29 CFR 1910 · General Industry · Subpart S

1910.303(g): Working space around electrical equipment (600 volts or less)

By Black Belt Safety Editorial Team Official text as of October 15, 2026 Data updated October 20, 2026 9 min read

In plain words:

For electrical equipment running at 600 volts or less, there must be enough clear working space around it for safe operation and maintenance. Where equipment may be worked on while energized, the space must be at least as deep as Table S-1 requires, at least 30 inches wide or the width of the equipment (whichever is greater), let doors and hinged panels open at least 90 degrees, and stay clear from the floor up. That working space may not be used for storage, and it needs at least one entrance. Live parts operating at 50 volts or more must be guarded against accidental contact.

Key takeaways

  • 1910.303(g) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
  • OSHA cited it 3,265 times in the last 3 years, in 3,073 inspections, with $5,619,585 in current penalties.
  • 8 deaths are linked to inspections that cited this rule.
  • Most citations: VA (226), NY (212), CT (202).
  • Related part: 1910.303(g)(1) Space about electric equipment (2,528 citations).
  • Free 5-minute toolbox talk for your crew below.
3,265citations, 3 years
$5,619,585current penalties
3,073inspections
8linked deaths
In this article
  1. What this rule covers
  2. Official text
  3. Injuries linked to this rule
  4. Where and how often it was cited
  5. Free toolbox talk
  6. OSHA interpretation letters
  7. Related parts of this rule
  8. Get your crew competent
  9. Frequently asked questions
  10. About this page

What this rule covers

29 CFR 1910.303(g) ("600 Volts, nominal, or less") is one requirement inside 1910.303 General, an OSHA general industry standard (Part 1910, Subpart S). It includes 25 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.

Official text

(g) 600 Volts, nominal, or less. This paragraph applies to electric equipment operating at 600 volts, nominal, or less to ground. 3,265 citations

(1) Space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment. Open (g)(1) 2,528 citations

(i) Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized shall comply with the following dimensions, except as required or permitted elsewhere in this subpart: Open (g)(1)(i) 436 citations

(A) The depth of the working space in the direction of access to live parts may not be less than indicated in Table S-1. Distances shall be measured from the live parts if they are exposed or from the enclosure front or opening if they are enclosed; Open (g)(1)(i)(a) 176 citations

(B) The width of working space in front of the electric equipment shall be the width of the equipment or 762 mm (30 in.), whichever is greater. In all cases, the working space shall permit at least a 90-degree opening of equipment doors or hinged panels; and Open (g)(1)(i)(b) 87 citations

(C) The work space shall be clear and extend from the grade, floor, or platform to the height required by paragraph (g)(1)(vi) of this section. However, other equipment associated with the electrical installation and located above or below the electric equipment may extend not more than 153 mm (6 in.) beyond the front of the electric equipment. Open (g)(1)(i)(c) 24 citations

(ii) Working space required by this standard may not be used for storage. When normally enclosed live parts are exposed for inspection or servicing, the working space, if in a passageway or general open space, shall be suitably guarded. Open (g)(1)(ii) 817 citations

(iii) At least one entrance of sufficient area shall be provided to give access to the working space about electric equipment. Open (g)(1)(iii) 24 citations

(iv) For equipment rated 1200 amperes or more and over 1.83 m (6.0 ft) wide, containing overcurrent devices, switching devices, or control devices, there shall be one entrance not less than 610 mm (24 in.) wide and 1.98 m (6.5 ft) high at each end of the working space, except that:

(A) Where the location permits a continuous and unobstructed way of exit travel, one means of exit is permitted; or

(B) Where the working space required by paragraph (g)(1)(i) of this section is doubled, only one entrance to the working space is required; however, the entrance shall be located so that the edge of the entrance nearest the equipment is the minimum clear distance given in Table S-1 away from such equipment.

(v) Illumination shall be provided for all working spaces about service equipment, switchboards, panelboards, and motor control centers installed indoors. Additional lighting fixtures are not required where the working space is illuminated by an adjacent light source. In electric equipment rooms, the illumination may not be controlled by automatic means only. Open (g)(1)(v) 11 citations

(vi) The minimum headroom of working spaces about service equipment, switchboards, panelboards, or motor control centers shall be as follows: 2 citations

(A) For installations built before August 13, 2007, 1.91 m (6.25 ft); and

(B) For installations built on or after August 13, 2007, 1.98 m (6.5 ft), except that where the electrical equipment exceeds 1.98 m (6.5 ft) in height, the minimum headroom may not be less than the height of the equipment. 1 citations

Table S-1—Minimum Depth of Clear Working Space at Electric Equipment, 600 V or Less

Nominal voltage to ground Minimum clear distance for condition 2 3
Condition A Condition B Condition C
m ft m ft m ft
0-150 1 0.9 1 3.0 1 0.9 1 3.0 0.9 3.0
151-600 1 0.9 1 3.0 1.0 3.5 1.2 4.0
Notes to Table S-1:
1. Minimum clear distances may be 0.7 m (2.5 ft) for installations built before April 16, 1981.
2. Conditions A, B, and C are as follows:
Condition A—Exposed live parts on one side and no live or grounded parts on the other side of the working space, or exposed live parts on both sides effectively guarded by suitable wood or other insulating material. Insulated wire or insulated busbars operating at not over 300 volts are not considered live parts.
Condition B—Exposed live parts on one side and grounded parts on the other side.
Condition C—Exposed live parts on both sides of the work space (not guarded as provided in Condition A) with the operator between.
3. Working space is not required in back of assemblies such as dead-front switchboards or motor control centers where there are no renewable or adjustable parts (such as fuses or switches) on the back and where all connections are accessible from locations other than the back. Where rear access is required to work on deenergized parts on the back of enclosed equipment, a minimum working space of 762 mm (30 in.) horizontally shall be provided.

(vii) Switchboards, panelboards, and distribution boards installed for the control of light and power circuits, and motor control centers shall be located in dedicated spaces and protected from damage. 7 citations

(A) For indoor installation, the dedicated space shall comply with the following: 1 citations

(1) The space equal to the width and depth of the equipment and extending from the floor to a height of 1.83 m (6.0 ft) above the equipment or to the structural ceiling, whichever is lower, shall be dedicated to the electrical installation. Unless isolated from equipment by height or physical enclosures or covers that will afford adequate mechanical protection from vehicular traffic or accidental contact by unauthorized personnel or that complies with paragraph (g)(1)(vii)(A)(2) of this section, piping, ducts, or equipment foreign to the electrical installation may not be located in this area;

(2) The space equal to the width and depth of the equipment shall be kept clear of foreign systems unless protection is provided to avoid damage from condensation, leaks, or breaks in such foreign systems. This area shall extend from the top of the electric equipment to the structural ceiling;

(3) Sprinkler protection is permitted for the dedicated space where the piping complies with this section; and

(4) Control equipment that by its very nature or because of other requirements in this subpart must be adjacent to or within sight of its operating machinery is permitted in the dedicated space.

A dropped, suspended, or similar ceiling that does not add strength to the building structure is not considered a structural ceiling.

(B) Outdoor electric equipment shall be installed in suitable enclosures and shall be protected from accidental contact by unauthorized personnel, or by vehicular traffic, or by accidental spillage or leakage from piping systems. No architectural appurtenance or other equipment may be located in the working space required by paragraph (g)(1)(i) of this section. 2 citations

(2) Guarding of live parts. Open (g)(2) 737 citations

(i) Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more shall be guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the following means: Open (g)(2)(i) 587 citations

(A) By location in a room, vault, or similar enclosure that is accessible only to qualified persons; 3 citations

(B) By suitable permanent, substantial partitions or screens so arranged so that only qualified persons will have access to the space within reach of the live parts. Any openings in such partitions or screens shall be so sized and located that persons are not likely to come into accidental contact with the live parts or to bring conducting objects into contact with them; 6 citations

(C) By placement on a suitable balcony, gallery, or platform so elevated and otherwise located as to prevent access by unqualified persons; or

(D) By elevation of 2.44 m (8.0 ft) or more above the floor or other working surface. 4 citations

(ii) In locations where electric equipment is likely to be exposed to physical damage, enclosures or guards shall be so arranged and of such strength as to prevent such damage. Open (g)(2)(ii) 132 citations

(iii) Entrances to rooms and other guarded locations containing exposed live parts shall be marked with conspicuous warning signs forbidding unqualified persons to enter. 6 citations

Source: eCFR, text current as of 2026-10-15. Read all of 1910.303.

Injuries linked to this rule

8 deaths are linked to inspections where OSHA cited 1910.303(g).

Employee is found unresponsive and dies from natural causes
2024-12-27 · Fatal · LARGO, FL

At 3:20 p.m. on December 27, 2024, an employee returned from lunch and entered the water purifying system room (utility room) inside the establishment. Minuteslater, the employee was found unresponsive on the floor by a coworker. The medical examiner determined the cause of death as…

See all 8 cases

Full case list with employer, penalty, filters and download is part of OSHA Data (Purple Belt).

Unlock with Purple Belt

Where and how often it was cited

YearCitations
2023236
20241,203
20251,131
2026695

Top states: VA (226), NY (212), CT (202), PA (173), TN (169)

Largest penalties

EmployerLocationPenalty for this rule
THE JAMES SKINNER LLCOMAHA, NE$132,500
NEBRASKA BEEF, LTDOMAHA, NE$117,194
FUYAO GLASS AMERICA INC.MORAINE, OH$99,300
THE KROGER COMPANYSTOCKBRIDGE, GA$76,043
KRISPY KREME DOUGHNUT CORPORATIONWEST ALLIS, WI$70,938

Free toolbox talk

A 5-minute crew talk on 1910.303(g), plus alerts when this rule changes. Free.




OSHA interpretation letters

Related parts of this rule

Get your crew competent

Trainers on Black Belt Safety: Marc Harvey, Dana Reyes

Trainers and suppliers: feature your business on this rule for $25/month.

Frequently asked questions

Can we store things in front of an electrical panel?

No. The working space required around electric equipment may not be used for storage.

How wide must the working space in front of a panel be?

The width of the equipment or 30 inches (762 mm), whichever is greater, and wide enough for doors or hinged panels to open at least 90 degrees.

How deep must the working space be?

At least the depth in Table S-1, which depends on the voltage and on what is on the opposite side of the space.

About this page

Sources

3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.

Written and reviewed by

Black Belt Safety Editorial Team

Site Safety Officer and Safety Professional

OSHA 30 · CPR · USACE CQM

Written and reviewed by the Black Belt Safety team. Every post is checked against the OSHA standard or agency source it cites.

Scroll to top