii)(e)

(1) Only one circuit or piece of equipment is deenergized, and

(2) The lockout period does not extend beyond the work shift, and

(3) Employees exposed to the hazards associated with reenergizing the circuit or equipment are familiar with this procedure.

(iv) Verification of deenergized condition. The requirements of this paragraph shall be met before any circuits or equipment can be considered and worked as deenergized. Open (b)(2)(iv) 31 citations

(A) A qualified person shall operate the equipment operating controls or otherwise verify that the equipment cannot be restarted. Open (b)(2)(iv)(a) 2 citations

(B) A qualified person shall use test equipment to test the circuit elements and electrical parts of equipment to which employees will be exposed and shall verify that the circuit elements and equipment parts are deenergized. The test shall also determine if any energized condition exists as a result of inadvertently induced voltage or unrelated voltage backfeed even though specific parts of the circuit have been deenergized and presumed to be safe. If the circuit to be tested is over 600 volts, nominal, the test equipment shall be checked for proper operation immediately before and immediately after this test. Open (b)(2)(iv)(b) 24 citations

(v) Reenergizing equipment. These requirements shall be met, in the order given, before circuits or equipment are reenergized, even temporarily. Open (b)(2)(v) 4 citations

(A) A qualified person shall conduct tests and visual inspections, as necessary, to verify that all tools, electrical jumpers, shorts, grounds, and other such devices have been removed, so that the circuits and equipment can be safely energized. 2 citations

(B) Employees exposed to the hazards associated with reenergizing the circuit or equipment shall be warned to stay clear of circuits and equipment. 1 citations

(C) Each lock and tag shall be removed by the employee who applied it or under his or her direct supervision. However, if this employee is absent from the workplace, then the lock or tag may be removed by a qualified person designated to perform this task provided that: Open (b)(2)(v)(c)

(1) The employer ensures that the employee who applied the lock or tag is not available at the workplace, and

(2) The employer ensures that the employee is aware that the lock or tag has been removed before he or she resumes work at that workplace.

(D) There shall be a visual determination that all employees are clear of the circuits and equipment.

Source: eCFR, text current as of 2026-10-15. Read all of 1910.333.

Injuries linked to this rule

7 deaths are linked to inspections where OSHA cited 1910.333(b).

Employee is electrocuted while replacing fuses on electrical
2025-02-25 · Fatal · NEWARK, NJ

At approximately 4:20 a.m. on February 25, 2025, Employee #1 was working on an AirTrain switch electrical panel, attempting to replace blown fuses. During the task, the employee came into contact with energized components and received a 600-volt electric shock. Employee #1 was fatally electrocuted.

See all 7 cases

Full case list with employer, penalty, filters and download is part of OSHA Data (Purple Belt).

Unlock with Purple Belt

Where and how often it was cited

YearCitations
202310
202479
202582
202654

Top states: VA (25), MI (18), TX (15), CT (14), OK (11)

Largest penalties

EmployerLocationPenalty for this rule
MILLISON CASTING TECHNOLOGY, LLCSALLISAW, OK$33,100
SOUTHERN TECHNICAL INSTITUTE, LLCTAMPA, FL$23,646
CHIEF FABRICATIONGRAND ISLAND, NE$20,326
GEO PREP MID-CITY, INC.BATON ROUGE, LA$20,000
HIRSCH ELECTRIC LLCFAIRFAX, VA$18,299

Free toolbox talk

A 5-minute crew talk on 1910.333(b), plus alerts when this rule changes. Free.




OSHA interpretation letters

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey, Dana Reyes

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

Are deenergized parts safe if they are not locked out?

No. Parts that have been deenergized but not locked out or tagged under this paragraph must be treated as energized.

Must the lockout steps be done in a set order?

Yes. The requirements must be followed in the order in which they are presented.

Can a 1910.147 lockout program meet this rule?

Yes, if the procedures address the electrical hazards of this subpart and include the requirements of paragraphs (b)(2)(iii)(D) and (b)(2)(iv)(B).

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Desplácese hacia arriba