29 CFR 1910 · General Industry · Subpart S

1910.303(g)(1)(i): Working Space Around Live Electrical Equipment

By Black Belt Safety Editorial Team Official text as of October 15, 2026 Data updated October 20, 2026 3 min read

In plain words:

Employers must keep clear working space in front of electrical equipment that may be examined, adjusted, serviced or maintained while energized. The space must meet the depth in Table S-1, be at least as wide as the equipment or 30 inches, whichever is greater, allow equipment doors to open at least 90 degrees, and stay clear from the floor to the required height.

Key takeaways

  • 1910.303(g)(1)(i) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
  • OSHA cited it 436 times in the last 3 years, in 430 inspections, with $747,006 in current penalties.
  • 3 deaths are linked to inspections that cited this rule.
  • Most citations: VA (37), AK (34), TN (32).
  • Related part: 1910.303(g) 600 Volts, nominal, or less (3,265 citations).
  • Free 5-minute toolbox talk for your crew below.
436citations, 3 years
$747,006current penalties
430inspections
3linked deaths
In this article
  1. What this rule covers
  2. Official text
  3. Injuries linked to this rule
  4. Where and how often it was cited
  5. Free toolbox talk
  6. OSHA interpretation letters
  7. Related parts of this rule
  8. Get your crew competent
  9. Frequently asked questions
  10. About this page

What this rule covers

29 CFR 1910.303(g)(1)(i) is one requirement inside 1910.303 General, an OSHA general industry standard (Part 1910, Subpart S). It includes 3 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(i) Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized shall comply with the following dimensions, except as required or permitted elsewhere in this subpart: 436 citations

(A) The depth of the working space in the direction of access to live parts may not be less than indicated in Table S-1. Distances shall be measured from the live parts if they are exposed or from the enclosure front or opening if they are enclosed; Open (g)(1)(i)(a) 176 citations

(B) The width of working space in front of the electric equipment shall be the width of the equipment or 762 mm (30 in.), whichever is greater. In all cases, the working space shall permit at least a 90-degree opening of equipment doors or hinged panels; and Open (g)(1)(i)(b) 87 citations

(C) The work space shall be clear and extend from the grade, floor, or platform to the height required by paragraph (g)(1)(vi) of this section. However, other equipment associated with the electrical installation and located above or below the electric equipment may extend not more than 153 mm (6 in.) beyond the front of the electric equipment. Open (g)(1)(i)(c) 24 citations

Source: eCFR, text current as of 2026-10-15. Read all of 1910.303.

Injuries linked to this rule

3 deaths are linked to inspections where OSHA cited 1910.303(g)(1)(i).

Employee is found unresponsive and dies from natural causes
2024-12-27 · Fatal · LARGO, FL

At 3:20 p.m. on December 27, 2024, an employee returned from lunch and entered the water purifying system room (utility room) inside the establishment. Minuteslater, the employee was found unresponsive on the floor by a coworker. The medical examiner determined the cause of death as…

See all 3 cases

Full case list with employer, penalty, filters and download is part of OSHA Data (Purple Belt).

Unlock with Purple Belt

Where and how often it was cited

YearCitations
202328
2024169
2025166
202673

Top states: VA (37), AK (34), TN (32), UT (31), OR (22)

Largest penalties

EmployerLocationPenalty for this rule
FUYAO GLASS AMERICA INC.MORAINE, OH$99,300
KROGER COMPANY #359KINGWOOD, TX$57,044
DOLLAR TREE INCALEXANDRIA, VA$21,075
CASE FARMS PROCESSING, INC.WINESBURG, OH$16,550
MOUNTAINVIEW REGIONAL MEDICAL CENTERLAS CRUCES, NM$16,071

Free toolbox talk

A 5-minute crew talk on 1910.303(g)(1)(i), plus alerts when this rule changes. Free.




OSHA interpretation letters

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey, Dana Reyes

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

How wide must the working space in front of electrical equipment be?

The width of the equipment or 30 inches (762 mm), whichever is greater.

How far must equipment doors be able to open?

The working space must allow equipment doors or hinged panels to open at least 90 degrees.

Can other equipment stick out into the working space?

Associated electrical equipment above or below may extend not more than 6 inches (153 mm) beyond the front of the electric equipment.

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Scroll to top