1910.333(c)(3): Working Near Overhead Power Lines
Before work near overhead lines starts, employers must have the lines deenergized and grounded by the operator of the circuit, or provide guarding, isolating or insulating that prevents any contact. Unqualified workers and their longest conductive object must stay at least 10 ft. from lines 50kV or below, plus 4 in. for every 10kV over 50kV.
Key takeaways
- 1910.333(c)(3) is part of OSHA's general industry standards (29 CFR Part 1910, Subpart S).
- OSHA cited it 110 times in the last 3 years, in 83 inspections, with $642,861 in current penalties.
- 13 deaths are linked to inspections that cited this rule.
- Most citations: FL (19), TX (15), NY (9).
- Related part: 1910.333(c) Working on or near exposed energized parts (200 citations).
- Free 5-minute toolbox talk for your crew below.
In this article
What this rule covers
29 CFR 1910.333(c)(3) ("Overhead lines") is one requirement inside 1910.333 Selection and use of work practices, an OSHA general industry standard (Part 1910, Subpart S). It includes 11 sub-paragraphs. The official text below is copied word for word from the Electronic Code of Federal Regulations (eCFR). The numbers, injury cases and training on this page show how OSHA enforces it on real job sites.
Official text
(3) Overhead lines. If work is to be performed near overhead lines, the lines shall be deenergized and grounded, or other protective measures shall be provided before work is started. If the lines are to be deenergized, arrangements shall be made with the person or organization that operates or controls the electric circuits involved to deenergize and ground them. If protective measures, such as guarding, isolating, or insulating are provided, these precautions shall prevent employees from contacting such lines directly with any part of their body or indirectly through conductive materials, tools, or equipment. 110 citations
The work practices used by qualified persons installing insulating devices on overhead power transmission or distribution lines are covered by § 1910.269 of this part, not by §§ 1910.332 through 1910.335 of this part. Under paragraph (c)(2) of this section, unqualified persons are prohibited from performing this type of work.
(i) Unqualified persons. Open (c)(3)(i) 46 citations
(A) When an unqualified person is working in an elevated position near overhead lines, the location shall be such that the person and the longest conductive object he or she may contact cannot come closer to any unguarded, energized overhead line than the following distances: Open (c)(3)(i)(a) 36 citations
(1) For voltages to ground 50kV or below—10 ft. (305 cm);
(2) For voltages to ground over 50kV—10 ft. (305 cm) plus 4 in. (10 cm) for every 10kV over 50kV.
(B) When an unqualified person is working on the ground in the vicinity of overhead lines, the person may not bring any conductive object closer to unguarded, energized overhead lines than the distances given in paragraph (c)(3)(i)(A) of this section. Open (c)(3)(i)(b) 10 citations
For voltages normally encountered with overhead power lines, objects which do not have an insulating rating for the voltage involved are considered to be conductive.
(ii) Qualified persons. When a qualified person is working in the vicinity of overhead lines, whether in an elevated position or on the ground, the person may not approach or take any conductive object without an approved insulating handle closer to exposed energized parts than shown in Table S-5 unless: 1 citations
(A) The person is insulated from the energized part (gloves, with sleeves if necessary, rated for the voltage involved are considered to be insulation of the person from the energized part on which work is performed), or
(B) The energized part is insulated both from all other conductive objects at a different potential and from the person, or
(C) The person is insulated from all conductive objects at a potential different from that of the energized part.
| Voltage range (phase to phase) | Minimum approach distance |
|---|---|
| 300V and less | Avoid contact. |
| Over 300V, not over 750V | 1 ft. 0 in. (30.5 cm). |
| Over 750V, not over 2kV | l ft. 6 in. (46 cm). |
| Over 2kV, not over 15kV | 2 ft. 0 in. (61 cm). |
| Over 15kV, not over 37kV | 3 ft. 0 in. (91 cm). |
| Over 37kV, not over 87.5kV | 3 ft. 6 in. (107 cm). |
| Over 87.5kV, not over 121kV | 4 ft. 0 in. (122 cm). |
| Over 121kV, not over 140kV | 4 ft. 6 in. (137 cm). |
(iii) Vehicular and mechanical equipment. Open (c)(3)(iii) 27 citations
(A) Any vehicle or mechanical equipment capable of having parts of its structure elevated near energized overhead lines shall be operated so that a clearance of 10 ft. (305 cm) is maintained. If the voltage is higher than 50kV, the clearance shall be increased 4 in. (10 cm) for every 10kV over that voltage. However, under any of the following conditions, the clearance may be reduced: Open (c)(3)(iii)(a) 26 citations
(1) If the vehicle is in transit with its structure lowered, the clearance may be reduced to 4 ft. (122 cm). If the voltage is higher than 50kV, the clearance shall be increased 4 in. (10 cm) for every 10kV over that voltage.
(2) If insulating barriers are installed to prevent contact with the lines, and if the barriers are rated for the voltage of the line being guarded and are not a part of or an attachment to the vehicle or its raised structure, the clearance may be reduced to a distance within the designed working dimensions of the insulating barrier.
(3) If the equipment is an aerial lift insulated for the voltage involved, and if the work is performed by a qualified person, the clearance (between the uninsulated portion of the aerial lift and the power line) may be reduced to the distance given in Table S-5.
(B) Employees standing on the ground may not contact the vehicle or mechanical equipment or any of its attachments, unless: 1 citations
(1) The employee is using protective equipment rated for the voltage; or
(2) The equipment is located so that no uninsulated part of its structure (that portion of the structure that provides a conductive path to employees on the ground) can come closer to the line than permitted in paragraph (c)(3)(iii) of this section.
(C) If any vehicle or mechanical equipment capable of having parts of its structure elevated near energized overhead lines is intentionally grounded, employees working on the ground near the point of grounding may not stand at the grounding location whenever there is a possibility of overhead line contact. Additional precautions, such as the use of barricades or insulation, shall be taken to protect employees from hazardous ground potentials, depending on earth resistivity and fault currents, which can develop within the first few feet or more outward from the grounding point.
Source: eCFR, text current as of 2026-10-15. Read all of 1910.333.
Injuries linked to this rule
13 deaths are linked to inspections where OSHA cited 1910.333(c)(3).
At 9:03 a.m. on February 6, 2025, Employee #1 working for a tree care company was trimming a tree from a self-propelled boom lift. Using a 21-foot aluminum pole saw to clear up the canopy on a residential property, he turned his body causing him…
Full case list with employer, penalty, filters and download is part of OSHA Data (Purple Belt).
Unlock with Purple BeltWhere and how often it was cited
| Year | Citations |
|---|---|
| 2023 | 5 |
| 2024 | 35 |
| 2025 | 44 |
| 2026 | 26 |
Top states: FL (19), TX (15), NY (9), MA (7), NJ (5)
Largest penalties
| Employer | Location | Penalty for this rule |
|---|---|---|
| GAGE TREE SERVICE LLC | CHUGIAK, AK | $99,308 |
| HUNT FOREST PRODUCTS, LLC | POLLOCK, LA | $33,100 |
| 108756 - DISCOUNT TREE CARE INC | MAYER, MN | $25,000 |
| OSMOSE UTILITIES SERVICES, INC. | WEST HELENA, AR | $21,508 |
| SERIOUS TREE SERVICES LLC | ACWORTH, GA | $16,943 |
Free toolbox talk
A 5-minute crew talk on 1910.333(c)(3), plus alerts when this rule changes. Free.
OSHA interpretation letters
None exist. OSHA has not published a letter of interpretation for 1910.333(c)(3).
Related parts of this rule
- 1910.333(c) Working on or near exposed energized parts 200 citations
- 1910.333(c)(2) Work on energized equipment 61 citations
- 1910.333(c)(3)(i) Unqualified persons 46 citations
- 1910.333(c)(3)(i)(A) 36 citations
- 1910.333(c)(3)(iii) Vehicular and mechanical equipment 27 citations
- 1910.333(c)(3)(iii)(A) 26 citations
- 1910.333(c)(7) Portable ladders 11 citations
- 1910.333(c)(6) Conductive materials and equipment 10 citations
- 1910.333(c)(3)(i)(B) 10 citations
Get your crew competent
Trainers on Black Belt Safety: Marc Harvey, Dana Reyes
Trainers and suppliers: feature your business on this rule for $25/month.
Frequently asked questions
What must be done before working near overhead lines?
The lines must be deenergized and grounded, or other protective measures must be provided before work starts.
Who arranges to deenergize the lines?
Arrangements must be made with the person or organization that operates or controls the circuits.
How close can an unqualified person get to a 50kV or lower line?
The person and the longest conductive object they may contact cannot come closer than 10 ft. (305 cm).
About this page
Sources
- 29 CFR 1910.333 (eCFR), text current as of 2026-10-15
- U.S. Department of Labor enforcement data: OSHA inspections, citations and accident records, copied nightly; data as of 2026-10-22
3-year window. Federal OSHA only; state-plan rules are not counted. Plain-language text is a summary, not legal advice; the official text controls. Black Belt Safety is not part of OSHA or the Department of Labor.